高层住宅楼供配电

高层住宅楼供配电
高层住宅楼供配电

毕业设计

高层住宅楼供配电系统的设计

姓名:

学号:

班级: 11电气1

专业:电气工程及其自动化

所在系:自动化工程系

指导教师:

高层住宅楼供配电系统的设计

摘要

我国的城市建设过程中,住宅向着高层化趋势发展。高层住宅楼,因其为住户提供的安全、舒适、高效、节能的居住环境,受到了越来越多人的青睐,也成为现代人主要的居住方式。与此同时,高质量的高层住宅楼供配电系统的设计就显得尤为重要。在电气设计时既要考虑用电负荷日益增长的需要,又要满足供电的可靠性及安全性的要求。

本课题以高层建筑的供配电系统为研究对象。为了达到用户能够安全、可靠、高效用电的目的,我们对高层建筑的供配电系统整体进行设计。其中包括对建筑负荷的计算,选择恰当地供电方式;进行短路电流的计算,选择合适的导线及低压电器产品;对室内照明进行设计;对防雷接地的设计等。同时为了提高设计质量及缩短设计周期,本课题采用功能强大的建筑电气软件CAD来设计供配电系统的电路图。

关键词:电气设计;安全性;负荷计算;防雷接地;软件AutoCAD

The Design of High-rise Residential Building Power Supply

and Distribution System

ABSTRACT

In the process of urban construction in our country, the housing development trend towards upwards. High-rise residential buildings, because of its for residents to provide safe, comfortable, efficient and energy saving living environment, got the favour of more and more people, modern has become the main way of living. At the same time, the high quality of high-rise residential building design of power supply and distribution system is particularly important. In the electrical design should not only consider the increasing needs of the power load, and to meet the requirements of the reliability and security of the power supply.

This topic in power supply system of high-rise building as the research object. In order to achieve the user to the purpose of safe, reliable and efficient utilization, our power supply system of high-rise building the overall design. Including the building load calculation, choose proper power supply way; For the calculation of short-circuit current, select the appropriate conductor and low-voltage electrical products; For indoor lighting design; The design of lightning protection grounding, etc. At the same time in order to improve the design quality and shorten the design cycle, this subject adopts powerful building electrical software AutoCAD to design the circuit diagram of power supply and distribution system.

Key Words: Electrical Design ;security;Load calculation;Lightning protection and grounding;Software AutoCAD

目录

第一章绪论 0

1.1 引言 0

1.2 课题的国内外发展状况 0

1.3 课题的研究内容与方法 0

1.4 课题的研究步骤与依据 (1)

1.5 课题的研究依据 (3)

第二章负荷计算 (4)

2.1 负荷分级 (4)

2.1.1负荷 (4)

2.1.2电力负荷的分级 (4)

2.1.3 电力负荷对供电的要求 (5)

2.1.4此住宅负荷 (6)

2.2 电力负荷的计算 (6)

2.2.1电力负荷计算的计算方法 (6)

2.2.2 此住宅楼负荷计算 (8)

第三章低压配电系统设计 (13)

3.1 低压配电概述 (13)

3.1.1 低压配电系统组成 (13)

3.1.2 低压配电概况 (13)

3.2 低压电器 (16)

3.2.1 低压电器的分类及用途 (16)

3.2.2 低压电器选择的基本原则及注意事项 (17)

3.2.3 低压电器选择的基本规定 (17)

3.2.4 正常工作条件低压电器选择原则 (18)

3.3 插座的设计 (19)

3.3.1 设计原则及要求 (19)

3.3.2 插座的选择 (19)

3.3.3 插座的安装 (20)

3.4 插座具体设计要求 (20)

3.4.1 起居室 (20)

3.4.2 卧室 (20)

3.4.3 厨房 (20)

3.4.4 卫生间 (21)

第四章照明系统的设计 (22)

4.1 照明设计规范 (22)

4.1.1 照明设计的分类 (22)

4.1.2 照度的选择 (23)

4.1.3 照度设计的要求 (25)

4.2 各个房间照明设计 (25)

4.2.1 照明灯具的选择 (25)

4.2.2 客厅照明设计 (26)

4.2.3 卧室照明设计 (26)

4.2.4 餐厅照明设计 (27)

4.3 照明计算 (28)

4.3.1 利用系数计算公式 (28)

4.4.2 照明具体计算 (29)

第五章防雷与接地 (32)

5.1 民用建筑的防雷分类 (32)

5.1.1 防雷分类与等级 (32)

5.1.2 防雷接地的安全 (34)

5.2 避雷针保护范围计算 (36)

5.3 各类建筑物的防雷措施 (37)

5.4 本建筑物的各种防雷措施 (37)

第六章总结与体会 (39)

参考文献 (40)

致谢 (41)

第一章绪论

1.1 引言

随着社会的发展、科技的进步、人民生活水平的提高,我国的建筑行业突飞猛进,高层建筑应运而生,城市中各类高层超高层建筑如雨后春笋般拔地而起。由于高层建筑符合了人们对居住环境、科技、娱乐、教育等方面的要求,所以在21世纪高层建筑得以飞速发展。其中高层住宅楼,因其为住户提供的安全、舒适、高效、节能的居住环境,受到了越来越多人的青睐,也成为现代人主要的居住方式。与此同时,高质量的高层住宅楼供配电系统的设计就显得尤为重要。在电气设计时既要考虑用电负荷日益增长的需要,又要满足供电的可靠性及安全性的要求。供配电系统的设计直接影响着住宅的整体供电性能。合理的供配电系统,可以给人们的生活带来便利,改善居民的生活质量,使城市生活更加美好。

1.2 课题的国内外发展状况

20世纪90年代初至今,随着我国建筑电气行业的管理水平不断提高,新的法令、法规、规范、规程和标准等不断颁布、修订、补充和完善,并逐步与国际标准接轨,使得迅速发展的电气新技术在工程实践中的应用更加规范化[1]。

近50年以来,我国的供配电技术也取得了很大的进展。由于建筑逐渐向着建筑面积大、功能复杂、建筑设备多、能耗大的方向发展,所以,在对供配电系统进行设计时,对电气设备的要求、供电系统的可靠性等都大大提高了。随着新一代高性能智能电器的出现,使得建筑供配电系统的设计更加完善。

针对高层建筑的供配电系统的设计,它除了满足一般建筑工程的电气设计、遵循国家有关工程设计的法规和政策之外,还要遵循针对高层建筑的设计规范。

1.3 课题的研究内容与方法

本课题以高层建筑的供配电系统为研究对象。为了达到用户能够安全、可靠、高效用电的目的,我们对高层建筑的供配电系统整体进行设计。其中包括对建筑负荷的计算,选择恰当地供电方式;进行短路电流的计算,选择合适的导线及低压电器产品;对

室内照明进行设计;对防雷接地的设计等。

本课题拟采用的技术路线是通过对高层住宅楼供配电系统的负荷、线路的短路电流计算、室内的照度等进行计算。并以此来确定供配电系统的供电结构、选择恰当地配电线路及敷设方法、完成照度系统的设计等。同时为了提高设计质量及缩短设计周期,本课题采用功能强大的建筑电气软件AutoCAD来设计供配电系统的电路图。

1.4 课题的研究步骤与依据

第一步:深入学习高层住宅楼供配电系统的相关知识。第二步:熟练掌握AutoCAD软件的使用方法。第三步:完成整个住宅楼的负荷计算及短路电流计算。第四步:完成低压电器设备的选择。第五步:配电系统及防雷接地的设计。第六步:使用AutoCAD软件设计出电路图。其中使用AutoCAD软件设计照明配电箱供电系统图如图1.1所示:

图1.1 照明配电箱供电系统图

Fig.1.1 Lighting distribution box supply power system figure

电源箱供电系统图如图1.2所示:

图1.2 电源箱供电系统图

Fig.1.2 Power source box supply power system figure 电表箱供电系统图如图1.3所示:

图1.3电表箱供电系统图

Fig.1.3 Electric meter box supply power system figure

AutoCAD配电干线图如图1.4所示:

e

图1.4AutoCAD配电干线图

Fig.1.4 AutoCAD Distributing main figure

1.5 课题的研究依据

本课题设计是对某高层住宅楼的电气设计,其主要概况是:地上十八层,地下一层的住宅楼,地下一层为人防间,里面设有防毒室,配电室,供水间。本设计用到的设计依据有:

1、《民用建筑电气设计规范》JGJ 16—2008

2、《建筑物防雷设计规范》GB50016—2006

3、刘介才.工厂供电.北京:机械工业出版社,2009

4、张九根.高层建筑电气设计基础.北京:中国建筑工业出版社,2011

5、其他有关国家及地方的现行规程、规范及标准。

第二章负荷计算

2.1 负荷分级

2.1.1负荷

1.电力负荷与电量

在电力系统中,用电设备需用的电动率称为电力负荷或功率。功率是表示能量变化速率的一个重要物理量。电功率又分为有功功率,无功功率和视在功率。电阻性用电设备消耗电能的功率称为有功功率[10],其用P表示;纯电感(或纯电容)性设备不消耗电能,它与电源进行能量交换的功率称为无功功率,其用Q表示;视在功率在三相交流电

路中是3乘以线电压和线电流,其用S表示。它们之间的关系为:S=

22

P Q

所谓电量,指用电设备所需用的电能数量。有功电量表示用电设备所消耗的电能数量,无功电量表示用电设备与电源所交换的电能数量。

2.负荷计算的内容和目的

在进行高层住宅楼供电设计时,基本的原始资料为工艺部门提供的各种用电设备的产品铭牌数据,如额定容量,额定电压等,这是设计的依据。因为所安装的设备并非都同时运行,所以不能用设备额定容量来选择各种用电设备而且运行着的设备实际需用的负荷也并不是每一时刻都等于设备的额定容量,而是在不超过额定容量的范围内时大时小的变化着,所以是不能直接用额定容量(也称安装容量)来选择供电设备和供配电系统的。因而,供配电设计的第一步,是需要计算全厂和各用电设备的实际负荷。

计算负荷是确定供电系统,选择变压器容量,电气设备,导线截面和仪表量程的依据,也是整定继电保护的重要数据。计算负荷确定的是否正确,直接影响到电器和导线的选择是否经济合理。如计算负荷确定过大,将使电器和导线截面选择过大,造成投资和有色金属的浪费;如计算负荷确定过小,又将使电器和导线运行时增加电能损耗,并产生过热,引起绝缘过早老化,甚至烧毁,以致发生事故,同样给国家造成损失。为此,正确进行负荷计算是供电设计的前提,也是实现供电系统安全,经济运行的必要手段。

负荷计算主要包括:

(1)求计算电流。目的是为了合理的选择工厂各级电压供电网络,变压器容量和电器设备型号。

(2)计算尖峰电流。用于计算电压波动,电压损失,选择熔断器和保护元件等。

2.1.2电力负荷的分级

电力系统应根据对供电可靠性的要求及中断供电在政治、经济上所造成的损失及影响的程度分为一级、二级、三级负荷。独立于正常电源的发电机组,供电网络中独立于正常的专用馈电线路,以及蓄电池和干电池可作为应急电源。二级负荷的供电系统,应由两线路供电。必要时采用不间断电源(UPS)。

1.一级负荷

一级负荷为突然中断供电将造成人身伤亡或会引起对周围环境严重污染的,突然中断供电将会造成经济上的巨大损失,如重要的大型设备损坏,重要产品或用重要原料生产的产品大量报废,连续生产过程被打乱且需要长时间才能恢复生产的;突然中断供电将会造成社会秩序严重混乱或产生政治上的严重影响,如重要的交通与通信枢纽,国际社交场所,高层建筑的消防,安全照明等用电负荷[10]。

特别重要的一级负荷通常称为保安负荷。保安负荷必须备有应急电源,从而保证在工作电源失去时对保安负荷的供电,以保证企业安全生产及人员安全。其包括有:

(1)中断供电将发生中毒,爆炸和火灾等情况的负荷;

(2)特别重要场所的不允许中断供电的负荷;

(3)如正常电源中断时,必须设有处理安全停产所必须的应急照明,通信系统,火灾报警系统,保证安全停产的自动控制装置等;

(4)民用建筑中大型金属中心的关键电子计算机系统和防盗报警系统,大型国际比赛场的记分系统及监控系统等。

2.二级负荷

二级负荷为中断供电将在政治上,经济上产生较大损失的负荷,如主要设备损坏,大量产品报废,连续生产过程被打乱需要较长时间才能恢复,重点企业大量减产等;或中断供电将影响重要的用电单位正常的工作负荷,如交通枢纽、通信枢纽用点单位中的重要电力负荷等;或中断供电将造成秩序混乱的负荷等,如大型影剧院,商场等较多人员集中的公共场所,城市主要水源,广播电视,矿井主提升设备,高层建筑的电梯,商业住宅建筑等。

3.三级负荷

不属于一级,二级负荷的均属于三级负荷。对一些非连续生产的中小型企业,停业仅影响产量或导致少量产品报费的用电设备,以及一般民用建筑的用电负荷等均属于三级负荷。对这类负荷,突然中断供电造成的损失不大或不会造成直接损失。

2.1.3 电力负荷对供电的要求

1.对一级负荷必须有两个或两个以上的独立电源回路供电,且当任何一个电源失去后,能保证对全部一级负荷不间断供电。负荷容量较大或有高压用电设备应采用两路高压电源,如一级容量不大,可从电力系统或邻近单位取得第二低压电源。

对特殊重要的一级负荷,除了应由两个独立电源点供电外,还必须增设应急电源。为确保对特别重要负荷的供电,严禁将其它负荷介入应急供电系统。根据允许中断供电

的时间可分别选择下列应急电源:

(1)蓄电池静止型不间断供电装置(UPS),蓄电池及写出能带年级型不间断供电装置或柴油机电磁储能电机型不间断供电装置,适用于允许中断供电时间为毫秒级的负荷。

(2)带有自动投入装置的独立于正常电源的专用馈电线路,适用于自动装置的动作时间能满足允许中断供电时间为1.5S以上的供电系统。

2.对于二级负荷一般要有两个独立电源供电,且供电变压器也应有两台(不一定在同一变电所)。当任何一个电源失去后,能保证全部或大部分二级负荷的供电迅速恢复。

在负荷较小或地区供电条件因难时,可有一路6KV及以上专用架空线路供电;当采用电缆线路时,采用两根电缆组成的电缆段供电,每根电缆应能承受百分之百的二级负荷;为了解决线路和变配电设备的检修以及突然停电后,设备能安全停产的问题,可采用小容量的柴油发电站,其容量可由实际需要确定。

3.对于三级负荷一般只需一个电源供电。

2.1.4此住宅负荷

本设计要求小区内配电室引入一路三相四线制220/380V电源,电缆直接埋地引入,进户穿钢管保护,室外埋深0.8米。由小区变电所提供的这条220/380V电源进线,承担本小区的全部负荷。本小区负荷等级为三级。

2.2 电力负荷的计算

2.2.1电力负荷计算的计算方法

计算负荷,又称需要负荷或最大负荷。计算负荷是一个单位的持续性负荷。其热效应与同一时间内实际变动负荷所产生的最大热效应相等。在配电设计中通常采用30分钟的最大平均负荷作为按发热条件选择配电变压器,导线以及电气设备的依据,并用来说计算电压损失和功率损耗。在工程上为了方便计算也可作为电量损耗量及无用功率补偿的计算依据[4]。

计算负荷的定义:计算负荷是按发热条件选择导体和电器设备时使用的一个假想负荷。其物理意义为:按这个计算负荷持续运行的产生的热效应,与按实际变动负荷长期运行所产生的最大热效应相等。通常规定取30分钟平均最大负荷P30,Q30和S30作为该用户的计算负荷,并用P js,Q js和S js分别表示其有功,无功和视在计算负荷。计算负荷是按发热条件选择导体和电器设备的依据,并有如下关系:

P= P30=s P

js

Q= Q30=Q s(2.1)

js

S= S30=S s

js

P,P30,s P分别为最大工作班的有功计算负荷,30min平均最大负荷,最大式中js

负荷。

尖峰电流指单台或多台用电设备持续1秒左右的最大负荷电流,一般取启动电流的周期分量作为计算电压损失,电压波形和电压下降以及选择电器和保护元件的依据。在校验瞬动元件时,还应考虑启动电流的非周期分量。

一二级负荷用以确定备用电源或应急电源。

季节性负荷,从经济运行条件出发,用以考虑变压器的台数和容量。

负荷计算的方法:目前负荷计算常用的方法有需用系数法(也称需要系数法),二项式法和利用系数法。前两种方法在国内使用最为普遍。利用系数法的理论根据是概率论和数理统计,因而计算结果比较接近实际,适用于各种范围的负荷计算,但计算结果繁琐,因此目前还没有更广泛的应用。在方案设计阶段,需要对用电负荷进行估算,可以采用单位面积功率法或单位容量法。我国地域宽广,各地经济发展情况不一,单位面积功率,单位指标也各不相同。

1.需用系数法

该计算方法是把设备功率乘以需用系数,直接求出计算负荷。由于这种计算方法比较简单,因此得到了很广泛的应用。但当用电设备台数少而功率相差悬殊时,利用需用系数法的得到的计算结果往往偏小,故不适用于低压配电线路的计算。为此在初步设计或扩大初步设计阶段作为负荷统计或施工图设计确定变配电所的电力负荷时采用[3]。

2.二项式法

该方法是设计负荷包括用电设备组的平均功率,同时考虑数台大功率设备工作时的附加功率。这种方法比较简便,但计算结果往往偏大,一般用于低压配电支干线和配电箱的负荷计算,在施工图阶段对各种机械加工厂或各种其中电焊设备作配电线路或动力配电箱选型中也经常采用。

上面都是常用的计算方法,根据本设计的特殊情况本设计主要采用需用系数法和单位面积功率法相结合的方法。

由于住宅楼主要的负荷为照明和动力部分,而且以照明为主要。因此,在统计负荷时,先对整个住宅楼的照明做一个计算负荷的统计。

现在再简要介绍本设计的计算方法和相应的参考。

负荷密度法和单位指标法是目前对民用建筑计算负荷常用的计算方法。

负荷密度法计算有功功率s P。

P=a×S/1000(KW) (2.2)

s

式中 a :预计负荷密度(单位面积功率)W/㎡;

S: 建筑面积(㎡);

利用负荷密度计算有功功率为规划值或为可能发生的最大负荷值,在确定计算负荷时,还应结合具体情况,乘上不同的需用系数。即:

js P =s P ×x K (2.3)

式中 js P :有功功率 (KW) x K :系数

负荷密度法适用于照明功率及非工业负荷功率的计算。

其中部分用电单位负荷密度参考值参考芮静康主编的《现代工业与民用供配电设计手册》。近年来,在城市电网制订发展规划中,符合预测值多采用负荷密度法来确定。特别在是在城市中,按功能将建筑划分为不同的等级,根据功能特点,功能区负荷性质,参照已有城市的经验值,结合本市建筑特点,及其具体情况,利用负荷密度法制定将来的拓展计划,是比较接近实际情况的。

2.2.2 此住宅楼负荷计算

本次设计的高层住宅楼,对其的照明负荷统计采用采用负荷密度法(单位容量法)计算。

由于要设计的此高层住宅楼共18层,其中地下一层,作为一个人防的地点,地上十八层,在十层和十一层之间有一个设备间,主要是对水压和气压的一点补偿。整幢大楼每一层的结构布局基本一致,可按一层的结构面积进行计算。

1.室内照明计算

此高层的每一层均为一梯六户,并且采用对称结构,每户面积分别为135㎡,125㎡,155㎡, 135㎡,125㎡,155㎡,所以,每一层平面的面积为:

S=(135+125+155)×2=830㎡

根据照明手册,结合实际,每一层的负荷如表2.1所示:

表2.1 每一层负荷表

Table 2.1 Each layer load table 名称

面积(㎡) 单位负荷密度a(W /㎡) 需用系数x K 功率因数Cos θ 一层 830 3.5

0.4 0.85

s P =a×S/1000=3.5×830/1000=2.91KW

js P =s P ×x K =1.16KW

js Q =js P ×tanθ=0.72Kvar

js S =22js js P Q +=1.36KV A

js I =3N js

U S =2.07A

2.楼梯间及走廊照明

根据实际,每一层的楼梯间及走廊的面积为:

S=21.6+39.04=60.64㎡

单位面积功率为2W/㎡,楼梯及走廊负荷如表2.2所示:

表2.2 楼梯及走廊负荷表

Table 2.2 The stairs and corridors load table 名 称

面积(㎡) 单位负荷密度a(W /㎡) 需用系数x K 功率因数Cos θ 楼梯间及走廊 60.64 2

0.9 0.85

s P =a×S/1000=2×60.64/1000=0.12KW

js P =s P ×x K =0.11KW

js Q =js P ×tanθ=0.07Kvar

js S =22js js P Q +=0.2KV A

js I =3N js

U S =0.31A

3.每个房间其它用电

对每一户内插座的统计按提高型住宅插座计算:

每一户房间要求如表2.3所示:

表2.3 每一户房间要求表

Table 2.3 Each room requirements table 插座类型用途

起居室

(厅) 主卧室 次卧室 厨房 卫生间 工作室 二、三孔双联插座

(组)

4 3 2 1 1 2 三孔插座

3 2 2 2 2 2

每一户内插座总数的统计如表2.4所示:

表2.4 每一户内插座总数的统计表

Table 2.4 Each household indoor socket of the total number of statistics table 插座类型

135㎡房间(个) 125㎡间(个) 155㎡间(个) 二、三孔双联组合

插座

13 12 14 三孔插座

24 23 28 总计 37 35 42

所以插座的总数为:

N=(37+35+42)×2=234(个)

其中,每一个插座的功率按100W 进行计算,则有:

s P =234×100/1000=23.4KW

其需用系数为1,功率因数cos θ=0.7,所以:

js P =23.4KW

js Q =js P ×tanθ=23.87Kvar

js S = 22js js P Q +=33.43KV A

js I =3N js

U S =151.95A

所以一层的单元的照明总负荷为:

js P ∑=24.67KW

js Q ∑=24.66Kvar

一层平面总的照明负荷为:

js S =22()()js js Q P +∑∑ =34.88KV A

js I =

3N js U S =53.00A

4.地下室 此高层住宅楼的地下一层为人防间,里面设有防毒室,,配电室,供水间,对其负

荷计算如表2.5所示:

表2.5 地下室负荷表

Table2.5 The basement load table 名称

面积(㎡) 单位负荷密度a(W/㎡) 需用系数 功率因数c osθ 地下室 850 2 0.9 0.85

s P =a×S/1000=2×850/1000=1.70KW

js P =s P ×x K =1.57KW

js Q =js P ×tanθ=0.97Kvar

js S =22js js P Q + =1.74KV A

js I =3N js

U S =2.64A

5.设备层

此高层住宅楼的第十层和第十一层之间有一设备层,主要功能为对消防水压及生活用水水压进行加压。对其负荷统计如表2.6所示:

表2.6 设备层负荷表

Table 2.6 Device layer load table 名 称

面积(㎡) 单位负荷密度a(W/㎡) 需用系数 功率因数Cos θ 设备层 830 2

0.6 0.85

s P =a×S/1000=2×830/1000=1.66KW

js P = s P ×x K =1.00KW

js Q =js P ×tanθ=0.62Kvar

js S =22js js P Q + =1.18 KV A

js I = 3N js

U S =1.79A

6.消防电梯,生活电梯的负荷统计:

电梯共两部,采用20KW 的电动机进行曳引。

单梯:

X K 取0.6,c osθ取0.5,N U =380V ,

js P =s P ×X K =20×

0.6=12KW js Q =js P ×tanθ=12×1.73=20.78Kvar

js S =22js js P Q +=24KV A

js I =3js N S U =36.46A

双梯:

js P =24KW

js Q =20.78Kvar

js S =12×

2=48KV A js I =3js N S U =72.93A

7.整个大楼的总负荷统计

照明负荷:

js S = 22

()()js js P Q +∑∑=1049.39KV A js I = 3js N S U =1594.38A

动力负荷:

js S =22()()js js P Q +∑∑ =257.43KV A

js I =3js N S U =391.12A

总共的负荷统计;

js S =22

()()js js P Q +∑∑ =1306.34KV A js I =3js N S U =1984.78A

第三章低压配电系统设计

3.1 低压配电概述

3.1.1低压配电系统组成

低压配电由配电变电所(通常是将电网的输电电压降为配电电压)、高压配电线路(即1千伏以上电压)、配电变压器、低压配电[1]线路(1千伏以下电压)以及相应的控制保护设备组成[6]。

低压断路器:低压断路器又称自动开关,它是一种既有手动开关作用,又能自动进行失压、欠压、过载、和短路保护的电器。它可用来分配电能,不频繁地启动异步电动机,对电源线路及电动机等实行保护,当它们发生严重的过载或者短路及欠压等故障时能自动切断电路,其功能相当于熔断器式开关与过欠热继电器等的组合。而且在分断故障电流后一般不需要变更零部件,已获得了广泛的应用。

低压配电开关:1)负荷开关:负荷开关,顾名思义就是能切断负荷电流的开关,要区别于高压断路器,负荷开关没有灭弧能力,不能开断故障电流,只能开断系统正常运行情况下的负荷电流,负荷开关由此而得名。(2)隔离开关:隔离开关是高压开关电器中使用最多的一种电器,它本身的工作原理及结构比较简单,但是由于使用量大,工作可靠性要求高,对变电所、电厂的设计、建立和安全运行的影响均较大。刀闸的主要特点是无灭弧能力,只能在没有负荷电流的情况下分、合电路措施。

3.1.2低压配电概况

低压配电系统,是指从终端降压变电所的低压侧到用户内部低压设备的电力线路,其电压一般为380/220V。

1.设计低压配电系统时要注意以下各点:

(1)应保证对重要负载的供电可靠性,第一类负荷和重要的第二类负荷应有备用电源。

(2)一般应将动力和照明分别配电。配电系统要接线简单,操作方便,便于检修。

(3)由建筑外引来的配电线路,应在市内靠近进线处便于操作维护的地方装设进线开关。

(4)单相用电设备应适当配置,力求三相平衡。对于三相负荷不平衡的场所,由单相负荷不平衡所引起的中性线电流不得超过变压器低压侧额定电流的25%,且任何一项的负荷电流都不得超过额定电流值。低压配电箱如图3.1所示:

图3.1 低压配电箱

Fig.3.1 Low voltage distribution box

2.一般配电方式

电能通过输配电线路输送到用户,进行合理分配。电能的输送和分配方式有多种,通常以电流种类,电压高低、相数或线数进行分类。建筑中常用的有以下4种:(1)三相三线制用于高压配电线路。

(2)三相四线制用于中性点接地的低压配电线路。

(3)单相二线制用于照明线路或单相电动机的配电。

(4)三相五线制用于基本的建筑电气三相配电系统。

在低压配电网中,输电线路一般采用三相四线制,其中三条线路分别代表A,B,C三相,不分裂,另一条是中性线N(区别于零线,在进入用户的单相输电线路中,有两条线,一条我们称为火线,另一条我们称为零线,零线正常情况下要通过电流以构成单相线路中电流的回路,而三相系统中,三相自成回路,正常情况下中性线是无电流的),

某住宅小区供配电系统设计

For pers onal use only in study and research; not for commercial use 学号6 9 《工厂供电》 课程设计 (2010级本科) 题目:_某住宅小区供配电系统设计_ 学院:物理与机电工程学院 专业:电气工程及其自动化 作者姓名:甘孝田 指导教师:赵文忠职称:教授 完成日期:2012年12 月27 日

工厂供电课程设计任务书

四.需收集和阅读的资料及参考文献(指导教师推荐)

【1】刘涤尘、王明阳、吴政球?电气工程基础[M].武汉:武汉理工大学出版社.2003年【2】张学成.工矿企业供电设计指导书[M].北京:北京矿业大学出版社.1998年【3】刘介才.工厂供电简明设计手册[M].北京:机械工业出版社.1993年 【4】刘介才.实用供配电技术手册[M].北京:中国水利水电出版社.2002年 【5】刘介才.工厂供电[M].北京:机械工业出版社.1997年 【7】JGJ16-2008民用建筑电气设计规范 【8】GB50054-95低压配电设计规范 【9】GB50052-95供配电系统设计规范 【10】GB50217-2007电力工程电缆设计规范 【11】GB50060-92 3?110KV高压配电装置设计规范 指导教师签名:赵文忠 2012年12 月14 日

目录 一、设计说明 .............................................................. 1.. 1.1工程概况 ......... ... ..................................................... .1 1.2设计依据 (1) 1.3设计原则 (1) 1.4小区概况 (1) 二、小区负荷计算 .......................................................... 1.. 三、无功补偿方式 (3) 3.1无功补偿方式.......................................................... 3. 3.2无功补偿容量.......................................................... 3. 3.3并联电容器的选择及制 (4) 四、变配电所位置和型式的选择 .............................................. 4. 4.1 变配电所位置的确定 (4) 4.2变配电所的总体布置 (4) 五、主变压器台数和容量的确定 .............................................. 5. 5.1变压器主变台数的选择.......................................................... 5. 5.2变压器容量的选择 (5) 六、变配电所主接线方案的选择 .............................................. 5. 6.1变电所主接线方案的评价 (6) 七、短路电流的计算 ........................................................ 7. 7.1短路计算的意义和方法 (7) 7.2相关节点的短路计算............................................................ 7. 7.2.4 K-1点的短路电流计算 (8) 7.2.5 K-2点的短路电流计算 (8) 八、变电所低压侧一次设备的选择与校验 (9) 8.1低压母线的选择与校验 (9) 8.2低压电缆、设备的选择与校验 (10) 九、变压器保护设置 (13) 9.1变电所10kV馈线保护 (14)

高层住宅楼供配电

毕业设计 高层住宅楼供配电系统的设计 姓名: 学号: 班级: 11电气1 专业:电气工程及其自动化 所在系:自动化工程系 指导教师:

高层住宅楼供配电系统的设计 摘要 我国的城市建设过程中,住宅向着高层化趋势发展。高层住宅楼,因其为住户提供的安全、舒适、高效、节能的居住环境,受到了越来越多人的青睐,也成为现代人主要的居住方式。与此同时,高质量的高层住宅楼供配电系统的设计就显得尤为重要。在电气设计时既要考虑用电负荷日益增长的需要,又要满足供电的可靠性及安全性的要求。 本课题以高层建筑的供配电系统为研究对象。为了达到用户能够安全、可靠、高效用电的目的,我们对高层建筑的供配电系统整体进行设计。其中包括对建筑负荷的计算,选择恰当地供电方式;进行短路电流的计算,选择合适的导线及低压电器产品;对室内照明进行设计;对防雷接地的设计等。同时为了提高设计质量及缩短设计周期,本课题采用功能强大的建筑电气软件CAD来设计供配电系统的电路图。 关键词:电气设计;安全性;负荷计算;防雷接地;软件AutoCAD

The Design of High-rise Residential Building Power Supply and Distribution System ABSTRACT In the process of urban construction in our country, the housing development trend towards upwards. High-rise residential buildings, because of its for residents to provide safe, comfortable, efficient and energy saving living environment, got the favour of more and more people, modern has become the main way of living. At the same time, the high quality of high-rise residential building design of power supply and distribution system is particularly important. In the electrical design should not only consider the increasing needs of the power load, and to meet the requirements of the reliability and security of the power supply. This topic in power supply system of high-rise building as the research object. In order to achieve the user to the purpose of safe, reliable and efficient utilization, our power supply system of high-rise building the overall design. Including the building load calculation, choose proper power supply way; For the calculation of short-circuit current, select the appropriate conductor and low-voltage electrical products; For indoor lighting design; The design of lightning protection grounding, etc. At the same time in order to improve the design quality and shorten the design cycle, this subject adopts powerful building electrical software AutoCAD to design the circuit diagram of power supply and distribution system. Key Words: Electrical Design ;security;Load calculation;Lightning protection and grounding;Software AutoCAD

毕业设计方案(住宅小区供配电设计方案)

摘要 本设计主要阐述了现代化小区各系统电气设计的设计依据、原则和方法及设计选择的结论。本设计共主要包括强电部分设计部分设计及安防部分设计。 强电部分主要内容包括:低压配电系统、照明系统及防雷接地系统的设计,其中包括负荷计算、照度计算等。 本小区电气设计作为毕业设计,其目的是通过切身实践,综合运用所学知识,理论联系实际,锻炼独立分析和解决建筑电气设计问题的能力,为即将面临的工作奠定坚实的基础。 关键词:配电系统负荷防雷接地 目录 引言1 一设计简况2 二配电系统2 <一)设计要求2 <二)低压配电系统线路的选择2 <三)设备安装4 <四)电能计量方式选择5

三照明系统5 <一)照明系统的概述5 <二)照度方式6 <三)光源和灯具7 <四)照度计算8 <五)配电箱布置12 <六)负荷计算<需要系数法)12 <七)设备选型15 四防雷接地系统设计17 <一)建筑物防雷等级确定17 <二)防雷内容与设计方案20 总结23 致谢24 参考文献25

引言 本次设计的主要针对是现代化住宅小区楼内供配电系统设计。通过具体的实例工程设计,初步掌握高层建筑配电系统设计的基本方法,更好的将理论和实践相结合,将大学三年来所学的课程及知识应用到自己的专业中去,也为将来的工作打下良好的基础。 本工程为11层的民用普通高层建筑,为二类高层建筑,按三级负荷供电,三类防雷建筑物进行电气系统设计。在本设计中,要求完成对住宅小区楼内配电系统设计,主要包括低压供配电系统、照明系统、插座系统、防雷与接地系统。论文针对民用高层建筑电气的设计和使用需要,,侧重于电气基本理论和基本知识。设计中,总体按照民用建筑设计规范来建立设计的整体思路,并完成配电系统的负荷计算、设备选型、系统构成、照度计算等。 一设计简况 本次设计的主要针对是现代化住宅小区楼内供配电系统设计。通过具体的实例工程设计,初步掌握高层建筑配电系统设计的基本方法,更好的将理论和实践相结合,将大学三年来所学的课程及知识应用到自己的专业中去,也为将来的工作打下良好的基础。 本工程为11层的民用普通高层建筑,为二类高层建筑,按三级负荷供电,三类防雷建筑物进行电气系统设计。在本设计中,要求完成对住宅小区楼内配电系统设计,主要包括低压供配电系统、照明系统、插座系统、防雷与接地系统。论文针对民用高层建筑电气

某小区供配电系统设计

南阳理工学院本科生毕业设计(论文) 学院(系):电子与电气工程学院 专业:电气工程及其自动化 学生: 指导教师: 完成日期 2014 年 5 月

南阳理工学院本科生毕业设计(论文) 某小区供配电系统设计 Design for the Power Supply and distribution system of a residence community 总计: 36 页 表格: 10 个 插图: 9 幅

南阳理工学院本科毕业设计(论文) 某小区供配电系统设计 Design for the Power Supply and distribution system of a residence community 学院:电子与电气工程学院 专业:电气工程及其自动化 学生姓名: 学号: 指导教师(职称): 评阅教师: 完成日期: 南阳理工学院 Nanyang Institute of Technology

某小区供配电系统设计 [摘要]住宅小区供配电系统的稳定运行直接影响着人们的日常生活及秩序。因此研究小区供配电系统如何更好的实现安全、可靠、经济运行具有现实的意义。本课题初步对住宅小区的供配电系统进行设计,并根据国家相关标准对所设计的内容进行规范化。分析小区的原始数据和供电特点,对小区各类负荷进行计算;通过计算负荷选择变压器的容量和数目完成变电所的设计;合理选择电气主接线方式;根据短路电流选择合适的电力电缆;确定建筑物防雷等级,做好小区的防雷接地保护。设计过程中不仅要保证供电的质量和安全性,还应尽量满足供电的经济性,节省能源和材料。 [关键词]计算负荷;短路电流;变压器;供配电设计;防雷接地 Design for the Power Supply and Distribution System of a Residence Community Electrical Engineering and Automation Specialty MA Jun-yao Abstract: Residence community for safe and reliable operation of the distribution system directly affects people's daily lives.This project is initially designed for the power supply and distribution system of the residence community. And also the design is normalized in accordance with the relevant national regulations and standards. So the power supply and distribution system in residence community district how to realize the safe, reliable and economic operation has realistic meaning. Analysis the raw data for the residence community and load calculation of the residence community. Based on the calculated load the measures of power supply and distribution of the residence community is designed. It includes the electric main wiring design, transformer and distribution substation design. Meanwhile the appropriate electric power cable are selected according to the short-circuit current. And the protection design about grounding for lightning is also essential. Not only must the quality and safety of power supply be ensured, but also the economical power supply, energy-saving and material-saving should be met as much as possible. Key words:Load calculation; Short-circuit current; Transformer; Power supply and distribution design; Grounding for lightning 目录

住宅小区供配电系统设计

2012.06 167 建筑规划与设计 摘要:随着技术的进步,人们对城市配电网络供电可靠性要求越来越高,因此要求住宅小区的配电系统设计接线方式简单灵活、运行可靠。住宅小区的供配电设计应坚持“以人为本” 的原则,在确保安全可靠的大前提下,根据工程特点、建设规模、当地气候条件、地区供电条件及经济发展状况等诸多因素,兼顾技术先进性和经济合理性,综合确定小区的供配电方案。要正确处理近期建设和远期发展的关系,以近期为主,适当考虑发展的可能。 关键词:生活住宅小区;中压配电系统;低压配电系统1 前言 社会经济的快速发展使人们对居住条件的要求越来越高,各式各样的住宅小区层出不穷,在了解了小区的位置、环境、交通及户型等外观后,人们开始更加注重供配电等内在条件的质量。因此,安全可靠、技术先进、经济合理的小区供配电系统显得日趋重要。 2 供电电源 住宅小区一般应由10kV电源供电。住宅小区中的住宅楼和其他公用设施的用电负荷分级应符合现行的《建筑设计防火规范》和《高层民用建筑设计防火规范》等的规定。当住宅小区内仅有三级负荷时,供电电源可取自附近的110~35/10kV区域变电所的若干10kV供电回路,当住宅小区内同时具有一、二级负荷时,则应根据区域变电所的电源路数和变压器台数确定供电电源,若区域变电所的110~35kV电源仅为一路,则小区的备用电源应从另外的区域变电所引来。当住宅小区内的一、二级负荷较小,且设置自备电源比从城市电网取得第二电源更经济合理时,可设置自备电源。对规模较大的小区,当区域变电所的10kV出线走廊受到限制或配电装置间隔不足且无扩建余地时,宜在小区内设置10kV开闭所(开关站)。开闭所宜与10kV变电站联体建设。总之,住宅小区的供电方式必须与当地供电部门协商确定。 3 配变设置3.1 负荷计算 以前,住宅小区用电负荷的计算主要有单位面积法和需要系数法等,各地的计算标准千差万别。新的《住宅设计规范》出台后,对各类住宅的用电负荷标准、电表规格、进户线截面都规定了下限值。很多省、市、自治区也根据此规范并结合本地区情况,出台了地方住宅设计标准,对上述用电指标均作了等同或高于《住宅设计规范》的规定。据此,一般采用单位指标法进行负荷计算。 即Pc=ΣKx×Pe×N式中Pe——单位用电指标,如:4kW/户(不同户型的用电指标不同),可根据《住宅设计规范》或各地区的地方住宅设计标准的规定选取。 kWN——单位数量,即户数(对应不同面积户型的户数)Kx——需要系数,《住宅设计规范》对其取值未作规定,有些地方标准有规定,但是差别较大。如果地方标准无规定,可参照《全国民用建筑工程设计技术措施-节能专篇/电气》的推荐值,表2.2.4-1的规定取,具体按接三相配电计算时所连接的基本户数选定:9户以下取1;12户取0.95等。 对小区内的商业、办公等配套公建及路灯用电负荷需用其他方法单独计算。 3.2 配变选型 住宅小区配电的视在功率 S=Σ Pc/ 式中——功率因数,由于住宅以照明负荷和家用电器为主,一般取0.8—0.9(参见《住宅设计规范》条文说明6.5.1条)。当小区内有电梯、水泵、中央空调等动力设备时,其负荷应单独计算后再汇总。消防用电负荷一般不计入S——视在功率,kVA在计算设置变压器的容量时,应考虑变压器的经济负荷系数和功率因数补偿效果。变压器的经济负荷系数在0.6—0.75之间,变压器的负荷率应不大于0.85。10kV供电的功率因数应不低于0.9,否则应进行无功补偿。 由于住宅楼以单相负荷为主,容易造成三相不平衡负荷超出变压器每相额定功率15%的情况,因此,小区内应选用接线组别为D,yn11的变压器。 住宅小区用电负荷季节差别甚至昼夜差别都很大。所以宜选用空载损耗低的节能型变压器,如S9系列或非晶合金变压器。 小区内设置的变电站的型式和数量必须根据小区规模、建筑类别(别墅、多层、高层等)及配电总容量并结合当地电业部门的供电系统规划来确定。 目前住宅小区内设置的变电站的类型有多种:独立型、户内型和分散型。独立型变电站一般用于规模较小或负荷比较集中的住宅小区;分散型变电站一般用于规模较大、负荷分布比较分散的住宅小区,大多采用箱体移动式结构(即箱变),且一般设置开闭所(开关站);户内型变电站一般用于高层且单体面积较大的住宅建筑。 供电变压器的台数及单台容量可按以下原则确定:对于独立型或户内型变电站,配电变压器的安装台数宜为两台,单台变压器的容量不宜超过1000kVA;对于分散型变电站,根据小容量多布点的原则,对以多层住宅为主的小区单台变压器的容量不宜超过630kVA;对别墅区单台变压器的容量不宜超过315kVA。 3.3 配变选址 住宅小区内变电站的设置应遵循以下原则: (1)尽量接近小区负荷中心且进出线方便,以降低电能损耗、提高供电质量、节省设备材料。 (2)考虑合理的负荷分配及适宜的供电半径。单台变压器的容量一般不超过上节所述;中压供电半径:负荷密集地区不超过2km,其他地区应不超过3kin;380/220V配电线路的配电范围一般不宜超过250m。 (3)当小区内有高层、多层或别墅等多种类型住宅时,宜按不同类型分别划分供电范围。 (4)当小区规模较大时,如果分期开发,应尽量按分期片区划分供电范围。 (5)一般按小区内干道的自然分隔划分供电分区,避免大量管线穿越马路、交叉重叠。 (6)与住宅楼(尤其是住户的南卧室)保持一定距离,一般不低于6m (现行规范无明确规定),以满足防火、防噪声、防电磁辐射等要求。 (7)远离通信机房、微机机房和消防控制室等有防电磁干扰要求的房间。 4 低压配电 低压配电系统,应保障安全、配电可靠、经济合理、维护方 住宅小区供配电系统设计之我见 陈 勇 中国美术学院风景建筑设计研究院 下转169页

住宅小区供配电系统设计

XX学院 毕业论文(设计) 住宅小区供配电系统设计Residential quarters for the distribution design 系别物理与电子信息工程系 专业电气工程及其自动化 学号 XX 姓名 XX 指导教师 XX 2009年 5月10日

摘要 要提高高层建筑配电系统的可靠性,要正确选择各类配电设备的容量,就必须科学、合理的进行负荷计算。本文对符合计算中的相关问题进行了分析和探讨,就重要设备的容量选择做了较为详细的论述,提出了一些进一步提高配电系统可靠性的措施,并结合工程实例进行负荷计算,计算结果证明本文所述方法是正确合理,可在实际中应用。高层建筑比一般建筑遭受雷击的概率要大得多,而一旦遭受雷击,损失将非常严重。另外,普通建筑物防雷系统不但不能保护高层建筑物内的电子设备与计算机系统,反而可能会引入雷电。因此,高层建筑的防雷保护就越显重要,相应地对防雷保护提出了更高的要求。本文对于高层建筑物的防雷保护措施做了较为仔细的分析。 关键词:配电系统;负荷计算;防雷设计;照明 Abstract In order to improve the reliability of power distribution system of high building,choice capacity of power distribution debice rightly,it is necessary tocalculate charge rightly,the author analyacs and investigatcs relative question with charge calculation,expatiates particularly capacity choice of important equipment,puts forward these measure being used to improve the reliability of power distribution system,makes charge calculation combination to project example,the result shows that these means is right and reasonable,these means can guide project practice. High buiding is easy suffered from lightning stroke,in case being suffered lightning stroke,it should bring huge losing,lightning protection system of common building can not protect electronic device,on the contrary,it may intoduce lifhtning therefore high building’s lightning protection is more important.The author analyses and research these question of over voltage and of lifhtning stroke,puts forward these means of lightning protescition of in high building. Keywords: power distribution system ;load calculation synthetic; lightning protection;Illumination

某高层住宅供配电设计

摘要 本设计是按照建筑供配电的要求,以国家规范为准则以安全用电为用电、节约电能、经济环保为理念!在满足对供电的要求的同时,同时兼顾施工的可行性以及节约经济预算为理念,设计出满足人们对智能化建筑要求的满意工程,在设计中严格遵守国家的相关规定以及标准,执行国家的方针政策,从而达到科学,人性化设计的现代化电气工程设计内容主要包括负荷计算,供电电源、电压的选择、变压器的容量的选择、类型以及台数、变电所的选址、各个楼层的供电线线路中的短路电流的计算、供配电系统的主接线方式、高低压设备和导线电缆的选择以及校验,防雷接地的设计。设计中需要绘制、参照相应的CAD图然后进行分别运算设计最后将设计整理成文档形式的报告。 关键词: 国家标准、负荷计算、供电线路、防雷接地、CAD图

第一章工程概况 某高层综合楼,总23层,地上22层,地下1层。总建筑面积28807.1平方米,其中地下室建筑面积为2916平方米,建筑物总高度为99.8米。年预计雷击次数0.11次,为二类防雷建筑物。地下一层为附建式6级人防地下室,平时做汽车库,战时作为一个防护单元的二等人员掩蔽部,掩蔽人数为800;地面一到四层为商场,三层以上均为办公用房;屋顶为设备层,变电所设在一层。

第二章负荷分级、负荷计算及无功功率补偿 第一节、负荷分级 该工程属于一类高层建筑,用电多为一、二级负荷,用电负荷分级如下: 地下室:应急照明,消防设备用电(送、补风机,消防泵)及地面用生活水泵为一级负荷;战时送风机,消防楼梯口排污泵为二级;其余为三级负荷。 地面:排烟风机、屋顶正压风机、消防电梯、应急照明、防火卷帘门及普通客梯的电力属一级负荷;其余均为三级负荷。 第二节、负荷数据 本工程负荷包括照明、电力及消防负荷。所有电源均由一层变电所低压出线直接提供,其中一~四层商场以及二十一、二十二层、屋顶的电源用电缆供电,五到二十层的楼层配电箱用插接式母线槽供电。计量除五到二十层分层集中设电表计量以外,其余均在变电所计量。该综合楼个部分负荷数据见表1~3。

高层住宅楼供配电

高层住宅楼供配电 Prepared on 22 November 2020

毕业设计 高层住宅楼供配电系统的设计姓名: 学号: 班级:11电气1 专业:电气工程及其自动化 所在系:自动化工程系 指导教师:

高层住宅楼供配电系统的设计 摘要 我国的城市建设过程中,住宅向着高层化趋势发展。高层住宅楼,因其为住户提供的安全、舒适、高效、节能的居住环境,受到了越来越多人的青睐,也成为现代人主要的居住方式。与此同时,高质量的高层住宅楼供配电系统的设计就显得尤为重要。在电气设计时既要考虑用电负荷日益增长的需要,又要满足供电的可靠性及安全性的要求。 本课题以高层建筑的供配电系统为研究对象。为了达到用户能够安全、可靠、高效用电的目的,我们对高层建筑的供配电系统整体进行设计。其中包括对建筑负荷的计算,选择恰当地供电方式;进行短路电流的计算,选择合适的导线及低压电器产品;对室内照明进行设计;对防雷接地的设计等。同时为了提高设计质量及缩短设计周期,本课题采用功能强大的建筑电气软件CAD来设计供配电系统的电路图。 关键词:电气设计;安全性;负荷计算;防雷接地;软件AutoCAD

TheDesignofHigh-riseResidentialBuildingPowerSupplyandDistributionSystem ABSTRACT Intheprocessofurbanconstructioninourcountry,,becauseofitsforresidentstoprovidesafe,co mfortable,efficientandenergysavinglivingenvironment,gotthefavourofmoreandmorepeople,,,an dtomeettherequirementsofthereliabilityandsecurityofthepowersupply. ,reliableandefficientutilization,,chooseproperpowersupplyway;Forthecalculationofshort-circuitcurrent,selecttheappropriateconductorandlow- voltageelectricalproducts;Forindoorlightingdesign;Thedesignoflightningprotectiongrounding,, thissubjectadoptspowerfulbuildingelectricalsoftwareAutoCADtodesignthecircuitdiagramofpo wersupplyanddistributionsystem. KeyWords:ElectricalDesign;security;Loadcalculation;Lightningprotectionandgrounding;SoftwareAutoCAD

某小区供配电系统设计

, 南阳理工学院 本科生毕业设计(论文)( @ 学院(系):电子与电气工程学院 专业:电气工程及其自动化 学生: 指导教师: : 完成日期 2014 年 5 月

$

南阳理工学院本科生毕业设计(论文) 某小区供配电系统设计 Design for the Power Supply and distribution system of a residence community 总计: 36 页 表格: 10 个 插图: 9 幅

南阳理工学院本科毕业设计(论文) 某小区供配电系统设计 Design for the Power Supply and distribution system of a residence community 学院:电子与电气工程学院 专业:电气工程及其自动化 学生姓名: 学号: 指导教师(职称): 评阅教师: 完成日期: 南阳理工学院 Nanyang Institute of Technology

某小区供配电系统设计 [摘要]住宅小区供配电系统的稳定运行直接影响着人们的日常生活及秩序。因此研究小区供配电系统如何更好的实现安全、可靠、经济运行具有现实的意义。本课题初步对住宅小区的供配电系统进行设计,并根据国家相关标准对所设计的内容进行规范化。分析小区的原始数据和供电特点,对小区各类负荷进行计算;通过计算负荷选择变压器的容量和数目完成变电所的设计;合理选择电气主接线方式;根据短路电流选择合适的电力电缆;确定建筑物防雷等级,做好小区的防雷接地保护。设计过程中不仅要保证供电的质量和安全性,还应尽量满足供电的经济性,节省能源和材料。 [关键词]计算负荷;短路电流;变压器;供配电设计;防雷接地 Design for the Power Supply and Distribution System of a Residence Community Electrical Engineering and Automation Specialty MA Jun-yao Abstract: Residence community for safe and reliable operation of the distribution system directly affects people's daily project is initially designed for the power supply and distribution system of the residence community. And also the design is normalized in accordance with the relevant national regulations and standards. So the power supply and distribution system in residence community district how to realize the safe, reliable and economic operation has realistic meaning. Analysis the raw data for the residence community and load calculation of the residence community. Based on the calculated load the measures of power supply and distribution of the residence community is designed. It includes the electric main wiring design, transformer and distribution substation design. Meanwhile the appropriate electric power cable are selected according to the short-circuit current. And the protection design about grounding for lightning is also essential. Not only must the quality and safety of power supply be ensured, but also the economical power supply, energy-saving and material-saving should be met as much as possible. Key words: Load calculation; Short-circuit current; Transformer; Power supply and distribution design; Grounding for lightning

现代智能住宅小区10KV0.4KV供配电系统设计

摘要 本次设计的课题是住宅小区10kV供电系统的一次设计。依据配电自动化的内容和国内外配电自动化的发展现状,本着“安全性、可靠性、经济性以及易维护性”的原则,完成了本次设计。 以我国现行的各有关规范规程等技术标准为依据,再根据任务书提供原始资料,参照有关资料及书籍,对各种方案进行比较而得出最为合适的方案。这次设计的主要内容包括小区负荷的计算,短路电流计算,主要电气设备型号和参数的确定,无功补偿设计,防雷保护装置的设计。 供电系统采用的是降压箱式变电站,具有10kV和38个0V两电压等级,10kV一侧接与小区旁边经过的110kV变电站的10kV母线,380V主要用于小区用户及小区公共场所的用电。 关键词:箱式变电站,短路计算,无功补偿,接地

THE POWER SUPPLY SYSTEM DESIGN OF RESIDENTIAL Abstract: The design of this residential area is the subject of the preliminary design of 10kV power supply system. The development present condition that contents and domestic and international power distribution that automates according to the power distribution automate. The power supply system designed is very important, if the system is broken, the entire residential area will affect the power supply, so the high reliability requirements. Therefore, the design must take into account the power system security, reliability and economy. With our country each current relevant specification regulations etc. technique standard is basis, again provide original data according to the task book, according to interrelated data and book, carry on compare vs various scheme but get most suitable scheme.This manual wiring through the residential load calculation, short circuit current calculation,the main electrical equipment to determine the model and parameters, reactive power compensation design, lightning protection and over voltage protection. The power distribution system step-down box-type substation with 10kV and 380V 2 a voltage, 10kV and 110kV substation side of the access bus 10kV, 380V electricity mainly for residential users.

高层建筑供配电系统设计实例.

高层建筑供配电系统设计实例 兰海生深圳市建筑设计研究总院有限公司 摘要:通过工程设计实例,介绍了超高层建筑的配电系统设计(负荷估算和计算、变压器的选择、高低压配电系统)、变配电所设置等设计,阐述了超高层建筑配电系统设计要点及注意事项。 关键词:电气设计;配电系统;设计 一、工程概况 某工程总建筑面积56561.88M2,地下一层,主要位车库,地面1~3层为裙楼,主要位公寓与商业,4至23层伟塔楼,建筑物总高75.6米,为综合楼,属一类高层建筑。在扩大初步设计的估算中采用负荷密度法和单位指标法,施工图设计时采用需要系数法计算,最后以估算中的两法进行评价。 二、高层建筑电气的负荷估算和计算 1负荷估算 把全楼的负荷分为动力和照明两大部分。动力负荷包括冷冻机组全系统和各类水泵、电梯衍、锅护的配套动力设备及送排风机等。照明负荷包括裙楼各层、办公、公寓的照明、插座,以及风机盘管和窗式、分体式空调器等。经多个“高建”扩大初步设计估算的综合取动力总平均系数K动=0.5,照明总平均系数K 动=0.44。动力总设备容量是根据各工种提供的动力用电量的总和,照明总设备容量是按负荷密度法和单位指标法计算的。大堂、商场等场所的照明计算负荷按负荷密度法估算,负荷密度列于下表。 项目名称负荷密度(W/m2)备注 大堂120豪华装修、采用白炽灯、含风机盘管 商场80含风机盘管 写字楼40含风机盘管 设备用房20含风机盘管 库房10含风机盘管 汽车库10 按单位指标法估算,单位用电指标客房按 1.0-1.5kW/间,公寓(兼办公)按12.5-17kW/套(468套,约130-170m2,内设电热水器4-6kW,3-4台分体式空

住宅小区供配电设计方案

住宅小区供配电设计 目录 第一章前言??1 第二章工程概述??2 第三章电气照明设计??3 3.1 照明系统的概述??3 3.1.1 照明系统的发展现状??3 3.1.2 照明计量单位??3 3.2 照度方式和种类??3 3.2.1 照明方式??3 3.2.2 照明种类??4 3.3 照度计算??5 3.3.1 利用系数法??5 3.3.2 单位容量法??6 3.4 小区的电气照明设计??8 3.4.1 电气照明设计的基本原则??8 3.4.2 电气照明详细设计计算??8 3.5 插座系统??143.5.1 插座系统的概述??14 3.5.2 一般规定(规)??14 3.5.3 插座的安装??14 3.5.4

小区住宅的插座系统设计??16 3.5 该小区标准层照明设计??17 第四章低压配电系统设计??18 4.1 高层建筑一般规定??4.2 低压配电系统线路的选择??4.2.1 低压线路接线方式??4.2.2 导线和电缆的选择??4.3 低压配电系统电气设备的选择??4.3.1 基本要求??4.3.2 漏电保护??4.4 配电变压器的选择??4.5 小区的低压供配电系统设计?? 住宅小区供配电设计 4.5.1 小区整体低压配电设计(见附录1) ??4.5.2 小区1 号楼与 4 号楼低压配电设计(见附录2) ??4.5.3 小区2 号楼与3 号楼低压配电设计(见附录2)??4.5.4 小区商业、电梯、车库、消防、物管用电低压配电设计(见附录3)??4.6 负荷计算的方法??4.7 小区住宅的负荷计算?? 第五章防雷接地系统设计??32 5.1 防雷与接地系统概述?? 5.1.1 防雷系统概述??5.1.2 建筑物的防雷等级??5.1.3 高层建筑物的防雷措施??5.1.4 接地系统概述??4.4 小区1#楼接地设计??32 32 32 33 34 37 第六章技术经济分析??38 第七章结论??39 参考文献??39

相关文档
最新文档