摘要

本设计为南京市XX公司办公楼中央空调系统,拟为之设计合理的中央空调系统,

为室内工作人员提供舒适的工作环境。

设计内容包括: 空调冷负荷的计算;空调系统的划分与系统方案的确定;冷源的选择;空调末端处理设备的选型;风系统的设计与计算;室内送风方式与气流组织形式的选定;水系统的设计、布置与水力计算;风管系统与水管系统保温层的设计;消声防振设计;等内容。

本设计依据有关规范考虑节能和舒适性要求,设计的空调系统采用风机盘管—新风系统。

关键字:办公楼;中央空调;风机盘管—新风系统;性能比较。

Abstract

The graduation project designs a central air conditioning system for XX official building in Nanjing City, so as to create a comfortable work environment for the stuff.

It contains: cooling load calculation; the estimation of system zoning; the selection of refrigeration units; the selection of air conditioning equipments; the design of air duct system and calculation; the estimation of air distribution method and the selection of relevant equipments; the design of water system and its resistance analysis; the insulation of air duct plant and chilled water pipes; noise and vibration control; etc.

According to some correlation standard, allow for energy safe and indoor comfort, the air condition system of the design is Fan coil units (FCUs)--fresh air system.

Key words: official building; Central air conditioning;

Fan coil units (FCUs)--fresh air system;

The function compare.

1绪论

1.1我国暖通空调的现状及其发展

进入90年代后,我国的居住环境和工业生产环境都已广泛地应用空调,空调技术已成为衡量建筑现代化水平的重要标志之一。90年代中期,由于大中城市电力供应紧张,供电部门开始重视需求管理及削峰填谷,蓄冷空调技术提到了议事日程。近年来,由于能源结构的变化,促进了吸收式冷热水机组的快速发展,以及热泵技术在长江中下游地区的应用。

随着生产和科技的不断发展,人类对空调技术也进行了一系列的改进,同时也在积极研究环保、节能的空调产品和技术,已经投入使用了冰蓄冷空调系统、燃气空调、VAV空调系统、地源热泵系统等。暖通空调技术的发展,必然会受到能源、环境条件的制约,所以能源的综合利用、节能、保护环境及趋向自然的舒适环境必然是今后发展的主题。

1.2 建筑空调系统节能国内外研究现状

1.2.1 建筑空调系统节能国外研究现状

能源是整个经济系统的基本组成部份,作为一个能源消耗大国,美国在节能和提高能源利用率方面投入了大量的人力、物力。在美国的整个能源消耗中,有约1/3以上消耗在建筑能耗上,这些能耗用来满足人们的热舒适、空气品质、提高人们的生活质量。美国暖通空调制冷工程师协会、美国制冷协会、美国冷却塔协会等组织、美国能源部以及众多暖通空调设备生产厂家如York, Carrier等都为建筑节能做出了很大贡献。特别是美国制冷设备生产厂商投入了大量的资源研究高性能冷水机组,使得冷水机组单位制冷量的能耗仅为20世纪70年代的62.3%。美国在空调冷源水系统方面的研究也卓有成效,在冷却水系统方面着重于降低冷却水流量,以达到减少冷却水泵能耗的目的。日本是一个资源贫困的国家,其主要能源来自进口,同时又是一个能源高消费国家。因此,节能和提高能源的利用率对日本来讲有着重要的意义。长期以来,在建筑节能方面,日本做了大量工作,颁布了许多节能法规,提出了建筑节能的评价方法。日本的一些设备生产厂家对空调和制冷设备的投入也很大。Daikin公司首推的变频VRV系统,为中小型建筑安装集中式空调系统创造了条件;Sany公司则在直燃式冷水机组上成绩卓著。世界各国大力发展可再生能源作为空调冷热源用能。地源热泵供暖空调是一种使用可再生能源的高效节能、环保型的工程系统。在美国地源热泵系统占整个空调系统的20%左右;瑞士40%的热泵为地祸热泵,瑞典65%的热泵为地祸热泵。

1.2.2 建筑空调系统节能国内研究现状

我国是一个人均资源相对贫乏的国家,因此节能降耗有着十分重要的意义。近

年来,由于国民经济的快速发展,使我国的能源显得越来越紧张。

1)建筑空调系统节能国内研究现状概况

随着经济建设的不断深入和人们生活水平的不断提高,空调建筑物越来越多,建筑物消耗的能量也越来越大,甚至出现了空调系统与经济建设争抢电力资源的情况。因此,在建筑物节能显得十分迫切。在我国建筑总能耗中,空调系统的能耗占有相当大的比重,因此研究探讨空调系统的节能就显得十分重要。在建筑物空调系统运行能耗中,冷源系统的能耗是最大的。近年来,我国暖通空调学术界和工程界在空调冷源系统的节能方面做了大量的研究工作。研究工作主要集中在冷源系统的形式选择上,对压缩式冷水机组和吸收式冷水机组的技术经济比较研究较多,通过对众多方案的分析已经基本达成共识:吸收式冷水机组节电而不节能,对其在我国的应用应区别对待,对于有余热可以利用的地区,应大力提倡使用吸收式冷水机组,而一般建筑物则应采用蒸汽压缩式制冷。当然,在进行冷热源系统的选择时,还要

考虑建筑物所在地的气象条件、电力供应状况、能源情况、空调系统有无采用余热回收的可能性等方面的问题。

2)我国建筑空调系统节能研究有待解决的问题

通过对一些地区空调系统的调查发现,设计人员在涉及选用冷水机组时多考虑其额定工况下的全负荷性能,而对其部分负荷性能的考虑较少。在风冷式冷水机组和水冷式冷水机组的选择应用上我国制冷工程界也存在着认识上的差异。我国在冷源水系统方面的研究目前较少,一般都是按冷水机组的样本提供的冷却水量和冷冻水量进行冷却水泵和冷冻水泵的选择。对于水系统的水泵是否运行节能则关注不多。事实上,对于冷水机组的运行而言,冷凝器和蒸发器都要求定流量,因此,对于冷水机组部分负荷状态运行时,水泵的输出都是全负荷输出,水系统的全年运行能耗是相当大的。因此水系统的节能具有很大的潜力。

1.3 空调系统的设计与建筑节能

空调制冷技术的诞生是建筑技术史一项重大进步,它标志着人类从被动适应宏观自然气候发展到主动控制建筑微气候,在改造和征服自然的过程的又迈出了坚实的一步。但是对空调的依赖也逐渐成为建筑能耗增长的最主要的原因。制冷空调系统的出现为人们创造了舒适的空调环境,但20世纪70年代的全球能源危机,使制冷空调系统这一能源消耗大户面临严重考验,节能降耗成为空调系统设计的关键环节。据统计,我国建筑能耗约占全国总能能耗的35%,空调能耗又约占建筑能耗的50%~60%左右。由此可见,暖通空调能耗占总能耗的比例可高达22.75%。因此,建筑中的空调系统节能已成为节能领域中的一个重点和热点。于是降低空调能耗也被纳于建筑节能的任务中,如何更好的利用现在的空调技术服务人类同时又能满足建筑能耗的要求,是现阶段专业技术人员的工作要点。而暖通空调设计方案的好坏直接影响着建筑环境的质量和节能状况。随着科学技术的迅速发展以及对节能和环保要求的不断提高,暖通空调领域中新的设计方案大量涌现,针对同一个设计项目,往往可

以有很多不同的设计方案可供选择,设计人员要进行大量的方案比较和优选工作,设计方案技术经济性比较正在成为影响暖通空调设计质量和效率的一项重要工作。如何对暖通空调设计方案进行科学的比较和优选,是暖通空调设计人员在实际设计工作中经常遇到的一个重要技术难题。

1.4 空调的发展和前景

1.4.1 变频空调的发展

变频空调是目前空调消费的流行趋势。它与一般空调比,有着高性能运转、舒适静音。节能环保、能耗低的显著特点,它的出现改善了人们的生活质量。

日本作为变频空调强国,从20世纪80年代初开始到现在,变频空调已占其空调市场的90%左右。变频空调在我国发展速度相当快,不到8年时间就达到与日本先进水平同步。进入2000年,国内个别企业将直流变频技术与PAM控制技术结合应用,使空调完全进入变频空调的最高领域。它不仅使直流变频压缩机的优越性能充分发挥,更能利用数码特点,准确提高能效,达到节能51%的目的。

1.4.2 无氟空调的发展

臭氧层破坏是当前全球面临的重大的环境问题之一,由于以前空调业所采用的传统制冷剂对臭氧层有破坏作用及产生温室效应,对大气造成破坏,因而无氟空调是众所期待的产品。近年来以海尔空调为代表的无氟空调的出现,标志着无氟空调时代的来临。

1.4.3 舒适性空调的发展

健康是空调业发展的主题之一。以前的空调采用了多种健康技术,如负离子、离子集尘、多元光触媒等,这些技术的运用使空调产品的健康性能得到了极大提升。海尔空调把负离子、离子集尘、多元光触媒、双向换新风、健康除湿等领先技术在内的高科技手段组合起来使用,发挥了巨大的威力,而未来空调进步的一个方向也就是对各种技术的灵活使用。

空调气流的舒适度是健康空调的另一个标准。传统空调的送风方式简单直吹人体,易引起伤风、感冒、头痛、关节痛等不舒适状态,因此新近推出的风可以从周围环绕,而不是对人直吹,通过改善空调送风的气流分布,令人感觉更舒适的空调——环绕立体送风、三维立体风的健康空调成了热销产品也就不足为奇了。

1.4.4 一拖多

空调器的发展从一个侧面反映了我国居民居住环境的巨大变化,也为自身发展指明了方向。1993年以前,中国空调市场主要以一拖一为主,1993年海尔推出一拖

二空调后,率先将空调业引入了一拖多时代。目前海尔一拖多空调产量突破了百万台足以证明其市场消费能力。海尔MRV网络变频一拖多中央空调的出现以及众多厂家的家用中央空调产品使得家庭中央空调迅速普及。

1.4.5其它空调新技术的发展

1)HEPA酶技术

HEPA酶杀菌技术,对于0.3微米以上的粉尘吸附率可达99.9%,对结核菌、大肠菌等有害细菌具有高效杀菌能力,对霉菌的生长也有很强的抑制作用。

2)冷触媒技术

冷触媒这一技术采用日本专利,是一种低温低吸附的材料,根据吸附--催化原理,在常温下就能对甲醛等有害物质边吸附边分解成二氧化碳和水,这种触媒不需要再生,不需更换,使用寿命长达十年以上。

3)体感温度控制技术

智能装在遥控器上的感温元件,感知室内人们活动范围的温度,并将信息发射到主机接收器上,使主机随时调整运行状态,实现真正的体感温度控制自动化。

4)人感控制技术

人感控制技术利用双红外感应器控测人的方位,自动调节送风方向(左送风、中送风、右送风或全方位送风),风随人行。

5) PTC电辅助加热技术

PTC电辅助加热技术,可在超低温条件下迅速制热,效力强劲,安全可靠,可长期使用。

总之,伴随着科技和社会的进步,节能、环保、健康、智能控制已成为空调发展的大趋势。

1.5 防治“非典”时期空调系统的应急措施(风机盘管+新风系统)

进入空调降温时,面对“非典”蔓延的高峰期,不适当的运行空调,很可能导致“非典”的交叉感染,扩大“非典”传播,必须对此有高度重视。需要非常注意的是各大型商业建筑、公共建筑,这些建筑一般设集中制冷站,再通过送风系统和冷水系统把冷量送到各个房间。这时,就很容易通过空调系统使建筑物内空气互相掺混,某处有污染的空气很有可能通过空调系统传播到其它房间,从而导致交叉感染。尤其是有些高层建筑不能开窗,或有许多无外窗的内区房间,更容易出现问题。必须引起高度重视。防治“非典”的一个很有效的措施就是加强通风,其原理就是通过大量的室外空气进入室内,将室内可能存在的“非典”病毒通过换气排出室外,从而抑制了其发作的可能性。然而如果是内部循环通风,则不能起到排出病毒的作用,反而会使病毒积累,甚至使浓度逐渐增加。因此正确地运行空调通风系统至关重要。下面针对风机盘管+新风系统方式介绍应采取的相应措施。

多数办公楼、宾馆客房、医院病房都采用这种空调方式,该方式有单独的新风

机将新鲜空气送入房间,风机盘管有不同的回风方式。一种回风方式是各房间单独安装风机盘管,各房间的回风经过盘管冷却后送出,回风仅在自身房间内循环,不同房间之间互不流通。另一种回风方式是各个楼层的多个房间统一通过吊顶掺混回风后经过风机盘管冷却后送入各个房间,不同房间之间的回风有交叉。不论何种方式的风机盘管加新风系统,首先都要注意避免新风系统混入从建筑排出的污染空气,同时要注意风机盘管的清洁。根据不同的回风方式,风机盘管加新风方式在运行时要注意如下问题具体:

1)各房间单独回风的系统

首先要保持新风入口清洁,不被污染。新风机房位于大楼的地下或者顶部,一般直接通过风道从室外取新风。要注意取风口的位置,不要使其吸入建筑排风。有些系统是从风机房内取新风,对这种形式应防止楼内空气通过机房门进入机房并吸入新风机,应严格保证新风机房密闭,同时要保证新风机房清洁,必要时安装新风道,从室外取风,此外,新风过滤网也要作到定时清洗。新风竖井或者新风风道要注意清洁通畅。

风机盘管加新风系统的排风系统多数是和厕所排风合用,为保证通风效果,建议将厕所排风系统全天连续运行。

此外凝结水盘是污垢存积的地方,也要保持清洁。由于凝水是从房间回风在通过盘管制冷后凝结产生的,目前还难以确认空气中的病毒是否会在凝水中存活,为防患未然,建议运行管理人员对各风机盘管的凝结水盘统一清洁,消灭病毒生存的载体。

2)吊顶统一回风的系统

有一些小型办公楼采用此类系统,和各房间单独回风的方式不同,采用这种方式的建筑基本上隔断仅到吊顶,吊顶上空是互相连通的,各房间的空气相互交叉。这种系统和全空气系统相同,也存在各房间空气相互掺混,污染物有可能在建筑各区域之间传播,潜在危险较大。对于这类系统,除了要注意保持新风不被污染、凝结水盘清洁外,要尽可能地停用风机盘管。可通过降低冷冻水温度,加大冷冻水流量,寻找增大新风量的途径等手段增加新风供冷能力来满足供冷要求。

某办公楼空调系统工程施工组织设计

xx公司综合办公楼空调系统工程施工组织设计 第一章编制依据 1.1施工方案依据 本施工组织设计依据国家现行规范、标准,以及我公司按照ISO9001质量体系标准编制的质量体系程序文件,企业管理标准和管理经验,业主提供的施工设计图纸以及本工程中标文件。 1.2本设计主要引用的规范、标准: 1、《建设工程项目管理规范》GB/T50382-2001 2、《建设工程监理规范》GB50319-2000 3、《建筑给水排水及采暖工程施工质量验收规范》GB50243-2002 4、《通风与空调工程安装工程施工及验收规范》GB50243-2002 5、《采暖通风与空气调节规范》GBJ19-87 6、《制冷设备安装工程施工及验收规范》GB50274-98 7、《机械设备安装工程施工及验收规范》GB50231-98 8、《压缩机、风机、泵安装工程施工及验收规范》GB50275-98 9、《工业金属管道工程施工及验收规范》GB50235-97 10、《现场设备工业管道焊接工程施工及验收通用规范》GB50236-98 11、《工业设备及管道绝热工程施工及验收规范》GBJ126-98 12、《电气装置安装工程施工及验收规范》GB50254-94 13、《工业安装工程质量检验评定统一标准》GB50252-94 14、《工业金属管道工程质量检验评定标准》GB50184-93 15、《工业设备及管道绝热工程质量检验评定标准》GB50185-93 16、《采暖标准图集》辽宁省建筑设计标准化办公室编 17、本工程施工图要求

18、VRV(R410A新冷媒)安装技术手册 19、国家现行的有关规范、标准及规定 第二章空调工程概况 2.1工程概况 2.1.1工程名称 **市索玛尼科研所综合办公楼空调系统安装工程。 2.1.2 工程介绍 本工程主体工程建筑面积19810 m2.地下二层,地上六层, 是一个集办公、实验室、生产车间融为一体的综合性办公大楼。其中空调工程有效的施工面积为15300 m2,夏季制冷采用 VRV系统,冬季取暖采用常规暖气取暖方式。本工程的空调工程仅指夏季制冷采用 VRV系统,总造价451万元,单位造价295元/ m2。 2.1.2工程地点 **市六一路99号,六一广场东侧180米。 2.1.3招标人 索玛尼公司 2.2工作内容 2.2.1 VRV空调系统设备采购及安装。 2.2.2空调冷媒系统及空调新风系统及地下厨房送风系统的安装。 2.2.3空调冷凝水系统安装、新风机组水管道系统安装 2.2.4系统的调试、验收、培训及售后服务、保修。 2.3施工关键部位 本工程的关键部位为冷媒管道安装、连接及系统隐蔽工程等部分。 第三章项目施工管理目标 3.1工期目标 3.1.1总体工程目标控制: 空调的施工开始时间在2006年7月10日,总工期为80天。80天的工期按照整体工程的总进度,又分3个阶段: 第1阶段为50天,在主楼框架,封顶完成后,本项目进入现场开始施工作业,主要工程包括冷媒管路敷设、风管路的制作、安装、风机盘管的安装、保温等。完成空调主要设备的安装,做好隐蔽工程的验收,交给装修工程。

北京某办公楼中央空调设计案例

北京某公司

目录 第一部分、热泵系统简介 (3) 一、水源热泵系统特点 (3) 二、地源热泵系统特点 (4) 第二部分、项目简介 (5) 一、项目概况 (5) 二、设计理念 (5) 第三部分、空调系统设计 (5) 一、设计依据 (5) 二、设计计算参数 (6) 三、系统原理 (6) 四、末端设计 (9) 五、机房设计 (9) 六、冷热源设计 (10) 七、投资汇总 (11) 第四部分、运行经济分析 (11) 一、系统运行费用 (12) 二、年投资分析 (13)

第一部分、热泵系统简介 一、水源热泵系统特点 水源热泵是一种利用地球浅层水源,吸收的太阳能和地热能而形成的低温低位热能资源,并采用热泵原理,通过少量的高位电能输入,实现低位热能向高位热能转移的一种技术。 地球浅层水源温度一般都十分稳定。水源热泵机组工作原理就是冬季从水源中提取能量,由热泵原理通过空气或水作为载冷剂提升温度后送到建筑物中。通常水源热泵消耗1kW的能量,用户可以得到4kW以上的热量。 水源热泵机组的优、缺点: 1)水源热泵可利用的水体温度冬季为10-15℃,水体温度比环境空气温度高, 所以热泵循环的蒸发温度提高,能效比也提高。而夏季水体为15-20℃,水体温度比环境空气温度低,所以制冷的冷凝温度降低,使得冷却效果好于风冷式和冷却塔式,机组效率提高。据美国环保署EPA估计,设计安装良好的水源热泵空调系统,平均来说可以节约用户30~40%的供热制冷空调的运行费用。 2)运行稳定可靠:水体的温度一年四季相对稳定,其波动的范围远远小于空气 的变动。是很好的热泵热源,水体温度较恒定的特性,使得热泵机组运行更可靠、稳定,也保证了系统的高效性和经济性。不存在空气源热泵的冬季除霜等难点问题。 3)地下水含有各种矿物质、化学元素、对热泵机组换热器形成腐蚀、结垢现象, 影响机组的使用寿命,同时由于机组结垢影响换热量,考虑设计余量,增加初投资。 4)随着全世界淡水资源的紧缺,作为储备资源的地下水体,多数国家都限制其 开发利用。 5)用后尾水的回灌问题增加部分运行费用。 6)水井循环泵通常为潜水泵,潜水泵工作环境恶劣,维护量大,同时水井也要 定期维护。

郑州某办公楼空调系统设计

青岛农业大学 毕业论文(设计) 题目:郑州某办公楼空调系统设计 姓名: 学院: 专业: 班级: 学号: 指导教师:

毕业论文(设计)诚信声明 本人声明:所呈交的毕业论文(设计)是在导师指导下进行的研究工作及取得的研究成果,论文中引用他人的文献、数据、图表、资料均已作明确标注,论文中的结论和成果为本人独立完成,真实可靠,不包含他人成果及已获得青岛农业大学或其他教育机构的学位或证书使用过的材料。与我一同工作的同志对本研究所做的任何贡献均已在论文中作了明确的说明并表示了谢意。 论文(设计)作者签名:日期:年月日 毕业论文(设计)版权使用授权书 本毕业论文(设计)作者同意学校保留并向国家有关部门或机构送交论文(设计)的复印件和电子版,允许论文(设计)被查阅和借阅。本人授权青岛农业大学可以将本毕业论文(设计)全部或部分内容编入有关数据库进行检索,可以采用影印、缩印或扫描等复制手段保存和汇编本毕业论文(设计)。本人离校后发表或使用该毕业论文(设计)或与该论文(设计)直接相关的学术论文或成果时,单位署名为青岛农业大学。 论文(设计)作者签名:日期:年月日 指导教师签名:日期:年月日

目录 摘要------------------------------------------------------------3 Abstract--------------------------------------------------------4 第1章工程概况-------------------------------------------------6 1.1 建筑概况-------------------------------------------------6 1.2 室外设计参数---------------------------------------------6 第2章建筑负荷计算---------------------------------------------8 2.1基本计算参数设定------------------------------------------8 2.1.1室内设计参数------------------------------------------8 2.1.2围护结构热工参数--------------------------------------9 2.1.3人员、设备和照明作息时间------------------------------10 2.1.4其他设计参数------------------------------------------11 2.2设计依据--------------------------------------------------13 2.3计算内容及基本公式----------------------------------------13 2.3.1 计算内容----------------------------------------------13 2.3.2 计算方法----------------------------------------------14 2.3.3 手算冷负荷 -------------------------------------------15 2.4天正暖通负荷计算------------------------------------------21 2.4.1天正负荷计算参数设定----------------------------------21 2.4.2天正软件负荷计算结果与分析----------------------------21 第3章冷热源系统设计--------------------------------------------25 3.1冷水机组的选择--------------------------------------------25 3.2水泵的选择计算--------------------------------------------25 第4章空气-水系统的布置设计-------------------------------------27 4.1空气-水系统的特点------------------------------------------27 4.2状态点的确定----------------------------------------------27 4.3 空气-水系统的计算-----------------------------------------28 第5章气流组织的设计--------------------------------------------33 5.1送、回风方式及风口形式-------------------------------------33 5.1.1送风方式及风口形式-------------------------------------33 5.1.2回风方式及风口形式-------------------------------------33 5.2全空气系统气流组织计算-------------------------------------33 5.3送、回风口的风量及尺寸-------------------------------------33 5.4空气-水系统气流组织计算------------------------------------34 第6章空调水系统设计---------------------------------------------35 6.1水系统的布置和选取-----------------------------------------35 6.2水系统的水力计算-------------------------------------------35 第7章管道的设计-------------------------------------------------38 7.1消声隔振措施-----------------------------------------------38 7.2管道的保温防腐设计-----------------------------------------38 总结-------------------------------------------------------------39 参考文献---------------------------------------------------------40

10万平方写字楼中央空调主机选型方案

西安ⅩⅩ集团配套部软件园项目空调能源比较方案 1.项目概要 2.技术原则 3.能源方案 4.能源状况 5.能源状况分析 6.方案选型 7.初投资比较 8.运行费用比较 9.结论 10.附件(投资计算书)

1.项目概要 西安ⅩⅩ集团配套部软件园外包服务大楼项目,总建筑面积 5.4万平方米。冷负荷5660kw,热负荷约3600 kw;孵化器热负荷1180;培化楼热负荷400kw;餐厅热负荷437 kw。 远大推荐采用可靠、经济、环保的空调系统,采用BZ250ⅩDH1×2直燃机满足系统冷热负荷的需求。制冷能力5815kw,制热能力5582 kw。 2.技术原则 根据西安ⅩⅩ集团配套部软件园项目要建成国际化的、具有领航和示范作用的形象定位要求,应对能源系统提出极高的技术原则: 第一,要确保能源供应的绝对可靠。 第二,应采用世界领先的能源科技,建成一流的精品工程。 第三,系统高效低耗,具有最佳的经济性。 第四,清洁环保,社会效益显著,符合可持续发展方针。 3. 能源方案 远大推荐的能源系统,采用燃气直燃机的能源方式,为项目提供空调冷热源需求。其构成如下表。 4、能源状况 开闭所建设费:500元/KVA 基本电费:20元/KW.月 平均电价:0.95元/ KW 电功率因数:0.85 天然气价格:1.9元/m3天然气热值:8500kcal/ m3 开机时间:12小时/天天然气接入:约25万元 热网入网费:30元/m2热网价格:123元/蒸吨

5、能源状况分析: a.西安高新区空调的使用特点决定了电价属于非居民照明用电电价,平均电价约:0.95 元/ KW。 b.由于采用电制冷方式所需要的电力配套负荷巨大,需要建设相应的电力开闭所,而 开闭所到各大楼的电缆地沟等铺设费用依然要收取。 c.天然气接入费:约25万元。 d.高薪区热网建设费:30元/平方米; d.远大Ⅸ型直燃机制冷额定负荷COP为1.34(含电耗),综合负荷1.529。 6、方案选型 方案A:选用2台远大BZ250ⅩDH1型溴化锂直燃机满足服务大厦及相关建筑(87400m2)的制冷和采暖。 方案B:选用2台530KW的水冷式离心机组满足服务大厦制冷;采用热电厂热网通过换热实现服务大厦及相关建筑采暖。 说明:主机设备的冷量按成倍数配置是考虑了使用中的负荷调节问题。冷却水泵的型号不同是因为远大采用冷却水大温差小流量技术来降低水泵的电耗,在保证同样制冷量的前提下,最大程度的节约用电。 7 8、运行费用比较: 运行费用的计算是在同等的制冷采暖负荷、设备运行时间和同样的负荷率等条件下,根 据不同方案所对应的设备需要的运行费的测算值。可能与实际的使用情况有一定差异。 注意:以下运行费用的计算只针对主机,冷却水变频系统未予以考虑。 制冷运行参数计算依据来源约克离心机、远大直燃机参数样本。 计算公式:天然气耗量×气价×年小时数×负荷率=制冷运行气费

哈尔滨望江集团办公楼空调系统工程设计 说明书

摘要 本设计为哈尔滨望江集团办公楼空调系统工程设计。哈尔滨望江集团办公楼属中小型办公建筑,本建筑总建筑面积4138m2,空调面积2833m2。地下一层,地上八层,建筑高度33.9m。全楼冷负荷为191千瓦,全楼采用水冷机组进行集中供给空调方式。 此设计中的建筑主要房间为办公室,大多面积较小,且各房间互不连通,应使所选空调系统能够实现对各个房间的独立控制,综合考虑各方面因素,确定选用风机盘管加新风系统。在房间内布置吊顶的风机盘管,采用暗装的形式。将该集中系统设为风机盘管加独立新风系统,新风机组从室外引入新风处理到室内空气焓值,不承担室内负荷。风机盘管承担室内全部冷负荷及部分的新风湿负荷。风机盘管加独立新风系统由百叶风口下送和侧送。水系统采用闭式双管同程式,冷水泵三台,两用一备;冷却水泵选三台,两用一备。 在冷负荷计算的基础上完成主机和风机盘管的选型,并通过风量、水量的计算确定风管路和水管路的规格,并校核最不利环路的阻力和压头用以确定新风机和水泵。 依据相关的空调设计手册所提供的参数,进一步完成新风机组、水泵、热水机组等的选型,从而将其反应在图纸上,最终完成整个空调系统设计。 关键词:风机盘管加独立新风系统;负荷;管路设计;制冷机组:冷水机组

Abstract The design for the Harbin Wangjiang Design Group office building air conditioning system. Harbin Wangjiang Group is a small and medium-sized office building office buildings, the total floor area of building is 4138m2, air-conditioned area is 2833m2. There are eight floor of the building, building height is 33.9m. Cooling load for the entire floor, 191 kilowatts, the whole floor using Central Cooling Chillers to focus on the way . This design of the main room of the building for office, most of them is very small, and the rooms are not connected, the selected air-conditioning system should be able to achieve independent control of each room, considering the various factors to determine the selection of fan-coil plus fresh air system. Arrangement in the room ceiling fan coil units, using the dark form of equipment. Set the focus on fan-coil system, plus an independent air system, fresh air from the outdoor unit to deal with the introduction of a new wind to the indoor air enthalpy value, do not bear the load of indoor. All bear the indoor fan-coil cooling load and part of its new rheumatoid load. Fan-coil plus an independent air system sent by the Venetian and the under side air delivery. Closed water system with a dual-track program, three cold-water pump, dual-use a prepared; cooling pumps three elections, one prepared by dual-use. In the cooling load calculation based on the completion of the selection of host and fan coil units, and air volume, the calculation of water, the wind pipe and water pipes to determine the specifications of the road and check the resistance to the most disadvantaged and the loop to determine the pressure head new fans and pumps. Based on the relevant manuals provided by air-conditioning design parameters, and further completion of the new air units, water pumps, hot water units, such as the selection, which will be reflected in their drawings, the final design of the entire air-conditioning system Key words:PAU+FCU systems; load; pipeline design; refrigeration machine;Chillers

【开题报告】行政办公楼建筑中央空调工程设计

开题报告 建筑环境与设备工程 行政办公楼建筑中央空调工程设计 一、综述本课题国内外研究动态,说明选题的依据和意义 改革开放之前,人们的日常生活中鲜见制冷空调设备,国内能够生产制冷空调设备的企业也屈指可数,更谈不上专业化生产。随着我国国民经济的发展和人民生产水平的不断提高,宾馆、酒店、写字楼、商业中心、文化体育、教育、医疗、国防、科研、居民住宅、特殊工业厂房等建筑的增长,带动了中央空调行业的快速发展。目前,人们对居住条件生活环境的舒适性的要求越来越高,对中央空调的需求越来越大,对中央空调节能、舒适、健康更加关注。 在我国建筑总能耗中,空调系统的能耗占有相当大的比重,因此研究探讨空调系统的节能就显得十分重要。在建筑物空调系统运行能耗中,冷源系统的能耗是最大的。近年来,我国暖通空调学术界和工程界在空调冷源系统的节能方面和医疗净化空调做了大量的研究工作。研究工作主要集中在冷源系统的形式选择上,对压缩式冷水机组和吸收式冷水机组的技术经济比较研究较多,通过对众多方案的分析已经基本达成共识:吸收式冷水机组节电而不节能,对其在我国的应用应区别对待,对于有余热可以利用的地区,应大力提倡使用吸收式冷水机组,而一般建筑物则应采用蒸汽压缩式制冷。当然,在进行冷热源系统的选择时,还要考虑建筑物所在地的气象条件、电力供应状况、能源情况、空调系统有无采用余热回收的可能性等方面的问题。 空调设计是作为建筑环境与设备工程专业学生所必须要掌握的重要的专业知识和专业技能。本次设计是对专业知识的综合掌握、合理利用。对于行政办公楼,在采用合理的暖通设计方法掌握建筑土建资料信息的同时,运用本专业相关知识,记录设计步骤,运用CAD辅助设计软件完成其暖通建筑施工图的绘制。使自己的设计方案能通过图纸完美体现,并能准确的指导建筑安装、施工,达到毕业设计的目的。 本设计项目为行政办公楼建筑中央空调工程设计。该建筑共4层,层高为3米,各层面积为770㎡,总面积为3080㎡左右。主要为各种性质的办公室和会议

华中科技大学暖通空调毕业设计—西安市某办公楼空调系统设计

毕业设计[论文] 任务书姓名班号院系 同组姓名指导老师 一、课题名称 西安市某办公楼空调系统设计 二、课题内容 1.设计地点:西安 2.夏季室内设计温度:26-28℃ 3.夏季制冷,冬季供暖系统设计 三、课题任务要求 1.空调系统冷负荷,热负荷计算 2.空调系统水力计算 3.用CAD绘制空调系统施工图及系统图 4.空调系统设备选型 5.完成毕业设计论文

四、同组设计者 五、主要参考文献 1.陆耀庆,《实用供热空调设计手册》,中国建筑工业出版社; 2.赵荣玉,《空气调节》,中国建筑工业出版社; 3. 采暖通风空气调节设计规范 GBJ19-87 4.有关空调设计资料、图集; 5. 柴慧娟,《高层建筑空调设计》,中国建筑工业出版社. 指导老师签字_____________ 教导主任签字_____________ 年月日 (此任务书装订时放在毕业设计报告第一页)

空调工程设计任务书 一、设计原始资料 1、某办公楼建筑图纸(8层),包括建筑平、剖面图13张图纸,本建筑为八 层综合大楼,以中小型办公室,标准客房为主。 2、本建筑位于西安市,按当地气象条件计算。 3、动力资料:按选定的冷热源形式进行设计,本设计采用夏季冷源,冬季 热源,均由风冷热泵机组提供。 二、设计内容与要求 设计内容包括:设计计算书和设计图纸 (一)计算说明部分 1、空调负荷计算 2、空调系统方案选择 3、空调设备选择计算 4、空调房间气流组织计算 5、空调系统风道设计 6、水系统设计计算 7、管道保温消声设计与设备减震设计 8、设计及施工说明 (二)设计图纸部分 1、设计与施工说明1:100 2、设备材料表1:100 3、空调系统水原理图1:100 4、空调系统风管平面图1:100 5、空调系统水管平面图1:100 6、空调设备安装大样图1:10 7、空调水管轴侧图1:50 (三)设计要求 1、设计说明书按一定格式编写,除设计要求部分外要有封面,目录, 后附参考资料名称。设计计算部分可适当采用表格。要求计算准确,

办公楼中央空调设计系统案例

办公楼中央空调设计系统案例 工程概况:XX办公大楼是集培训大厅、会议、总部办公等功能一体的现代化大楼,机关正用地28亩,实际用地25亩,该大楼主楼高8层,总建筑面积12380m2,其中空调面积约11142m2,是一项空调能耗较大的工程。 1、空调方案 本设计主要选用大型风冷单螺杆式热泵机组,采用独立新风加风机盘管系统,但对相对独立性强的房间采用分体式家用空调。在整个设计过程中注重自动控制在空调中的应用,从节能、实用、经济和美观四方综合考虑,力求暖通与建筑的完美结合,体现了庄重典雅又不失现代气息的设计理念。在此项目中使用风机盘管加新风系统具有一下优点: 1)布置灵活,可以和集中处理的新风系统联合使用,也可以单独使用 2)各空调房间互不干扰,可以独立地调节室温,并可随时根据需要开停机组,节省运行费用,灵活性大,节能效果好 3)与集中式空调相比不需回风管道,节约建筑空间 4)机组部件多为装配式、定型化、规格化程度高,便于用户选择和安装 5)只需新风空调机房,机房面积小 6)使用季节长 7)各房间之间不会互相污染 2、系统划分 考虑到此建筑处在县中心地带,面积宝贵,所以制冷机组设置在裙楼屋顶。空调机组设在大楼屋顶,为尽量减小管道尺寸和管道输送损失,系统划分为一个,整个项目为一个:水系统1至8层;功能主要为办公室,系统采用灵活性大、节能

效果好的风机盘管加新风系统,对相对独立性强的房间采用分体式家用空调。 3、主要主要设计气象参数 1)长沙地区室外设计参数 夏季:空调室外计算干球温度35.8℃空调室外计算湿球温度27.7℃ 通风室外计算温度33℃空调室外日平均温度32.7℃ 冬季:空调室外计算温度-0.8℃空调室外计算相对湿度81% 室外通风计算温度5℃室外平均主导风向NNE 2)室内设计参数 室内设计温度:冬季18℃相对湿度45%夏季26℃相对湿度60% 4、冷热负荷计算 通过用冷负荷系数法计算,得出空调夏季总冷负荷为1080kw 5、空调设备选型(表一) 该整幢办公大厦(除配电房、茶水房)的冷负荷约为1080KW,考虑机组本身和介质在泵、风机、管道中升温及泄露的损失,取1.1系数,制冷系统总制冷量取1188kW。取冷冻水进出口温度为12℃、7℃时,冷冻水流量为71.839kg/s,查开利30SHP产品说明书,选取30SHP750-模块A两台机组,其机组相关参数见表一。 表一30SHP750-模块A机组参数

基于PLC系统的中央空调控制系统毕业设计论文

哈尔滨理工大学毕业设计 题目:基于PLC的中央空调控制系统设计院、系:自动化学院自动化系 姓名: 指导教师: 系主任: 2012年06月25 日

哈尔滨理工大学毕业设计(论文)任务书 学生姓名:学号: 学院:自动化学院专业:自动化 任务起止时间:2012 年 2 月27 日至2012 年 6 月25 日 毕业设计(论文)题目: 基于PLC的中央空调控制系统设计 毕业设计工作内容: 1.第1~2周,查阅相关资料并翻译外文资料; 2.第3~4周,了解课题目前在国内外的研究现状、发展趋势,确定中央空调所要实现的功能和了解整个系统的结构框架; 3.第5~8周,进一步了解中央空调的所要实现的具体功能,确定系统中所要用到的原器件,并进行最初的硬件电路的设计,为软件编程做准备; 4.第9~11周,学习PLC程序的设计与开发,确定最终的硬件电路的设计; 5.第12~13周,编写PLC程序,并和硬件一起进行程序调试,来检查程序的可行性; 6.第14~15周,修改必要的程序部分来完善系统,并书写论文的初稿;7.第16~17周,修改并完成书面论文,准备答辩。 资料: 1.王卫兵,高俊山. 可编程控制器原理及应用.第二版.机械工业出版社,2005 2.任光.可编程序控制器(PC)应用技术与实例.华南理工大学出版社,2001 3.汤蕴缪,史乃. 电机学.机械工业出版社,1999 4.康贤永,万大福. 可编程控制器及其应用. 重庆大学出版社,1998 5.梅晓榕,柏桂珍. 自动控制元件及线路. 科学出版社,2005 6.刘金琨. 先进PID控制Matlab仿真(第二版). 电子工业出版社,2004 指导教师意见: 签名: 年月日系主任意见: 签名: 年月日 教务处制表

综合办公楼空调系统设计说明书

综合办公楼空调系统设 计说明书 空调系统 过去 50 年以来,空调得到了快速的发展,从曾经的奢侈品发展到可应用于大多 数住宅和商业建筑的比较标准的系统。在 1970 年的美国, 36% 的住宅不是全空气调节就是利用一个房间空调器冷却;到1997年,这一数字达到了 77%,在那年作的第一 次市场调查表明,在美国有超过一半的住宅安装了中央空调 (人口普查局, 1999)。在1998年,83%的新建住宅安装了中央空调 ( 人口普查局, 1999)。中央空调在商业建筑物中也得到了快速的发展,从 1970年到1995年,有空调的商业建筑物的百分比从54% 增加到 73%(杰克森和詹森,1978)。 建筑物中的空气调节通常是利用机械设备或热交换设备完成.在大多数应用中,建筑物中的空调器为维持舒适要求必须既能制冷又能除湿,空调系统也用于其他的场所,例如汽车、卡车、飞机、船和工业设备,然而,在本章中,仅说明空调在商业和住宅 建筑中的应用。 商业的建筑物从比较大的多层的办公大楼到街角的便利商店,占地面积和类型差 别很大,因此应用于这类建筑的设备类型比较多样,对于比较大型的建筑物,空调设 备设计是总系统设计的一部分,这部分包括如下项目:例如一个管道系统设计,空气 分配系统设计,和冷却塔设计等。这些系统的正确设计需要一个有资质的工程师才能 完成。居住的建筑物(即研究对象)被划分成单独的家庭或共有式公寓,应用于这些 建筑物的冷却设备通常都是标准化组装的,由空调厂家进行设计尺寸和安装。 本章节首先对蒸汽压缩制冷循环作一个概述,接着介绍制冷剂及制冷剂的选择,最后介绍冷水机组。 1.1 蒸汽压缩循环

某办公楼中央空调设计方案

某办公楼中央空调设 计方案 1 绪论 1.1 我国暖通空调的现状及其发展 进入上世纪90年代后,我国的居住环境和工业生产环境都已广泛地应用空调,空调技术已成为衡量建筑现代化水平的重要标志之一。90年代中期,由于大中城市电力供应紧,供电部门开始重视需求管理及削峰填谷,蓄冷空调技术提到了议事日程。近年来,由于能源结构的变化,促进了吸收式冷热水机组的快速发展,以及热泵技术在长江中下游地区的应用。 随着生产和科技的不断发展,人类对空调技术也进行了一系列的改进,同时也在积极研究环保、节能的空调产品和技术,已经投入使用了冰蓄冷空调系统、燃气空调、VAV空调系统、地源热泵系统等。暖通空调技术的发展,必然会受到能源、环境条件的制约,所以能源的综合利用、节能、保护环境及趋向自然的舒适环境必然是今后发展的主题。 1.2 建筑空调系统节能国外研究现状 1.2.1 建筑空调建筑空调系统节能国外研究现状 能源是整个经济系统的基本组成部份,作为一个能源消耗大国,美国在节能和提高能源利用率方面投入了大量的人力、物力。在美国的整个能源消耗中,有约1/3以上消耗在建筑能耗上,这些能耗用来满足人们的热舒适、空气品质、提高人们的生活质量。美国暖通空调制冷工程师协会、美国制冷协会、美国冷却塔协会等组织、美国能源部以及众多暖通空调设备生产厂家如York, Carrie r等都为建筑节能做出了很大贡献。特别是美国制冷设备生产厂商投入了大量的资源研究高性能冷水机组,使得冷水机组单位制冷量的能耗仅为20世纪70年代的62.3%。美国在空调冷源水系统方面的研究也卓有成效,在冷却水系统方面着重于降低冷却水流量,以达到减少冷却水泵能耗的目的。日本是一个资源贫困的国家,其主要能源来自进口,同时又是一个能源高消费国家。因此,节能和提高能源的利用率对日本来讲有着重要的意义。长期以来,在建筑节能方面,日本做了大量工作,颁布了许多节能法规,提出了建筑节能的评价方法。日本的一些设备生产厂家对

中央空调系统毕业设计

中央空调系统毕业设计 篇一:某办公楼中央空调系统毕业设计全文 第一章工程概况 1.1 建筑说明 湖北科技学院办公楼位于湖北省咸宁市,地处夏热冬冷区,总建筑面积为10012㎡,其中空调面积为5114.7㎡。建筑总高度为12米,地上三层为办公用房以及会议室,每层层高均为4米。工程设计范围为1—3层空调与采暖设计,空调系统的设计满足室内工作人员对温度,湿度和新风的要求即可,为舒适性空调。 1.2 维护结构性能参数 外墙类型(自内至外):370mm页岩烧结多孔承重砖:K370=1.191W/(m·℃)取2%的销键作用的影响,则:K370=1.191W/(m2·℃)×1.02=1.22 W/(m2·℃); 内墙类型:20 mm水泥砂浆+240mm砖墙+20mm水泥砂浆,K=1.974W/(m2.K); 屋面类型:内粉刷(20mm)+钢筋混凝土(35mm)+水泥砂浆(20mm)+隔气层(5mm)+水泥膨胀珍珠岩350(200mm)+水泥砂浆(20mm)+卷材防水(5mm)+砾砂外表层(5mm),K=0.49W/(m2.K)。 楼板材料:7mm五夹板+370mm热流向下(水平、倾斜)60mm以上+80mm钢筋混凝土+25mm水泥砂浆+25mm大理石,

K=0.508 W/(m2·K); 外窗类型:PVC框+Low-E中空玻璃6+12A+6遮阳型,传热系数2.444 W/(m2.K)自身遮阳系数0.55,内遮阳系数0.60,有外遮阳;. 外门系列:节能外门,传热系数3.02 W/(m2.K);内门系列:木框夹板门,传热系数2.504 W/(m2.K);另外卫生间门窗玻璃均采用磨砂玻璃。窗高1800mm,窗台高900mm。维护结构热工性能参数如下表: 2 表1-1 维护结构热工性能参数 第二章空调负荷计算 2.1 设计参数 2.1.1 室外设计计算参数 台站位置:北纬 30°37′东经114°08′海拔高度:23.3m 大气透明度的等级为4 2.1.2 室内设计计算参数 参考《公共建筑节能设计标准》,确定各房间的设计参数如下表: 表2-2 室内设计计算参数 注:室内空气压力稍高于室外大气压。 2.2 冷负荷的计算

暖通毕业设计开题报告

题目:永州商业广场综合楼中央空调系统设计 学院:建筑工程学院 专业:建筑环境与设备工程 学生姓名: xx 学号: 201209010114 指导老师: xxx 2016年3月30日

开题报告填写要求 1.开题报告(含“文献综述”)作为毕业设计(论文)答辩委员会对学生答辩资格审查的依据材料之一。此报告应在指导教师指导下,由学生在毕业设计(论文)工作前期内完成,经指导教师签署意见及所在专业审查后生效。 2.开题报告内容必须用黑墨水笔工整书写或按此电子文档标准格式(可从教务处网页上下载)打印,禁止打印在其它纸上后剪贴,完成后应及时交给指导教师签署意见。 3.“文献综述”应按论文的格式成文,并直接书写(或打印)在本开题报告第一栏目内,学生写文献综述的参考文献应不少于10篇(不包括辞典、手册),其中至少应包括1篇外文资料;对于重要的参考文献应附原件复印件,作为附件装订在开题报告的最后。 4.统一用A4纸,并装订单独成册,随《毕业设计(论文)说明书》等资料装入文件袋中。

毕业设计(论文)开题报告 文献综述 一、引言 随着我国人民生活水平的不断提高,购买力增强。近年来修建了不少商业建筑,并且向多元化方向发展,建筑规模越来越大。装饰豪华、营销全面、多维服务,集商贸、娱乐、居住、办公为一体的高级商城也层出不穷。 商业建筑是一个流动人口众多的公共场所,室内空气的温湿度、洁净度和新鲜空气量等,对顾客和商场职工的身体健康影响很大。因此,商业建筑的空气环境越来越被商业部门所重视。我国卫生防疫部门对商业建筑提出了卫生要求,对较大的重点商场还进行过监测,对一些已建的大中商场要求进行改造,增设通风设施或加建空气调节装置。新建的大中商业建筑纷纷安装了空调系统,以提高商场的档次,吸引更多的顾客。各大城市中频频展开的“商战”更加速了空调系统在商业建筑中的普及。 商业建筑不断的增多,以及人们对室内空气的温湿度、洁净度和空气品质问题越来越重视,加上能源的紧缺,节能问题越来越引起人们的重视。因此迫切需要为商业建筑物安装配置节能、健康、舒适的中央空调系统来满足人们对高生活水平的追求。目前,随着我国经济的快速增长,生活条件日益改善,人们对生活环境的舒适性的要求越来越高,对中央空调的需求越来越大,对中央空调节能、舒适、健康更加关注。 国际标准规定,商用空调是3HP以上空调机组的统称,因此商用空调种类颇多。包括风冷热泵型中央空调机组,水冷螺杆式冷水机组、离心式冷水机组等等。 因此,设计一项节能、舒适、健康的中央空调工程是很有实际意义的。 二、研究现状 中央空调在世界上已有百年的发展历史,在中国也有20多年的应用时间,然而真正引起国内企业关注还是近几年。目前国内市场中央空调领域竞争已经进入白热化阶段,随着价格战连绵不断,在家用空调领域几乎已经无利可图的企业纷纷开始在中央空调领域寻找新的发展空间和利润增长点。 2003年中央空调市场容量将达到85亿元,2005年达到200亿元以上。市场空间迅

合肥市综合办公楼空调系统设计说明书定稿版

合肥市综合办公楼空调系统设计说明书 HUA system office room 【HUA16H-TTMS2A-HUAS8Q8-HUAH1688】

青岛农业大学 毕业论文(设计)题目:合肥市某综合办公楼空调系统设计 姓名:季广学 学院:建筑工程学院 专业:建筑环境与设备工程 班级: 2010级2班 学号: 20103012 指导教师:梁泽德 2014年 6月3 日

毕业论文(设计)诚信声明 本人声明:所呈交的毕业论文(设计)是在导师指导下进行的研究工作及取得的研究成果,论文中引用他人的文献、数据、图表、资料均已作明确标注,论文中的结论和成果为本人独立完成,真实可靠,不包含他人成果及已获得青岛农业大学或其他教育机构的学位或证书使用过的材料。与我一同工作的同志对本研究所做的任何贡献均已在论文中作了明确的说明并表示了谢意。 论文(设计)作者签名:季广学日期: 2014 年 6月 3 日 毕业论文(设计)版权使用授权书 本毕业论文(设计)作者同意学校保留并向国家有关部门或机构送交论文(设计)的复印件和电子版,允许论文(设计)被查阅和借阅。本人授权青岛农业大学可以将本毕业论文(设计)全部或部分内容编入有关数据库进行检索,可以采用影印、缩印或扫描等复制手段保存和汇编本毕业论文(设计)。本人离校后发表或使用该毕业论文(设计)或与该论文(设计)直接相关的学术论文或成果时,单位署名为青岛农业大学。 论文(设计)作者签名:季广学日期: 2014 年 6月 3 日指导教师签名:日期:年月日

合肥市某综合办公楼空调系统设计 建筑环境与设备工程专业季广学 指导老师梁泽德 摘要:本设计为合肥市保一集团公司科研信息中心综合办公楼中央空调系统,通过对建筑内部的空气温度,湿度和洁净度的控制,从而营造人体感觉舒适的室内工作环境。建筑性质:民用建筑工程设计等级,二级。地上,9层办公楼、地下,一层。占地面积为892.5㎡,总建筑面积为8326㎡(不包括地下室),地下室为262.5㎡,总高度为34.3㎡。由于所在地冬季无集中供暖,故采取热泵空调系统,夏季供冷,冬季供热。 设计的内容包括:1~2层是大厅、产品展示区、外贸部,都是大空间;3~9层是大空间的活动厅和会议室以及面积相对较小的办公室和休息室。所以,1~2层可采用全空气空调系统,过渡季节可采用全新风系统;3~9层可采用全空气与风机盘管加新风的混合系统。楼梯间做加压送风,厕所设置机械排风。其中风机盘管处理室内回风,承担室内围护结构和人体照明等冷负荷,新风机处理室外新风,新风处理到室内空气焓值,不承担室内负荷,而风机盘管承担全部室内冷湿负荷,盘管在湿负荷下工作。新风负荷由新风机组承担,进入风机盘管的供水温度可适当提高,水管的结露现象可得到改善。 1.空调系统的划分与系统方案的确定,冷源的选择。 2.室内热湿负荷的计算,利用焓湿图进行冬、夏季工况分析。3.室内送风方式与气流组织形式的选定。4.完成风、水管道的布置及水力计算。6.进行空气处理设备的选择计算,并确定出各种设备的规格、型号和数量。7.空调机房设计。 8.风管系统与水管系统保温层的设计;消声防振设计等。

中央空调毕业设计论文

毕业设计(论文) 题目名称:惠新大厦中央空调系统设计 学院名称:能源与环境学院 班级:建环 学号: 学生: 指导教师: 年月日

论文编号: 惠新大厦中央空调系统设计 专业:建筑环境与设备工程:教导老师: 摘要 本设计为惠新大厦中央空调设计。通过方案比较,在负荷计算的基础上,采用了风机盘管加新风和全空气两种空调系统形式。一层除了有单独办公室,还有一个长17.8m,宽15.6的办公大厅,不适合用风机盘管加新风系统,选用全空气系统。二层到十层楼层,大部分为单独办公室,所以全部选用风机盘管加新风系统。风机盘管为卧式暗装,新风不承担室负荷;全空气系统为一次回风系统,室送风采用散流器下送方式。新风从墙洞引入,再由各层的新风机组集中处理供应。冷冻水由地下室的冷冻机房供应,采用了闭式同程两管制水系统。水管用泡沫橡塑保温,风管采用离心玻璃棉。设计工程中考虑了消声、减振措施。 关键词:中央空调,风机盘管加新风系统,全空气系统,大厦

Central Air-conditioning Design for HuiXin Building Abstract The air conditioning engineering of Huixin Building was designed. On the base of cooling load, heating and moisture load calculation, primary air fan-coil system and all air system are adopted by way of technical and economic analysis. In addition to individual office level, there is a length 17.8m, width of 15.6 in the office lobby, not suitable for fan coil plus fresh air system, use an all air system. The second floor to ten floors, most as a separate office, so all the fan coil selection of a new air system.The fresh air doesn’t undertake indoor load and delivers air through double deflection grille after mixing the return air in the horizontal recessed fan coil. The return air is harnessed one time by the air handling unit in the all air system and the handled air is delivered through double deflection grille by sidewall air supply. The fresh air is supplied by hole or shaft and handled by the fresh air handling unit. The chilled water which is a closed two-pipe direct return water system is supplied by the refrigerating plant room. The thermal insulation material of water pipe and air duct are foam plastics and centrifugal glass wool respectively. Measures of noise elimination, damp, fire prevention and smoke extraction is considered during the design. Key Words: air conditioning primary air fan-coil system all air system building.