3250变压器测试

3250变压器测试
3250变压器测试

3250變壓器測試

測試參數

變壓器掃描測試圈數比Turn Ratio,相位Phase,圈數Turn,電感L,品質因子Q,漏電感LK ,平衡Balance,交流電阻ACR,電容Cp,直流電阻DCR,接腳短路Pin Short

測試信號

測試電壓Turn 10 mV~10 V,±10%,10mV/step

其它10 mV~2 V,±10%,10mV/step

測試頻率Turn 3200,3202,3250 , 3252 :1 kHz ~200 kHz,±0.02%

3300 , 3302 :1 kHz ~1 MHz,±0.02%

分辨率:0.01 Hz

其它3200/3202/3250,3252 :20Hz ~200kHz,±0.02%

3300,3302 :20Hz~1MHz,±0.02%

分辨率:0.001Hz <1 kHz

輸出阻抗Turn 10Ω, 當測試位準點2V 50Ω, 當測試位準>2 V

其它Constant=OFF:依電阻範圍不同而定

Constant=320X:100Ω+0.5%

Constant=107X:25Ω+0.5%

Constant=106X:100mA±5%1V設定,

電感負載小於10Ω,10Ω+10%,阻抗點10Ω

以上適用於325X 系列

Constant=OFF:依電阻範圍不同而定

Constant=320X:100 Ω+ 0 5%

以上適用於320X系列

測量顯示範圍

L,LK 0.00001uH ~9999.99H

C 0.00001pF ~999.999mF

Q,D 0.00001 ~99999

Z,X,R 0.00001 Ω~99.9999M Ω

Y 0.01nS ~99.9999 S

θ-90.00 。~+90.00 。

DCR 0.01m Ω‘0 99.999M Ω

Turn 0.01 ~99999.99 圈次電壓小於100 Vrms

Pin-Short 11 組, 接腳與接腳之間,

基本準確度

L,LK,C,Z,X,Y,R,DCR 0.1%若為AC參數1kHz

Q,D 0.00051kHz

θ0.03 °1kHz

Turn 0.5%1kHz

量測速度最快速

L , LK , C ,Z , X , Y ,R ,Q ,D , θ80 meas./sec .

DCR 50 meas./sec .

Turn 10 meas./sec .

判定方式

變壓器掃描測試各測試參數之良品/不良品判定由選購之處理器接口輸出顯示器320×240點矩陣LCD 液晶顯示器

修正功能開路Open /短路Short歸零,負載修正

內存15 組儀器設定,可藉由記憶卡擴充

等效電路模式串聯,並聯

觸發內部,手動,外部

一般規格

環境條件溫度:10 ℃~40 ℃溼度:10%~90% RH

消耗功率最大140 VA

電源需求90 ~125Vac 或190 ~250Vac 48 Hz ~62 Hz

重量約9 kg

尺寸(寬×高×深)430 ×180 ×320 mm

测试变压器的好坏方法

测试变压器的好坏方法(总2 页) -CAL-FENGHAI.-(YICAI)-Company One1 -CAL-本页仅作为文档封面,使用请直接删除

测试变压器的好坏方法 我们门禁电源中一般用的都是线性电源。线性电源就离不开变压器,变压器的功率器件,负荷带多了,接错线电流过大了,短路了就容易烧坏,但好多时候不是变压器烧坏,可能是电源板子坏了,所以判断电源的好坏首先判断变压器好坏的很关建。变压器重,返修时寄来寄去不好保护也浪费运费。今天来教各位怎样检测变压器的好坏。 1、断电测量:变压器是由两组线圈组成的。每组线圈就是由一条线绕成,所以量阻值可以判断好坏,220V输入线一般是红线,这组线阻值不能太小,用万用表量的时候不能短路,短路接近0Ω就坏了,红线一般阻值会在30Ω至200Ω,功率越大的阻值越小,功率小的阻值大。如出现开路,查看保险丝,如保险丝是好的,就是变压器输入线圈内部线断坏了。输出线一般是黑线或其他颜色,阻值都是接近0Ω,如阻值很大或开路就是线断坏了。 2、通电测量:通电用万用表交流AC档测试输出线,如有电压输出且稳定的是好的,如无电压输出或输出电压不稳压就是坏了。 3、外观检查:看看变压器的外观有没有高温烧焦的痕迹,如有外观出现高温变形就是烧坏了。

门禁专业电源的选择 说到门禁专用电源里面有好多的内容,其一是功率大小不一样,其二是功能多样化,其三是价格也是天差地别,其四是牌子很多。做门禁做久了可能懂之一二,但对于刚入门,刚进到门禁这个行的人员来说,选个电源跟选个媳妇似的,怕选错,怕不匹配,怕质量不好等。下面我来给大家简述一下门禁电源的区别: 门禁电源一搬分为控制器门禁专用电源和一体机门禁专用电源,还分后备电源和无备电源,再有就是功率大小之分。 控制器门禁专用电源,是专门接联网型门禁控制板用的,内部有固定控制板的螺丝孔位,慊容大部分品牌控制板,这种电源只输出DC12V,控制器专用电源有以下之分 1、有些电源是带电压调节钮,输出电压可调节DC12V-DC15V这样子,带电压可调节的电源门禁设备连线可以长一点。有些是电压固DC12V输出,固定电压输出的电源与设备连线有限制,线太长电压就不足会导致门禁设备开不了机或死机的情况。带电压调节的一般都比不带电压调节的会贵些。 2、电源还分带接后备电池和不带接后备电池功能的,带接电池的电源可以在市电220V停电后还可以用电池带门禁,不至于停电门禁系统出现瘫痪。带接电池功能的电源还分为放电保护功能和无放电保护功能,带放电保护的电源一般在电池放电致10.5V时会自动断开防止电池放电过低而造成电池致命损坏。 3、可接电池的电源还分为内部接电池和外部接电池之分。 4、功率大小之分,标称一般功率有5A和3A,实际功率能达到的也就是3A和1.2A。 一体机门禁专用电源,这种电源种类比较多,前面1、2、3、4、都是和控制器门禁专用电源一样。就是多以下功能: 1、带接电锁功能NC(常闭)点、NO(常开)点,带接开关量信号开门PUSH点,有些还带电信号开门的-CONTROL+两点。 2、有些带遥控器接收模块接口,配合遥控器开门用,这种很少有人用,一般都外接遥控器的多,外接遥控器方便又稳定。 3、就是给电锁供电输出稳压与不稳压,给电锁供电稳压的电源用的都是大功率稳压管,价格相对也会比不稳压的贵,给电锁供电不稳压的电源门禁供电接口DC12V一般都是用1个7812A或2个7812稳压管稳压输出,1个7812输出的电流是500MA,两个的话最多也是1A,建议带800MA。7812稳压方式是市场上最便宜的门禁电源,这种电源带的电锁温度会高点,有些厂家的电锁耐电压低的容易烧锁,而且接门禁DC12V也只能达到1A,带指纹机,掌纹机时电流小可能带不动。 最后给各位一点建议,电子产品中不管什么产品都是很多生产制造商,很多品牌,五花八门的,网上,市场上一看眼花缭乱,所以选电子产品一定要选品牌,选专业的制造商,只有真正的品牌和专业才能保证质量,才能保证服务。 开尔瑞门禁专用电源八年品牌,专注八年,用心八年,值得您信信赖。 器是两线圈级成的。

油浸电力变压器设计手册-沈阳变压器(1999) 6负载损耗计算

目录 1 概述SB-007.6 第 1 页 2 绕组导线电阻损耗(P R)计算SB-007.6 第 1 页 3 绕组附加损耗(P f)计算SB-007.6 第1页3.1 层式绕组的附加损耗系数(K f %)SB-007.6 第 1 页3.2 饼式绕组的附加损耗系数(K f %)SB-007.6 第 2 页3.3 导线中涡流损耗系数(K w %)计算SB-007.6 第 2 页 3.3.1 双绕组运行方式的最大纵向漏磁通密度(B m)计算SB-007.6 第 2 页3.3.2 降压三绕组变压器联合运行方式的最大纵向漏磁通密度(B m)计算SB-007.6 第 3 页 SB-007.6 第3 页3.3.3 升压三绕组(或高-低-高双绕组)变压器联合运行方式的最大纵向漏 磁通密度(B m)计算 3.3.4 双绕组运行方式的涡流损耗系数(K w %)简便计算SB-007.6 第4 页3.4 环流损耗系数(K C %)计算SB-007.6 第 4 页3. 4.1 连续式绕组的环流损耗系数(K C %)计算SB-007.6 第4 页3.4.2 载流单螺旋―242‖换位的绕组环流损耗系数(K C1 %)计算SB-007.6 第5 页 SB-007.6 第5 页3.4.3 非载流(处在漏磁场中间)单螺旋―242‖换位的绕组环流损耗系数 (K C2 %)计算 3.4.4 载流双螺旋―交叉‖换位的绕组环流损耗系数(K C1 %)计算SB-007.6 第6 页 SB-007.6 第7 页3.4.5 非载流(处在漏磁场中间)双螺旋―交叉‖ 换位的绕组环流损耗 系数(K C2 %)计算 4引线损耗(P y)计算SB-007.6 第7 页5杂散损耗(P ZS)计算SB-007.6 第8 页5.1小型变压器的杂散损耗(P Z S)计算SB-007.6 第8 页5.2中大型变压器的杂散损耗(P Z S)计算SB-007.6 第9 页5.3 特大型变压器的杂散损耗(P Z S)计算SB-007.6 第10 页

变压器安装及系统调试流程

变压器安装及系统调试 流程 Company number:【0089WT-8898YT-W8CCB-BUUT-202108】

变压器安装及系统调试 施工工序:外观检查→基础安装→本体就位→器身检查→附件安装→变压器试验→系统模拟试验→空载试验 k、模拟实验: 依据设计图检查控制设备及二次回路。 检查安装及效验记录。 做短路、过流、重瓦斯、信号、合分闸二次回路传动试验并做记录,动作结果要正确。 l、对绝缘有怀疑时,进行局部放电实验。 m、冲击合闸试验: 要在盘柜试验和模拟试验完全合格的基础上才能进行。 做冲击合闸实验前要对变压器的所有资料进行检查并保证变压器清洁。 加额定电压,合闸5次,每次间隔5分钟无异常后方可送电运行。 101变压器系统调试该如何套用定额? 电力变压器系统调试,包括三相和单相电力变压器系统调试两个分项工程,都是按变压器容量区分规格,分别以“系统”为单位计算。 三相及单相电力变压器系统调试工作内容包括变压器、断路器、互感器、隔离开关、风冷及油循环装置等一、二次回路的调试及空载投入试验。 10kV以下送配电调试: 1. 送配电调试子目适用于10千伏以下送配电回路的系统调试,如从配电装置至分配电箱的供电回路。但从配电箱至电动机的供电回路已包括在电动机的系统调试子目之内。

2. 供电系统调试包括系统内的电缆试验、绝缘子耐压、线路绝缘测试及其一回或二回线路中所有断路器、继电保护、测量仪表的试验等全套调试工作。 3. 一般仪表(如电压表、电流表)、保护互感器的试验均包括在相应的送配电设备系统调试内;计量用仪表、互感器的校验由供电部门统一进行,费用计取按相应规定。 2变压器送电调试运行实验内容 (1)测量线圈连同套管一起的直流电阻。 (2)检查所有分接头的变压比。 (3)检查三相变压器的联结组标号和单相变压器引出线极性。 (4)测 量线圈同套管一起的绝缘电阻。 (5)线圈连同套管一起做交流耐压试验。 (6)油箱中绝 缘油的试验。变压器送电调试运行前的检查 (1)检查各种交接试验单据是否齐全、真实合格,变压器一、二次引线相位、相色正确,接地线等压接触良好。 (2)变压器应清理擦拭干净,顶盖上无遗留杂物,本体及附体无缺损,且不渗油。 (3)通风设施安装完毕,工作正常,事故排油设施完好,消防设施齐全。 (4)油浸变压器的油系统油门应拉开,油门指示正确,油位正常。 (5)油浸变压器的电压切换位置处于正常电压档位。 (6)保护装置整定值符 合规定要求,操作及联动试验正常。变压器送电调试运行 (1)变压器空载投入冲击试验。即变压器不带负荷投入,所有负荷侧开关应全部拉开。必须进行全电压三次冲击实验,以考核变压器的绝缘和保护装置,第一次投入时由高压侧投入,受电后持续时间不少于10 min,经检查无异常情况后,再每隔5 min进行冲击一次,励磁涌流不应引起保护装置动作。最后一次进行空载运行24 h。 (2)变压器空载运行检查方法主要是听声音。正常时发出嗡嗡声,而异常时有以下几种情况发生:声音比较大而均匀时,可能是外加电压比较高;声音比较大而嘈杂时,可能是芯部有松动;有吱吱放电声音,可能是芯部和套管表面有闪络;有爆裂声响,可能是芯部击穿现象。 (3)在冲击试验中操作人员应注意观察冲击电流、空载电流、—、二次测电压、变压器油温度等,做好记录。变压器半负荷调试运行 (1)经过空载冲击试验后,可在空载运行24 h~28 h,如确认无异常便可带半负荷进行运行。 (2)将变

电力变压器的倒闸操作

电力变压器的倒闸操作 电力变压器的倒闸操作一、变压器倒闸操作的原则1(大型变压器倒闸操作原则(1)大型变压器停、送电要执行逐级停、送电的原则,即:停电时先停低压侧负荷,后停高压侧负荷,送电时与此相反。(2)大电流直接接地系统的中性点刀闸数目应按继电保护的要求设置。变压器倒闸操作时,必须合上其中性点刀闸,正常运行中性点应按调度令决定其投、停。(3)变压器投入运行时,应该选择励磁涌流较小的带有电源的一侧充电,并保证有完备的继电保护。现场规程没有特殊规定时,禁止由中压、低压向主变充电,以防主变故障时保护灵敏度不够。(4)主变压器投、停时,要注意中性点消弧线圈的运行方式。主变停电检修,在主变消弧线圈中性点刀闸主变侧挂一组单相接地线。(5)主变检修后恢复送电时,应核对变压器有载调压分接头位置与运行变压器的一致。(6)主变停电检修应考虑相应保护的变动,如停用主变保护切母联、分段开关压板等。防止继电人员做保护定检时误跳母联及分段。(7)停电检修主变后恢复送电,主变充电前应停用运行变压器中性点过流II段压板,充电良好后再投入。防止充电时电压不平衡,中性点产生环流将运行变压器误跳闸。(8)主变停电时,应考虑一台变压器退出后负荷的重新分配问题,保证运行变压器 不过负荷。2(中、小型变压器倒闸操作原则(1)中、小型变压器停、送电要执行逐级停、送电的原则,即:停电时先停低压侧负荷,后停高压侧负荷,送电时与此相反。(2)停电时应考虑一台变压器退出后负荷的重新分配问题,保证运行变压器不超过负荷。(3)主变停电时要考虑停用变压器联跳压板,恢复送电时要检查有载调压分接头位置正确。二、变压器停、送电的操作步骤1(大型变压器倒闸操作步骤(1)某变压器和开关由运行转检修的操作步骤1)检查运行主变能否带全部负荷。2)合上主变直接接地中性点刀闸。3)拉开主变低压侧开关。4)拉开主变中压侧

HVFP_260kW变压器局放试验系统(220kV变压器)

H V F P-260k W变压器局部放电、感应耐压 试验系统 单位:工业园区海沃科技 地址:省工业园区泾茂路285号4号厂房 邮编:215122 电话:0567619936 传真:0582277685

局放试验回路示意图 一、成套试验系统适用围: 1) HVFP 型260kW 无局放变频电源是由大功率晶体管组成的线性矩阵放大网络,并运用最新DSP 工业控制器及光纤传输技术,工作在线性放大区,从而获得与信号源一致的标准正弦波形,由于其部没有任何工作在开关状态下的电路,因此不产生严重的干扰信号,适合作为局部放电试验的电源。采用HVFP 系列无局放变频电源作为串联谐振的励磁电源,由于输出波形为纯正弦波,损耗小,可使回路Q 值提高25%,也适合作为串联谐振的励磁电源。 2) 220kV/240MVA 及以下的电力变压器(低压侧电压10kV ~35kV )的局部放电、感应耐压试验; 3) 配置的260kW 变频电源及260kVA 励磁变压器可作为串联谐振试验装置的变频电源及励磁变压器使用。 二、设备供货围一览表 HVFP-260kW 变压器局部放电、感应耐压试验系统 供货围一览表 分类 名称 规格 数量 变频电源 1600宽×1900高×900厚 1.3T 无局放变频电源 HVFP —260kW 1套 智能变频电源控制箱 HVFP 1台 变频电源控制光纤 20m (含光电转换器) 2根 高压测量终端 高压信号采样用 含测量光纤20米 1套 专用工具 295简易晶体管测试仪、功放板专用抽取工具 1套 局放试验回路示意图

起重吊带等含吊带2根,U形扣4只,捆绑器4套1套防雨防尘罩1只 励磁变压器1350宽×1500长×1600高 2.5T 无局放励磁变压器ZB-260kVA/2×5/10/35kV 1台高压输出连接线黑色带皮导线,10mm2,10米/根,4根1套 补偿电抗器ф350×450 0.15T/台无局放补偿电抗器 HVFR-100kVA/20kV 20kV/5A/6H/90min 4台车载绝缘底座与电抗器器身做成一体4只 无局放电容分压器无局放电容分压器HV-300pF/60kV 1台多功能峰值电压表HV 1只屏蔽测量线低压臂至峰值表,配有三通测试接口1套铝合金包装箱电容器本体、峰值表用1套 附件10mm2/10米/根,8根带透明外皮接地导线;接地汇流盘2只;U型接地夹 2只;接地棒1根;0.8m/2.5mm2/根,红色接插线10根,配夹子、插片各 10个;3T/3米吊带4根,U型扣8只;附件箱1套 1套 低压电缆 电源电缆:120mm2、50m/根3根 变频电源输出用,每根规格120mm2、10m 2根低压电缆线盘用于收放电源电缆及变频电源输出电缆,带轮子,可方便搬运3只变压器均压帽110kV/3只;220kV/3只,配包装箱1套 三、配置说明:

变压器倒闸操作

变压器倒闸操作

检修一号主变步骤: 漯351断路器分闸 漯111断路器分闸 漯221中地分闸 漯221断路器分闸 漯351甲分闸 漯351西分闸 漯111甲分闸 漯111南分闸 漯221甲分闸 漯221南分闸 10/28/15 09:14:38 巡视一号主变本体 10/28/15 09:17:35 巡视漯35kV漯351线储能电源 10/28/15 09:19:42 漯351断路器操作箱控制电源断开 10/28/15 09:19:45 漯351开关操作箱储能电源断开 10/28/15 09:20:48 #1主变低压侧351开关现场操作方式开关就地10/28/15 09:21:04 漯351开关操作箱储能电源合上 10/28/15 09:21:06 漯351断路器操作箱控制电源合上 10/28/15 09:21:12 漯351分闸 10/28/15 09:21:12 #1主变低压侧351开关就地分 10/28/15 09:23:48 巡视漯110kV漯111线分合指示 10/28/15 09:23:51 巡视漯110kV漯111线SF6气体压力表 10/28/15 09:24:12 漯111就地远方切换开关在就地 10/28/15 09:24:22 漯111分闸 10/28/15 09:26:23 #2主变辅助风扇启动

10/28/15 09:28:19 巡视漯221中地刀 10/28/15 09:29:12 巡视漯220kV漯221线C相分合指示 10/28/15 09:30:14 #1主变高压侧221开关就地操作方式开关置就地10/28/15 09:30:25 #1主变高压侧221开关就地操作开关分闸 10/28/15 09:30:25 漯221A相分闸 10/28/15 09:30:25 漯221B相分闸 10/28/15 09:30:25 漯221C相分闸 10/28/15 09:32:15 巡视漯221中地刀 10/28/15 09:32:39 漯221中地分闸 10/28/15 09:32:39 漯221中地分闸操作 10/28/15 09:33:19 巡视漯35kV漯351西刀闸 10/28/15 09:33:23 漯351甲分闸 10/28/15 09:33:23 漯351甲分闸操作 10/28/15 09:33:43 巡视漯35kV漯351甲刀闸 10/28/15 09:33:47 漯351西分闸 10/28/15 09:33:47 漯351西分闸操作 10/28/15 09:35:50 巡视漯110kV漯111甲刀闸 10/28/15 09:37:29 漯111甲分闸 10/28/15 09:37:29 漯111甲分闸操作 10/28/15 09:37:48 巡视漯110kV漯111南刀闸 10/28/15 09:37:51 漯111南分闸 10/28/15 09:37:51 漯111南分闸操作 10/28/15 09:40:29 巡视漯220kV漯221甲三相小开关 10/28/15 09:40:50 漯221甲控制电源合上 10/28/15 09:41:01 漯221甲分闸 10/28/15 09:41:01 漯221甲分闸操作 10/28/15 09:42:07 巡视漯220kV漯221南三相小开关 10/28/15 09:42:52 漯221南控制电源合上 10/28/15 09:43:05 漯221南就地远方切换开关在就地 10/28/15 09:43:12 漯221南分闸 10/28/15 09:43:12 漯221南分闸操作

变压器故障检测系统毕业设计论文

变压器故障检测系统 摘要 大型电力变压器是电力系统中重要的和昂贵的设备之一,其运行状态直接影响系统的安全性。目前,电力系统的检修体制正由定期检修向状态检修转变,而状态检修是以了解设备的运行状态为基础的。要了解设备状态,就需要对设备信息进行分析诊断。本文的工作就是在这一背景下开展的,其意义在于为电力变压器的检修提供技术支持。本文是从变压器的故障原因、类型以及分析入手,介绍了现今国内外主要研究的基于变压器油中气体的故障诊断方法。 在系统的硬件部分,本文以ATmega8单片机为核心,将采集来的电压、电流、温度和气体等模拟量信号经过A/D转换器转换为数字量信号后送入单片机系统中进行处理,通过处理的结果来判断变压器是否含有故障以及故障的类型等。同时本系统也设置了电流保护、差动保护和气体保护等继电保护来防止因短路故障或不正常运行状态照成变压器的损坏,提高供电可靠性。在系统的软件部分,本文运用C语言编写软件程序,使之能够识别并处理从传感器传来的电信号,然后通过人机交互界面显示出来,近而使人能够很轻易判断故障类型。 关键词:变压器故障油气体分析单片机继电保护

Transformer malfunction detection system Abstract In the electrical power system, the large-scale power transformer is one of the important and expensive equipment, it’s running status direct influence system security. At present, the electrical power system overhaul system is transforming by the preventive maintenance to the condition overhaul, but the condition overhaul is take understands the equipment the running status as the foundation.Must understand the equipment condition, needs to carry on the analysis diagnosis to the equipment information. This article work is develops under this background, its significance lies in for the power transformer condition overhaul provides the technical support.This article is from the transformer breakdown reason, the type and the analysis obtains, introduced the nowadays domestic and foreign main research based on the transformer oil in the gas breakdown diagnosis method. Are partial in the system hardware, this article take the ATmega8 MCU as a core, use the gather simulation signal likes voltage, electric current, temperature, gas and so on, to transform after ADC for the digital quantity, and then signal sends in the MCU system to process, will judge the transformer through the processing result whether will include the breakdown and the breakdown type and so on.Simultaneously this system has also established the relay prevents likes the electric current protection, the differential motion protection and the gas protection and so on, to protect for short-circuit the breakdown or the off normal operation condition according to becomes the transformer the damage, enhances the power supply reliability.Are partial in system software, this article utilizes the C language compilation software procedure, enables it to distinguish and to process the electrical signal which transmits from the sensor, then demonstrated through the man-machine interactive contact surface, nearly enables the person the very easily diagnosis type. Keywords:transformer breakdown;oil gas analysis;MCU;relay prevents

某电力变压器继电保护设计(继电保护)

1 继电保护相关理论知识 1.1 继电保护的概述 研究电力系统故障和危及安全运行的异常工况,以探讨其对策的反事故自动化措施。因在其发展过程中曾主要用有触点的继电器来保护电力系统及其元件(发电机、变压器、输电线路等),使之免遭损害,所以沿称继电保护。 1.2.1 继电保护的任务 当电力系统发生故障或异常工况时,在可能实现的最短时间和最小区域内,自动将故障设备从系统中切除,或发出信号由值班人员消除异常工况根源,以减轻或避免设备的损坏和对相邻地区供电的影响。 1.2.2继电保护基本原理和保护装置的组成 继电保护装置的作用是起到反事故的自动装置的作用,必须正确地区分“正常”与“不正常”运行状态、被保护元件的“外部故障”与“内部故障”,以实现继电保护的功能。因此,通过检测各种状态下被保护元件所反映的各种物理量的变化并予以鉴别。依据反映的物理量的不同,保护装置可以构成下述各种原理的保护:(1)反映电气量的保护 电力系统发生故障时,通常伴有电流增大、电压降低以及电流与电压的比值(阻抗)和它们之间的相位角改变等现象。因此,在被保护元件的一端装没的种种变换器可以检测、比较并鉴别出发生故障时这些基本参数与正常运行时的差别.就可以构成各种不同原理的继电保护装置。 例如:反映电流增大构成过电流保护; 反映电压降低(或升高)构成低电压(或过电压)保护; 反映电流与电压间的相位角变化构成方向保护; 反映电压与电流的比值的变化构成距离保护。 除此以外.还可根据在被保护元件内部和外部短路时,被保护元件两端电流相位或功率方向的差别,分别构成差动保护、高频保护等。 同理,由于序分量保护灵敏度高,也得到广泛应用。 新出现的反映故障分量、突变量以及自适应原理的保护也在应用中。

设计变压器的基本公式精编版

设计变压器的基本公式 为了确保变压器在磁化曲线的线性区工作,可用下式计算最大磁通密度(单位:T) Bm=(Up×104)/KfNpSc 式中:Up——变压器一次绕组上所加电压(V) f——脉冲变压器工作频率(Hz) Np——变压器一次绕组匝数(匝) Sc——磁心有效截面积(cm2) K——系数,对正弦波为4.44,对矩形波为4.0 一般情况下,开关电源变压器的Bm值应选在比饱和磁通密度Bs低一些。 变压器输出功率可由下式计算(单位:W) Po=1.16BmfjScSo×10-5 式中:j——导线电流密度(A/mm2) Sc——磁心的有效截面积(cm2) So——磁心的窗口面积(cm2) 3对功率变压器的要求 (1)漏感要小 图9是双极性电路(半桥、全桥及推挽等)典型的电压、电流波形,变压器漏感储能引起的电压尖峰是功率开关管损坏的原因之一。 图9双极性功率变换器波形 功率开关管关断时电压尖峰的大小和集电极电路配置、电路关断条件以及漏感大小等因素有关,仅就变压器而言,减小漏感是十分重要的。 (2)避免瞬态饱和

一般工频电源变压器的工作磁通密度设计在B-H曲线接近拐点处,因而在通电瞬间由于变压器磁心的严重饱和而产生极大的浪涌电流。它衰减得很快,持续时间一般只有几个周期。对于脉冲变压器而言如果工作磁通密度选择较大,在通电瞬间就会发生磁饱和。由于脉冲变压器和功率开关管直接相连并加有较高的电压,脉冲变压器的饱和,即使是很短的几个周期,也会导致功率开关管的损坏,这是不允许的。所以一般在控制电路中都有软启动电路来解决这个问题。 (3)要考虑温度影响 开关电源的工作频率较高,要求磁心材料在工作频率下的功率损耗应尽可能小,随着工作温度的升高,饱和磁通密度的降低应尽量小。在设计和选用磁心材料时,除了关心其饱和磁通密度、损耗等常规参数外,还要特别注意它的温度特性。一般应按实际的工作温度来选择磁通密度的大小,一般铁氧体磁心的Bm值易受温度影响,按开关电源工作环境温度为40℃考虑,磁心温度可达60~80℃,一般选择Bm=0.2~0.4T,即2000~4000GS。 (4)合理进行结构设计 从结构上看,有下列几个因素应当给予考虑: 漏磁要小,减小绕组的漏感; 便于绕制,引出线及变压器安装要方便,以利于生产和维护; 便于散热。 4磁心材料的选择 软磁铁氧体,由于具有价格低、适应性能和高频性能好等特点,而被广泛应用于开关电源中。 软磁铁氧体,常用的分为锰锌铁氧体和镍锌铁氧体两大系列,锰锌铁氧体的组成部分是Fe2O3,MnCO3,ZnO,它主要应用在1MHz以下的各类滤波器、电感器、变压器等,用途广泛。而镍锌铁氧体的组成部分是Fe2O3,NiO,ZnO 等,主要用于1MHz以上的各种调感绕组、抗干扰磁珠、共用天线匹配器等。 在开关电源中应用最为广泛的是锰锌铁氧体磁心,而且视其用途不同,材料选择也不相同。用于电源输入滤波器部分的磁心多为高导磁率磁心,其材料牌号多为R4K~R10K,即相对磁导率为4000~10000左右的铁氧体磁心,而用于主变压器、输出滤波器等多为高饱和磁通密度的磁性材料,其Bs为0.5T(即5000GS)左右。 开关电源用铁氧体磁性材应满足以下要求:

电力变压器课程设计

1 前言 随着工农业生产和城市的发展,电能的需要量迅速增加。为了解决热能资源(如煤田)和水能资源丰富的地区远离用电比较集中的城市和工矿区这个矛盾,需要在动力资源丰富的地区建立大型发电站,然后将电能远距离输送给电力用户。同时,为了提高供电可靠性以及资源利用的综合经济性,又把许多分散的各种形式的发电站,通过送电线路和变电所联系起来。这种由发电机、升压和降压变电所,送电线路以及用电设备有机连接起来的整体,即称为电力系统。 电力系统是有各种电力系统元件组成的,它们包括发电、输变电、负荷等机械、电气主设备以及控制、保护等二次辅助设备。WDT-Ⅲ型电力系统综合自动化试验系统是一个完整的电力系统典型模型,它为我们提供了一个自动化程度很高的多功能实验平台,是为了适应现代化电力系统对宽口径“复合型”高级技术人才的需要而研制的电力类专业新型教学试验系统。 本设计所要完成的工作是利用VC语言开发WDT电力系统综合自动化实验台监控软件,主要是完成准同期控制器监控软件的编写,它要求能显示发电机及无穷大系统的相关参数,如电压、频率和相位角,并能发送准同期合闸命令。

2 电力系统实验台 WDT-Ⅲ型电力系统综合自动化实验教学系统主要由发电机组、试验操作台、无穷大系统等三大部分组成(如图2.1所示)。 图 2.1 WDT-Ⅲ型电力系统综合自动化试验系统 2.1 发电机组 该系统的发电机组主要由原动机和发电机两部分构成,另外,它还包括了测速装置和功率角指示器(用于测量发电机电势与系统电压之间的相角 ,即发电机转子相对位置角),测得的发电机的相关数据传输回实验操作台,与无穷大系统的相关参数进行比较,从而确定系统是否满足了发电机并网条件。 2.1.1 原动机 在实际的发电厂中,原动机一般用的是水轮机、气轮机、柴油机或者其他形式的动力机械,将水流,气流,燃料燃烧或原子核裂变产生的能量转换为带动发电机轴旋转的机械能,从而带动发电机转子的旋转。 在WDT-Ⅲ型电力系统综合自动化试验台的发电机组中,原动机是由直流发电机(P N=2.2kW,U N=220V)模拟实现其功能的。直流电动机(模拟原动机)与发电机的结

变压器标准倒闸操作票

高压配电室停送电操作程序 1、倒闸操作必须根据值班调度员或值班负责人的指令,受令人复诵无误 后执行。 2、操作人查对模拟系统图,填写操作票。 3、监护人、值班负责人审票,发现错误应由操作人重新填写。 监护人与操作人相互考问和预想。 值班负责人发布操作指令,并复诵无误。 准备必要的安全工具、用具、钥匙、并检查绝缘板、绝缘靴、验电笔等。监护人逐项唱票,操作人复诵,并核对设备名称编号相符。 监护人确认无误后,发出允许操作的命令“对,执行”;操作人正式操作,监护人逐项勾票。 对操作后设备进行全面检查。 向调度及值班负责人汇报操作任务完成并做好记录,盖“已执行”章;附:变压器标准倒闸操作票 变压器供电方式图:

停电倒闸操作:(以I#变检修停运为例) 检查两台变压器电流总和是否超过单台变压器的额定电流; 电告热电调:我方要退出1#变,并请求其合环; 得到电调准许操作后,合上高压10KV母联开关(ME1)查确已合上; 检查10KVI段、II段并运正常; 将低压配母联(ME2)合上,查确已合上; 检查低压配400VI段、II段并运正常; 断开低压1#进线开关(QF3),查确已断开; 将低压1#进线开关(QF3)摇至试验位,取下控制保险后,挂”禁止合闸,有人工作”标示牌; 在1#变高压开关(QF1)柜上查确无电流,变压器空载; 断开1#变高压开关(QF1),并查确已断开; 将1#变高压开关(QF1)摇至试验位后,挂”禁止合闸,有人工作”标示牌; 验明1#变确无电压

拉开1#变隔离刀闸(QF1甲)查确已拉开; 合上1#变高压柜QF1地刀闸,查确已合上; 断开高压10KV母联开关ME1; 查高压10KVI段,II段分段运行正常; 电告电调我方已操作完毕,可以解环,并做好记录; 注:1、在正常生产时,原料磨配、、2#蒸发配、种滤I#、II#变负荷较高。若退出以上配中的任何一台变压器时,必须向生产岗位和调度室说明情况,协调好,并要求启动任何设备,通知电气车间以免因启动时冲击电流过大,负荷电流大造成变压器过负荷运行,影响安全运行。 2、若是需停某整段母线时,应考虑是否影响到如计算机和高压直流屏的供电。 送电倒闸操作: 检查确认符合送电条件; 电告热电调:我方要恢复I#变,并请求其合环; 得到电调准许操作后,必要时要进行校相; 检查高压10KV母联开关(ME1)工作位置; 合上高压10KV母联开关(ME1),查确已合上; 查高压10kvⅠ、Ⅱ并列运行正常; 拉开1#变高压柜(QFI地)刀闸,查确已拉开; 合上1#变高压隔离刀闸(QFI甲),查确已合上;; 取下1#变高压开关(QF1)柜悬挂标示牌,并将小车摇至“工作”位;

电力变压器设计分析

所需输入数据 一般数据 1.制造商 2.变压器类型(例如:移动式、变电站用、整流器用等)3.数据来源:测试数据或规格参数 3.a.频率 4.自耦变压器:是或不是 5.空载损耗 6.负载损耗kW值以及在标准接线端和中间抽头处的基准温度7.阻抗在额定功率MV A基本接点和抽头位置处的阻抗8.铁芯与线圈总重量 9.额定容量每个绕组的MV A值 10.冷却方式 11.针对每一种额定容量及冷却方式,给出: a)顶层变压器油的温升 b)各绕组引起的温升 c)绕组的平均温升 12.绕组数目以及在铁芯上的位置 13.每个绕组的BIL(绝缘基本冲击耐压水平) 14.每个绕组的额定电压 15.每个绕组的连接形式:星型或三角型 16.每个绕组单相的电阻 17.每个绕组并联的电路数 18.有无低温冷却方式:有或没有 如果有:用在哪个绕组上? 最大抽头电压 最小抽头电压 该绕组的抽头数 接线位置数 连接方式 19.有无“无负载”抽头:有或没有 如果有:在哪个绕组上? 最大抽头电压 最小抽头电压 该绕组的抽头数

所需输入数据(续) 铁芯数据 20.截面积:毛截面与净截面 21.铁芯:a) 共有多少条 b) 每条的宽度 c) 每条的叠数 d) 芯体的周长或直径 22.通量密度 23.窗口尺寸:高度及宽度 23.a.窗口中心线的位置 24.接缝方式:全斜角接缝或半斜角接缝 25.材料:钢材等级及钢片厚度 25.a.在基准通量密度下的瓦/公斤数: 空隙数据 26.间隙:铁芯与绕组导线之间的空隙 27.间隙:绕组与绕组之间(绕组的导线与导线之间)的空隙28.间隙:相与相之间(导线与导线之间)的空隙 29.每个绕组的留空系数[1] 30.每个绕组的填充和抽头空间[2](沿高度的方向) 31.每个绕组的边缘距离 a)导线至线圈边缘 b)导线至铁芯箍圈 31a.每个绕组的高度: 径向: 轴向: 32.每个绕组的线槽: 径向:数量及尺寸[3] 轴向:数量及尺寸[4]

电力变压器设计原则

电力变压器设计原则 1.铁心设计 1.1铁心空载损耗计算:P 0=k p ?p 0?G W 其中:k p ——铁心损耗工艺系数,见表2; p 0——电工钢带单位损耗(查材料曲线),W/kg ; G ——铁心重量,kg 。 1.2铁心空载电流计算 空载电流计算中一般忽略有功部分。 (1)三相容量≤6300 kV A 时: 1230()10t f N G G G k q S n q I S ++??+??= ? % 其中:G 1、G 2、G 3——分别为心柱重量、铁轭重量、角重,kg ; k ——铁心转角部分励磁电流增加系数,全斜接缝k=4; q f ——铁心单位磁化容量(查材料曲线),V A/ kg ; S ——心柱净截面积,cm 2; S N ——变压器额定容量,k V A ; n ——铁心接缝总数,三相三柱结构n=8; q j ——接缝磁化容量,V A/ cm 2,根据B m 按表1进行计算。

(2)三相容量>6300 kV A :010i t N k G q I S ??= ? % k i ——空载电流工艺系数,见表2; G ——铁心重量,kg ; q t ——铁心单位磁化容量(查材料曲线),V A/ kg ; S N ——变压器额定容量,k V A 。 表2 铁心性能计算系数(全斜接缝) 注(1)等轭表示铁心主轭与旁轭的截面相等。 1.3铁心圆与纸筒之间的间隙见表3 表3 铁心圆与纸筒间隙 1.4铁心直径与撑条数量关系见表4 表4 铁心直径与撑条数量关系 续表4 铁心直径与撑条数量关系

1.5铁心直径与夹件绝缘厚度关系见表5 2.绝缘结构 2.1 10kV级变压器 2.1.1纵绝缘结构 (1)高压绕组(LI75 AC35) 1)饼式结构 导线匝绝缘0.45,绕组不直接绕在纸筒上,所有线段均垫内径垫条1.0mm;各线饼轴向油道宽度见表15;分接段位于绕组中部。 中断点油道 4.0mm,分接段之间(包括分接段与正常段之间)油道2.0mm,正常段之间0.5mm纸圈。整个绕组增加9.0mm调整油道。 2)层式结构 层式绝缘:首层加强0.08×2,第2层与末层加强0.08×1。当绕组不直接绕在纸筒上时,所有线段均垫内径垫条1.0mm。 (2)低压绕组(AC5) 当绕组不直接绕在纸筒上时,所有线段垫内径垫条 1.0mm,所有线段之间垫0.5mm纸圈。。 当高压绕组为饼式结构时,对应高压分接段处应注意安匝平衡。 2.1.2主绝缘结构 (1)铁心圆与纸筒之间的间隙见表3;低压绕组内纸筒厚2.0mm。当

1、电力变压器仿真模型的设计

电力变压器仿真模型的设计 摘要 随着电力系统的飞速发展,对变压器的保护要求也越来越高。研究三相变压器地暂态过程,建立一个完善的变压器仿真模型,对变压器保护方案的设计具有非常重要地意义。 本文在Matlab的编程环境下,分析了当前的变压器仿真的方法。在单相情况下,分析了在饱和和不饱和的励磁涌流现象,和单相励磁涌流的特征。在三相情况下,在用分段拟和加曲线压缩法的基础上,分别用两条修正的反正切函数,和两条修正的反正切函数加上两段模拟饱和情况的直线两种方法建立了Yd11、Ynd11、Yny0和Yy0四种最常用接线方式下三相变压器的数学仿真模型,并在Matlab下仿真实现。通过对三相励磁涌流和磁滞回环波形分析,三相励磁涌流的特征分析,总结出影响三相变压器励磁涌流地主要因素。最后,分析了两种方法的优劣,建立比较完善的变压器仿真模型。 关键词:三相变压器、励磁涌流、仿真、数学模型

Abstract Along with the electric power system’ development, the request of the protection of the transformer is more and more high. It has count for much meaning to the transformer protecting project to study the transient of a three-phase transformer, and found a perfect three-phase transformer’s digital model. This paper is worked with Matlab, analyzes the current methods of transformer’s digital model. In single-phase transformer, it is analyzed that the inrush current in saturate and unsaturated states, and the characters of the single-phase transformer’s inrush current. In three-phase transformer, with the foundation of the method of compressing curves, we use respectively two modified functions, and two modified functions and two straight line to establish four kinds of transformer’s digital model, such as Yd11, Ynd11, Yny0, Yy0, and realize these with Matlab. After analyzing the wave form of the three-phase transformer’s inrush current and hysteresis, and the characters of three-phase transformer’s inrush current, it is concluded that the primary factors which affect three-phase transformer’s inrush current. Finally, after analyzing the advantages and disadvantages of two methods, a good digital model of three-phase transformer is established. Keywords:three-phase transformer, inrush current, simulation, digital model

倒闸操作

第一节基本接线的倒闸操作 一、单母线(分段)接线的倒闸操作 (一)单母线(分段)接线倒闸操作原则 单母线(分段)接线方式操作比较简单。我们可以把母线系统的操作分解成几个单一操作,线路、主变压器、母线及分段开关可以各写一张操作票,把复杂的操作进行分解,达到化 繁为简的目的。 (1)停送电操作顺序:停电时先停线路,再停主变压器,最后停分段开关。送电时操作顺序与此相反。 (2)拉分段开关两侧刀闸时,应先拉停电母线侧的刀闸,后拉带电母线侧刀闸,送电时操作顺序与此相反。 (3)停电时母线所接电压互感器的操作应在拉开分段开关后进行,送电时与此相反,尽量不带电操作。对于可能产生谐振的采用不同时操作的方法,停电时先停电压互感器,送电 时后送电压互感器。 (4)线路接地线按调度令装设,所内接地线自行装设。 (5)分段开关检修时两段母线不能并列运行,当两母线接有双回线并配有双回线保护时,应停用该保护。 (6)给空母线充电尽量要用分段和主变开关进行,配有快速保护的要投入该保护。 (二)单母线(分段)接线倒闸操作的步骤 1.某段母线停、送电的操作步骤 (1)某段母线由运行转检修的操作步骤 1) 拉开该母线电容器开关。 2)拉开该母线线路开关。 3)拉开该母线主变压器母线开关。 4)拉开母线分段开关。 5)按顺序拉开该母线电压互感器一、二次刀闸和保险。 6) 按顺序拉开该母线厂(所)用变一、二次刀闸和保险。 7) 按顺序拉开该母线各出线开关两侧刀闸。 8)布置安全措施。

(2)某段母线由检修转运行的操作步骤 1)拆除安全措施。 2)按顺序合上该母线各出线开关两侧刀闸。 3)按顺序合上该母线电压互感器一、二次刀闸和保险。4)合上母线分段开关。 5)合上主变压器母线开关。 6)按顺序合上该母线各出线开关两侧刀闸。 7)合上各出线开关。 8) 按顺序合上该母线厂(所)用变一、二次刀闸和保险。2.分段开关停、送电的操作步骤 (1)分段开关由运行转检修的操作步骤 1) 拉开分段开关。 2) 拉开分段开关两侧刀闸。 3) 拉开分段开关的操作直流保险、动力保险。 4)布置安全措施。 (2)分段开关由检修转运行的操作步骤 1)拆除安全措施。 2)合上分段开关的操作直流保险、动力保险。 3)合上分段开关两侧刀闸。 4)合上分段开关。 二、双母线(分段)接线的倒闸操作 (一)双母线(分段)倒闸操作的原则

相关文档
最新文档