浅谈10kV配网自动化配电系统设计摘要:配网自动化就是利用通讯技术、现代电子技术以及计算机网络技术,完成配电系统的正常运行,在事故情况下,也能够实现及时保护、监测、控制和配电管理。一般情况下,110 kv及以下电力网络属于配电网络,380/220 v属于低压配电网,1 kv及以上属于中压配电网,35 kv及以上属于高压配电网。

关键字:10kv配网自动化配电系统设计

abstract: the power distribution automation is the use of modern communication technology, electronic technology and computer network technology, power system normal operation, in the case of accident, also can realize timely protection, monitoring, control and distribution management. in general, 110 and below kv power network of distribution network, 380/220 v belonging to the low-voltage distribution network, 1 kv and above belongs to medium voltage distribution network, 35 kv and above belongs to the high voltage distribution network.

key words: 10kv network; automation; power distribution system design

中图分类号:f407.67文献标识码:a 文章编号:

0引言

目前,配电网已从传统的架空线路为主的局面向电缆线路发展。

10kV及以下变电所场所设计规范

10kV及以下变电所设计规范 GB50053-94 第二节对建筑的要求 第6.2.1条高压配电室宜设不能开启的自然采光窗〃窗台距室外地坪不宜低于1.8m;低压配电室可设能开启的自然采光窗。配电室临街的一面不宜开窗。 第6.2.2条变压器室、配电室、电容器室的门应向外开启。相邻配电室之间有门时〃此门应能双向开启。 第6.2.3条配电所各房间经常开启的门、窗〃不宜直通相邻的酸、碱、蒸汽、粉尘和噪声严重的场所。 第6.2.4条变压器室、配电室、电容器室等应设置防止雨、雪和蛇、鼠类小动物从采光窗、通风窗、门、电缆沟等进入室内的设施。 第6.2.5条配电室、电容器室和各辅助房间的内墙表面应抹灰刷白。地(楼)面宜采用高标号水泥抹面压光。配电室、变压器室、电容器室的顶棚以及变压器室的内墙面应刷白。 第6.2.6条长度大于7m的配电室应设两个出口〃并宜布置在配电室的两端。长度大于60m时〃宜增加一个出口。当变电所采用双层布

置时〃位于楼上的配电室应至少设一个通向室外的平台或通道的出口。 第6.2.7条配电所〃变电所的电缆夹层、电缆沟和电缆室〃应采取防水、排水措施。 4.10 对有关专业的要求 4.10.1 可燃油油浸电力变压器室的耐火等级应为一级。非燃(或难燃)介质的电力变压器室、高压配电装置室和高压电容器室的耐火等级不应低于二级。低压配电装置和低压电容器室的耐火等级不应低于三级。 4.10.2 有下列情况之一时〃变压器室的门应为防火门: (1)变压器室位于高层主体建筑物内。 (2)变压器室附近堆有易燃物品或通向汽车库。 (3)变压器位于建筑物的二层或更高层。 (4)变压器位于地下室或下面有地下室。 (5)变压器室通向配电装置室的门。 (6)变压器室之间的门。 4.10.3 变压器室的通风窗〃应采用非燃烧材料。 4.10.4 配电装置室及变压器室门的宽度宜按最大不可拆卸部件宽度加0.30m〃高度宜按不可拆卸部件最大高度加0.30m。

工厂供配电系统设计设计

湖南理工职业技术学院 工厂供配电技术课程设计题目:某工厂供配电系统的电气设计 年级专业:风能工程系机电1132班 学生姓名:龙博 指导老师:卢永辉 2015年06月15日

摘要 工厂供电,是指工厂所需的电能的供应与分配,也称工厂配电。 众所周知,电能是现代工业生产的主要能源和动力。电能既能易于由其他形式的能量转换而来,而易于转换为其他形式的能量以供应用。电能的输送和分配既简单经济,又便于控制、调节和测量,有利于实现生产过程自动化,而且现代社会的信息技术和其他高新技术无疑不是建立在电能应用的基础之上的。因此电能在现代工业生产及整个国民经济生活中应用极为广泛。 本论文设计首先计算电力负荷和变压器的台数、容量;利用所学的知识确定变电所的位置。计算出短路电流的大小,选出不同型号的变压器,进而确定变压器的连接组别,画出必要的变电所主接线图。 关键词:主接线图、短路电流、电力负荷、变压器 目录 第1章前言 (4) 第2章设计任务 (5) 2.1 原始资料 (5) 2.2 工厂平面图 (5) 2.3 工厂供电电源 (5)

2.4 工厂负荷情况 (6) 2.5 设计要求 (7) 第3章全厂负荷计算和无功功率补偿 (8) 3.1 负荷计算 (8) 3.2 无功功率补偿 (11) 第4章变电所高压电器设备选型 (12) 4.1 主变压器的选择 (12) 4.2 各个车间变压器的选择 (12) 4.3 10KV架空线的选择 (13) 第5章短路电流的计算 (14) 5.1 短路的基本概念 (14) 5.2 短路的原 (14) 5.3 短路的后果 (14) 5.4 短路的形成 (15) 5.5 三相短路电流计算的目的 (15)

10kv工厂供配电系统设计

《电气工程CAD大作业》报告 系别:机电与自动化学院 专业班级:电气自动化技术0901 学生姓名:鲁学 _____________ 指导教师:陈强 (课程设计时间:2011年6月20 0——2011年6月 25 0) 华中科技大学武昌分校

1.设计的目的 (1) 2.设计任务 (1) 3.设计任务要求 (2) 负荷计算及无功补偿 (2) 3. 1. 1各部分的负荷计算 (2) 3. 1.2无功功率补偿 (5) 变压器的选择 (5) 导线与电缆的选择 (6) 电气设备的选择 (10) 4设计心得体会 (13) 参考文献 (14)

1.设计目的 ?帮助我们熟悉小型工厂的配电系统的构架及建模方案。 ?训练同学们对配电系统最基本的参数讣算,并根据计算参数选择正确的的器件来完成配电的需要系统。 ?利用CAD绘图软件画出10kv工厂供配电系统设计,使我们更加熟悉CAD的绘图,实现现10kV及以下低压供配电的CAD系统一体化设计,使其功能更趋完善,真正满足设计人员的需要,这项工作是很有实际意义的。 2.设计任务 机械厂的地理位置及负荷分布图 ⑷电WTM 7 生话X的 ft荷中 心 xx机械厂总平面图 比例1: 2000备 用 电 即 I公八电裁m

机械厂的负荷统计表 丿房编厂房名称负荷类型设备容量(kw)需要系数功率因数 号kx cose 1铸造车间2300 2锻压车3350 间 3热处理车3150 间 4电镀车间3250 5仓库320 6工具车间3360 7金工车间3400 8锅炉房250 9装配车间3180 10机修车间3160 11生活区3350 3.设计任务要求 负荷计算及无功补偿 3. 1. 1各部分的负荷计算 要进行低压供配电系统的设计,负荷的统讣计算是其中的一项重要内容,负荷讣算结果对选择供配电设备及安全经济运行均起决定性的作用。 负荷计算的目的是: ①算变配电所内变爪器的负荷电流及视在功率,作为选择变爪器容量的 据。 ②汁算流过各主要电气设备(断路器、隔离开关、母线、熔断器等)的负荷电 流,作为选择这些设备的依据。

10KV变电所设计

第1章绪论 1.1 设计目的 通过课程设计巩固本课程理论知识,掌握供配电设计的基本方法,通过解决各种实际问题,培养独立分析和解决实际工程技术问题的能力,同时对电力工业的有关政策、方针、技术规程有一定的了解,在计算、绘图、设计说明书等方面得到训练,为今后的工作奠定基础。 1.2设计任务 根据富威机械厂用电负荷,并适当考虑生产的发展,按安全可靠、技术先进、经济和的要求,确定工厂变电所的位置与型式;通过计算负荷,确定主变压器台数及容量;进行短路电流的计算,选择变电所的主线及高、低电气设备;选择整定继电保护装置;最后按要求写出设计计算说明书,绘出设计图纸。 1.3设计要求 1、要求每个学生独立完成设计任务。 2、要正确运用设计资料。 3、给出变配电所的主接线图。 4、完成课程设计任务书规定容。 5、要求提交成果。 (1)完成课程设计报告书一份; (2)A3变配电所的主接线图纸一。

第2章负荷计算及无功功率补偿2.1负荷计算 根据设计要求进行分析,机械厂负荷统计资料见下表2-1: 表2-1机械厂负荷统计 单组用电设备的负荷计算:

有功功率 n d c P K P ?= kw 无功功率 θarccos tan ?=c c P Q var k 视在功率 22c c c Q P S += KVA 计算电流 r c c U S I 3= A 通过以上公式对工厂各部分进行计算,得到计算结果如下: 1、仓库: 动力部分: 228825.0=?=c P kw 7.2565.0arccos tan 22=?=c Q var k KVA S c 8.337.252222=+= 2.5138 .33== r c U I A 照明部分: 6.1=c P kw 2、铸造车间; 动力部分: 3.8323835.0=?=c P kw var 857.0arccos tan 3.83k Q c =?= KVA S c 119853.8322=+= A U I r c 3.1803119 == 照明部分: kw P c 8= 3、锻压车间; 动力部分: kw P c 5.5923825.0=?= var 6.6965.0arccos tan 5.59k Q c =?=

10KV工厂供配电系统设计

题目10kv工厂变电站设计 目录 1. 设计任务 (3) 1.1设计题目 (3) 1.2设计目的 (3) 1.3设计任务与要求 (3) 2.设计内容...............................................4-10 2.1.负荷计算和无功功率补偿.............................4-7 2.1.1.负荷计算.......................................4-6 2.1.2.无功功率的补偿 (7) 2.2.变压器的选择.......................................7-8 2.2.1.变压器台数的选择 (7) 2.2.2.变压器容量的选择 (8) 2.2.3.变压器类型的选择 (8) 2.3.导线与电缆的选择 (9) 2.3.1高压进线和引入电缆的选择 (9) 2.3.2 380v低压出线的选择 (9) 2.4.电气设备的选择 (10) 2.4.1. 模块功能 (10) 2.4.2. 模块需要提供的参数 (10) 2.4.3. 继电保护及二次结线设计 (10) 3.防雷与接地装置的设置.....................................10-11 3.1.直接防雷保护.. (11) 3.2.雷电侵入波的防护 (11)

3.3接地装置的设计...........................................11 4. 参考文献.. (13) 1.设计任务 1.1设计题目:10KV 工厂供配电系统设计 1.2设计目的 通过本课程设计:熟悉供配电系统初步设计必须遵循的原则、基本内容、设计程序、设计规范等,锻炼工程设计、工程计算、工具书使用等能力,并了解供电配电系统前沿技术及先进设备。让我们了解设计工厂配电的一般流程,对工厂的布局有个大致的概念,对电力系统的接线方式有一定的了解。 1.3设计任务与要求 机械厂的地理位置及负荷分布如下图: 机械厂负荷统计表 厂房编号 厂房名称 负荷类型 设备容量(KW ) 需要系数Kx 功率因数cos ψ 1 铸造车间 2 300 0.3 0.7 2 锻压车间 3 350 0.3 0.65 3 热处理车间 3 150 0.6 0.8 生活区 电镀车间 铸造车间 仓库 锻压车间 工具车间 热处理车间 金工车间 厂区 锅炉房 装配车间 机修车间 北-------------- 南

10KV变电所配电系统设计

10KV变电所及其配电系统的设计 摘要:变电所是电力系统的一个重要组成部分,由电器设备及配电网络按一定的接线方式所构成,他从电力系统取得电能,通过其变换、分配、输送与保护等功能,然后将电能安全、可靠、经济的输送到每一个用电设备的转设场所。变电所涉及方面很多,需要考虑的问题多,分析变电所担负的任务及用户负荷等情况,选择所址,利用用户数据进行负荷计算,确定用户无功功率补偿装置。同时进行各种变压器的选择,从而确定变电站的接线方式,再进行短路电流计算,选择送配电网络及导线,进行短路电流计算。选择变电所高低压电气设备,为变电所平面及剖面图提供依据。本变电所的初步设计包括了:(1)总体方案的确定(2)负荷分析(3)短路电流的计算(4)配电系统设计与系统接线方案选择(5)继电保护的选择与整定(6)防雷与接地保护等内容。 关键词:变电所;负荷;输电系统;配电系统

第1章绪论 1.1工厂变配电所的设计 1.1.1用户供电系统 电力用户供电系统由外部电源进线、用户变配电所、高低压配电线路和用电设备组成。按供电容量的不同,电力用户可分为大型(10000kV·A以上)、中型(1000-10000kV·A)、小型(1000kV·A及以下) 1.大型电力用户供电系统 大型电力用户的用户供电系统,采用的外部电源进线供电电压等级为35kV 及以上,一般需要经用户总降压变电所和车间变电所两级变压。总降压变电所将进线电压降为6-10kV的内部高压配电电压,然后经高压配电线路引至各个车间变电所,车间变电所再将电压变为220/380V的低电压供用电设备使用。 某些厂区环境和设备条件许可的大型电力用户也有采用所谓“高压深入负荷中心”的供电方式,即35kV的进线电压直接一次降为220/380V的低压配电电压。 2.中型电力用户一般采用10kV的外部电源进线供电电压,经高压配电所和10kV用户内部高压配电线路馈电给各车间变电所,车间变电所再将电压变换成220/380V的低电压供用电设备使用。高压配电所通常与某个车间变电所合建。 3.小型电力用户供电系统 一般小型电力用户也用10kV外部电源进线电压,通常只设有一个相当于车间变电所的降压变电所,容量特别小的小型电力用户可不设变电所,采用低压220/380V直接进线。 1.1.2工厂变配电所的设计原则 1.必须遵守国家的有关规程和标准,执行国家的有关方针政策,包括节约能源、节 约有色金属等技术经济政策。 2.应做到保障人身和设备安全、供电可靠、电能质量合格、技术先进和经济合理,应采用效率高、能耗低、性能较先进的电气产品。 3.应根据工程特点、规模和发展规划,正确处理近期建设与远期发展的关系,做到远、近期结合,以近期为主,适当考虑扩建的可能性。 4.必须从全局出发,统筹兼顾,按照负荷性质、用电容量、工程特点和地区

10kv工厂供配电系统设计

《电气工程CAD大作业》 报告 系别:机电与自动化学院 专业班级:电气自动化技术0901 学生姓名:鲁学 指导教师:陈强 (课程设计时间:2011年6月20日——2011年6月25日) 华中科技大学武昌分校

目录 1.设计的目的 (1) 2.设计任务 (1) 3.设计任务要求 (2) 3.1负荷计算及无功补偿 (2) 3.1.1各部分的负荷计算 (2) 3.1.2无功功率补偿 (5) 3.2变压器的选择 (5) 3.3导线与电缆的选择 (6) 3.4电气设备的选择 (10) 4设计心得体会 (13) 参考文献 (14)

1.设计目的 ·帮助我们熟悉小型工厂的配电系统的构架及建模方案。 ·训练同学们对配电系统最基本的参数计算,并根据计算参数选择正确的的器件来完成配电的需要系统。 ·利用CAD绘图软件画出10kv工厂供配电系统设计,使我们更加熟悉CAD 的绘图,实现现10kV及以下低压供配电的CAD系统一体化设计,使其功能更趋完善,真正满足设计人员的需要,这项工作是很有实际意义的。 2.设计任务 机械厂的地理位置及负荷分布图

机械厂的负荷统计表 厂房编号厂房名称负荷类型设备容量(kw)需要系数kx 功率因数cosφ 1 铸造车间 2 300 0. 3 0.7 2 锻压车间 3 350 0.3 0.65 3 热处理车间 3 150 0.6 0.8 4 电镀车间 3 250 0. 5 0.68 5 仓库 3 20 0.4 0.8 6 工具车间 3 360 0.3 0.6 7 金工车间 3 400 0.2 0.65 8 锅炉房 2 50 0.7 0.8 9 装配车间 3 180 0.3 0.7 10 机修车间 3 160 0.2 0.65 11 生活区 3 350 0.7 0.9 3.设计任务要求 3.1负荷计算及无功补偿 3.1.1各部分的负荷计算 要进行低压供配电系统的设计,负荷的统计计算是其中的一项重要 内容,负荷计算结果对选择供配电设备及安全经济运行均起决定性的作 用。 负荷计算的目的是: ○1算变配电所内变压器的负荷电流及视在功率,作为选择变压器容量的 依 据。 ○2计算流过各主要电气设备(断路器、隔离开关、母线、熔断器等)的负 荷电 流,作为选择这些设备的依据。

某学校10kv变电所及配电系统设计

目录1课程设计原始数据 (3) 1.1设计题目 (3) 1.2设计要求 (3) 1.3设计依据 (3) 1.4设计任务 (4) 2负荷计算及功率补偿 (4) 2.1负荷计算的方法 (4) 2.2无功功率补偿 (6) 3变电所位置和型式的选择 (6) 3.1根据变配电所位置选择一般原则: (6) 3.2变电所的型式与方案: (7) 4变电所变压器和主接线方案的选择 (7) 4.1主变压器的选择 (7) 4.2装设一台主变压器的主接线方案 (7) 5 短路电流的计算 (7) 5.1绘制计算电路 (7) 5.2确定短路计算基准值 (7) 5.3计算短路电路中个元件的电抗标幺值 (8) 5.4 K-1点(10.5K V侧)的相关计算 (8) 5.5 K-2点(0.4K V侧)的相关计算 (8) 6变电所一次设备的选择校验 (8) 6.1选择校验条件 (8) 6.210KV侧一次设备的选择校验 (9) 6.30.4KV侧一次设备的选择校验 (10) 7变压所进出线与邻近单位联络线的选择 (10) 7.110KV高压出线的选择: (10) 7.2变电所及邻近单位焦点路线的选择 (11) 7.30.4KV低压出线选择 (11) 7.4按发热条件选择 (12) 7.5校验电压损耗 (12) 7.6短路热稳定校验 (12) 设计总结 (12) 致谢 (13) 参考文献 (13) 附图 (13) ***学校课程设计 某学校10kv变电所及配电系统设计

系部:机械工程系 班级:机电10-12(1)班 学生姓名: *** 学号: *** 指导教师:何颖 完成日期: 2012年6月15日 新疆工业高等专科学校 课程设计评定意见 设计题目:某学校10kv变电所及配电系统设计 学生姓名:*** 专业机电一体化班级机电10-12(1)班 评定意见: 评定成绩: 指导教师(签名):年月日评定意见参考提纲: 1.学生完成的工作量与内容是否符合任务书的要求。 2.学生的勤勉态度。 3.设计或说明书的优缺点,包括:学生对理论知识的掌握程度、实践工作能力、表现出的创造性和综合应用能力等。 新疆工业高等专科学校 课程设计任务书

某纺织厂供配电系统设计

CENTRAL SOUTH UNIVERSITY 设计题目:某纺织厂供配电系统设计 学号:0909113221 姓名:丁亮 班级:自动化1106班 指导老师:桂武鸣 第 1 页共43 页

目录 第一章原始资料 (3) 第二章接入系统设计 (4) 第三章车间供电系统设计 (16) 第四章工厂总降压变的选择 (26) 第五章所用变的选择 (27) 第六章主接线设计 (28) 第七章短路电流计算 (30) 第八章电气设备选择 (35) 第九章继电保护装置 (41) 结束语 (42) 参考文献 (43)

题目2某纺织厂供配电系统设计 一.原始资料 1.工厂负荷数据:工厂多数车间为2班制,年最大负荷利用小时数4600小时。工厂负荷统计资料见表1。设计需要考虑工厂5年发展规划负荷(工厂负荷年增长率按2%)。 2.供电电源请况:按与供电局协议,本厂可由16公里处的城北变电所(110/38.5/11kV),90MV A变压器供电,供电电压可任选。另外,与本厂相距5公里处的其他工厂可以引入10kV电缆做备用电源,但容量只能满足本厂负荷的20%(重要负荷),平时不准投入,只在本厂主要电源故障或检修时投入。 3.电源的短路容量(城北变电所):35kV母线的出线断路器断流容量为400MV A;10kV母线的出线断路器断流容量为350MV A。 4.电费制度:按两部制电费计算。变压安装容量每1kV A为18元/月,电费为0.5元/ kW·h。 5.气象资料:本厂地区最高温度为38度,最热月平均最高气温为30度。 6.地质水文资料:本厂地区海拔60m,底层以砂粘土为主,地下水位为2 m。二.设计内容 1.总降压变电站设计 (1)负荷计算 (2)主结线设计:根据设计任务书,分析原始资料与数据,列出技术上可能实现的多个方案,根据改方案初选主变压器及高压开关等设备,经过概略分析比较,留下2~3个较优方案,对较优方案进行详细计算和分析比较,(经济计算分析时,设备价格、使用综合投资指标),确定最优方案。 (3)短路电流计算:根据电气设备选择和继电保护的需要,确定短路计算点,计算三相短路电流,计算结果列出汇总表。

工厂10kv总变电所及配电系统设计

工厂10kv总变电所及配电系统设计 摘要 工厂供电系统就是将电力系统的电能降压再分配电能到各个厂房或车间中去,它由工厂降压变电所,高压配电线路,车间变电所,低压配电线路及用电设备组成。工厂总降压变电所及配电系统设计,是根据各个车间的负荷数量和性质,生产工艺对负荷的要求,以及负荷布局,结合国家供电情况.解决对各部门的安全可靠,经济技术的分配电能问题。其基本内容有以下几方面:进线电压的选择, 变配电所位置的电气设计, 短路电流的计算及继电保护, 电气设备的选择,车间变电所位置和变压器数量、容量的选择,防雷接地装置设计等。 本设计在对化工厂进行供配电调研、论证的基础上,完成了化工厂的负荷计算,无功功率补偿,变配电所位置和型式选择,10KV变配电所主接线设计;还进行了短路电流计算、电气设备的选择与校验。最后对化工厂的变压器进行了保护和供电系统的防雷。 关键词:变电所,负荷,短路电流,电力设备

CHEMICAL TOTAL SUBSTATION AND DISTIBUTION SYSTEM DESIGN ABSTRACT Factory power supply system is the redistribution of power system power step-down power to each plant or shop floor to it by the factory step-down transformer substation, high voltage distribution lines, plant and substation, low voltage distribution lines and electrical equipment composition. The total plant step-down substation and distribution system design is based on the load of each number and nature of the workshop, the production process on the load requirements, and load distribution, combined with the national electricity supply. Address the various departments of the safe, reliable, economic and technological The distribution of electric energy issues. The basic contents of the following areas: incoming line voltage selection, the location of the electrical substation design, calculation and short circuit current protection, electrical equipment selection, the number of plant and transformer substation location and capacity choices lightning protection grounding design. The design of power distribution in the chemical plant for research, demonstration, based on the completion of the chemical load calculation, reactive power compensation, power distribution by location and type selection, 10KV substation main wiring design; also conducted short-circuit current calculation, electrical equipment selection and validation. Finally, chemical plants and power transformer protection lightning protection system. KEY WORDS: substation ,load ,short-circuit current,power equipment

塑料制品厂总配变电所及高压配电系统设计

供配电课程设计 实践名称:塑料制品厂总配变电所及高压配电系统设计专业班级: 11自动化B班 姓名:卢伟健 学号: 2011100102050 指导教师:许先锋 实践时间: 2014年12月22——24日 实践单位:机电工程学院 教学单位:机电工程学院

前言 电能是现代工业生产的主要能源和动力。电能既易于由其它形式的能量转换而来,又易于转换为其它形式的能量以供应用;电能的输送的分配既简单经济,又便于控制、调节和测量,有利于实现生产过程自动化。因此,电能在现代工业生产及整个国民经济生活中应用极为广泛。 在工厂里,电能虽然是工业生产的主要能源和动力,但是它在产品成本中所占的比重一般很小(除电化工业外)。电能在工业生产中的重要性,并不在于它在产品成本中或投资总额中所占的比重多少,而在于工业生产实现电气化以后可以大大增加产量,提高产品质量,提高劳动生产率,降低生产成本,减轻工人的劳动强度,改善工人的劳动条件,有利于实现生产过程自动化。从另一方面来说,如果工厂的电能供应突然中断,则对工业生产可能造成严重的后果。 因此,做好工厂供电工作对于发展工业生产,实现工业现代化,具有十分重要的意义。由于能源节约是工厂供电工作的一个重要方面,而能源节约对于国家经济建设具有十分重要的战略意义,因此做好工厂供电工作,对于节约能源、支援国家经济建设,也具有重大的作用。 工厂供电工作要很好地为工业生产服务,切实保证工厂生产和生活用电的需要,并做好节能工作,就必须达到以下基本要求: 1. 安全在电能的供应、分配和使用中,不应发生人身事故和设备事故。 2. 可靠应满足电能用户对供电可靠性的要求。 3. 优质应满足电能用户对电压和频率等质量的要求. 4. 经济供电系统的投资要少,运行费用要低,并尽可能地节约电能和减少有色金属的消耗量。 一、赋值参数的设计任务书 根据实际需要,塑料制品厂欲新建一所变配电所,请结合实际情况进行设计。 图1 配电系统图

10KV工厂供配电系统设计

题目10kv工厂供配电系统设计 目录 1. 设计任务 (3) 1.1设计题目 (3) 1.2设计目的 (3) 1.3设计任务与要求 (3) 2.设计内容...............................................4-10 2.1.负荷计算和无功功率补偿.............................4-7 2.1.1.负荷计算.......................................4-6 2.1.2.无功功率的补偿 (7) 2.2.变压器的选择.......................................7-8 2.2.1.变压器台数的选择 (7) 2.2.2.变压器容量的选择 (8) 2.2.3.变压器类型的选择 (8) 2.3.导线与电缆的选择 (9) 2.3.1高压进线和引入电缆的选择 (9) 2.3.2 380v低压出线的选择 (9) 2.4.电气设备的选择 (10) 2.4.1. 模块功能 (10) 2.4.2. 模块需要提供的参数 (10) 2.4.3. 继电保护及二次结线设计 (10) 3.防雷与接地装置的设置.....................................10-11 3.1.直接防雷保护.. (11) 3.2.雷电侵入波的防护 (11)

3.3接地装置的设计...........................................11 4. 参考文献.. (13) 1.设计任务 1.1设计题目:10KV 工厂供配电系统设计 1.2设计目的 通过本课程设计:熟悉供配电系统初步设计必须遵循的原则、基本内容、设计程序、设计规范等,锻炼工程设计、工程计算、工具书使用等能力,并了解供电配电系统前沿技术及先进设备。让我们了解设计工厂配电的一般流程,对工厂的布局有个大致的概念,对电力系统的接线方式有一定的了解。 1.3设计任务与要求 机械厂的地理位置及负荷分布如下图: 机械厂负荷统计表 厂房编号 厂房名称 负荷类型 设备容量(KW ) 需要系数Kx 功率因数cos ψ 1 铸造车间 2 300 0.3 0.7 2 锻压车间 3 350 0.3 0.65 3 热处理车间 3 150 0.6 0.8 生活区 电镀车间 铸造车间 仓库 锻压车间 工具车间 热处理车间 金工车间 厂区 锅炉房 装配车间 机修车间 北-------------- 南

10KV配电线路规划与设计

10KV 配电线路规划与设计 摘要:10KV 配电线路主要包括10KV 架空线路和 10KV 电缆线路。本文主要以浙江省宁波奉化市某新建小区 条10KV 架空线路为例来简要分析10KV 配电线路的规划与设计。 关键词:10KV 配电线路;架空线路;小区供电 1.10kv 配电线路规划与设计的一般流程在实际设计过程中, 影响10kv 配电线路规划与设计因 素有很多,因此要想完美地进行配电线路设计就必须按照相关规定一步一步的进行。首先,在接受任务之后,要把很多失误都要明确清楚,如线路起点、终点和导面截面;其次,要清楚地掌握沿途地形,在地形图上对路径方案进行初步选定,并对现场进行勘测计算,并将路径图绘制出来;再次,杆塔的型式选择要根据实际情况来进行;第四,根据设计将所需的设备材料清单一一列出来,对此设计进行工程预算编制时,主要套用现行的定额、计费程序来进行;第五,从技术经济角度来对比各个方案,进而选择出最佳的方案。对这个最佳方案进行整理完善,为规划与设计提供完善的资料。 2. 10KV 架空线路设计实例本文主要以浙江省宁波奉化市一居 民小区供电设计为 例。小区配电所供电方案的接线方式如图1 所示。这种接线方式为单电源供电方式,在中等规模且无高层住宅的封闭式居民小区常用。居民小区配电室所采用的电缆单电源主要是以10kV 交联聚乙烯阻燃电缆为主。直埋是电缆铺设的主要方式。小区内一般会设一个或者几个配电室,继电保护主要采用SF6 或真空断路器来进行配置, 采用过电流和电流速断进行保护,除此之外,针对大容量配变而言,还需要在此保护基础上另装瓦斯保护和纵联差动保护。

配变低压侧分散补偿是武功补偿所采用的主要形式,按 照配变容量的40% 左右过来确定补偿容量。当在地下设置配电室时,主要采用环氧树脂绝缘的干式变压器来进行配变。 每座配电室可容纳200 户以内的供电户数,根据配变容量及住宅流分布情况,配电室低压出现路数可设置4~8 回路不等。 楼头箱在每栋楼之前设置,将单元配电箱设置在每个单元,配电室、楼头箱、单元配电箱所采用的供电方式都一样,都采用直埋低压电缆放射式进行供电。 供电可靠性。对于电网技术原则规定中所要求的“ N-1 ” 准则,10kV 线路及配电变压器仍无法满足。如果有一个设备发生问题,那么整个小区的供电就会产生问题,致使小区 居民无法正常用电。 无功补偿。据电网技术原则规定,电网无功应分层分区 就地平衡。在配变的低压侧集中装设无功补偿装置,补偿容量按配变容量的40%确定,且具有按功率因数控制的自动投切功能,但不允许向电网倒送无功功率。 线损。本供电方案具有较长的高压线路,较短的低压线 路,并且还有无功补偿装置装设,因此,虽然具有较长的整体供电半径,但在一定程度上减少了损耗。 占地及投资。配电室是该方案专门要建立的,配电室的 建立需要占用一定的土地资源。另外,高低压开关柜等设备增加时要想使投资大大增加,必须采用高供高计的参考计量方式。为了使占地面积更少以及投资更少,可由箱变代替该方案配电室,在一个箱体内装有箱变的各种高低压开关设备及配变本身,这样会使空间大大节省,但是箱变容量要适当,不宜过大,可以采取小容量多布点的措施,使供电的灵活性大大增加。此外,还可以使电源进一步靠近负荷中心,从而使供电质量大大提高。

低压工厂配电系统课程设计

工厂供电技术课程设计说明书 题目:工厂低压配电系统设计 学院:信息与控制工程学院 专业:自动化 ; 班级:三班 学生姓名: 尚帅学号: 指导教师:刘丽

2016年 11月 30日

目录 1 车间的负荷计算及无功补偿 ............................ 错误!未定义书签。 负荷计算的目的、意义及原则.......................... 错误!未定义书签。 工厂负荷情况........................................ 错误!未定义书签。 计算负荷、无功负荷、视在负荷的计算.................. 错误!未定义书签。 无功补偿的主要作用.................................. 错误!未定义书签。 2 确定车间变电所的所址和形式 .......................... 错误!未定义书签。 变电所位置的选择,应根据下列要求经技术、经济比较确定错误!未定义书签。 变电所的形式(类型)................................ 错误!未定义书签。 3 确定车间变电所主变压器型式,容量和台数及主结线方案 .. 错误!未定义书签。 4 短路计算 ............................................ 错误!未定义书签。 计算K-1点的短路电流和短路容量(UC1=10KV) .......... 错误!未定义书签。 计算K-2点的短路电流和短路容量(UC2=).............. 错误!未定义书签。 5 一次设备的选择 ...................................... 错误!未定义书签。 电气设备选择的一般原则.............................. 错误!未定义书签。 高低压电气设备的选择................................ 错误!未定义书签。 6 选择车间变电所高低进出线截面 ........................ 错误!未定义书签。 变压器高压侧进线电缆截面选择........................ 错误!未定义书签。 380V低压出线的选择................................. 错误!未定义书签。 7 选择电源进线的二次回路及整定继电保护。 .............. 错误!未定义书签。 测量与指示.......................................... 错误!未定义书签。 继电保护............................................ 错误!未定义书签。 8 车间变电所的防雷保护及接地装置的设计 ................ 错误!未定义书签。 防直击雷............................................ 错误!未定义书签。 雷器的选择(防雷电波) ................................ 错误!未定义书签。 9 车间变电所主结线电路图 .............................. 错误!未定义书签。心得体会: ............................................. 错误!未定义书签。参考文献: .............................................. 错误!未定义书签。

10KV变电所及其配电系统的设计 --优秀毕业论文

10KV变电所及低压配电系统的设计 摘要:变电所是电力系统的一个重要组成部分,由电器设备及配电网络按一定的接线方式所构成,他从电力系统取得电能,通过其变换、分配、输送与保护等功能,然后将电能安全、可靠、经济的输送到每一个用电设备的转设场所。变电所涉及方面很多,需要考虑的问题多,分析变电所担负的任务及用户负荷等情况,选择所址,利用用户数据进行负荷计算,确定用户无功功率补偿装置。同时进行各种变压器的选择,从而确定变电站的接线方式,再进行短路电流计算,选择送配电网络及导线,进行短路电流计算。选择变电所高低压电气设备,为变电所平面及剖面图提供依据。本变电所的初步设计包括了:(1)总体方案的确定(2)负荷分析(3)短路电流的计算(4)配电系统设计与系统接线方案选择(5)继电保护的选择与整定等容。 关键词:变电所;负荷;输电系统;配电系统

The Design Of 10KV Substation And Power Distribution System Abstract:The substation is an importance part of the electric power system, it is consisted of the electric appliances equipments and the Transmission and the Distribution. It obtains the electric power from the electric power system, through its function of transformation and assign, transport and safety. Then transport the power to every place with safe, dependable, and economical. The region of factory effect many fields and should consider many problems.Analyse change to give or get an electric shock a mission for carrying and customers carries etc. circumstance, make good use of customer data proceed then carry calculation, ascertain the correct equipment of the customer. At the same time following the choice of every kind of transformer, then make sure the line method of the transformer substation, then calculate the short-circuit electric current, choosing to send together with the electric wire method and the style of the wire, then proceeding the calculation of short-circuit electric current. This first step of design included:(1) ascertain the total project (2) load analysis(3) the calculation of the short-circuit electric current (4) the design of an electric shock the system design to connect with system and the choice of line project (5) the choice and the settle of the protective facility (6) the contents to defend the thunder and protection of connect the earth. Keywords:substation;load;transmission system;power distribution system

学校10kv变电所及配电系统设计

目录 1课程设计原始数据 (1) 1.1设计题目 (1) 1.2设计要求 (1) 1.3设计依据 (1) 2负荷计算 (2) 3变电所位置和型式的选择 (4) 3.1根据变配电所位置选择一般原则: (3) 3.2变电所的型式与方案: (4) 4变电所变压器和主接线方案的选择 (5) 4.1主变压器的选择 (5) 5 短路电流的计算 (8) 绘制计算电路 (8) 6变电所一次设备的选择校验 (10) 10KV侧一次设备的选择校验 (10) 0.4KV侧一次设备的选择校验 (11) 7变压所进出线与邻近单位联络线的选择 (11) 7.110KV高压出线的选择: (11) 7.2变电所及邻近单位焦点路线的选择 (12) 7.30.4KV低压出线选择 (12) 设计总结 (13) 参考文献 (15) 附图 (16)

1课程设计原始数据 1.1设计题目 我校10KV变电所及配电系统设计 1.2设计要求 要求根据学校所能取得的电源及学校用电负荷的实际情况,并适当考虑到学校的发展,按照安全、可靠、优质、经济的供配电基本要求,分别设计学生宿舍楼、家属楼、教学楼、办公楼、食堂、实训楼配电间。要求确定变电所的位置与型式,确定变电所主变压器的台数与容量、类型,选择变电所主结线方案及高低压设备和进出线,确定二次回路,选择继电保护装置,确定防雷和接地装置,最后按要求写出设计说明,绘出设计图样。 1.3设计依据 (1)学校总平面图 见附图。 (2)供电电源情况 由长沙供电局树木岭变电站10KV电源供电,电源进线为电缆线,YJV型10kv,学校原有两个箱式配电室,共有两台变压器,其中箱变1#内设有一台变压器,容量为400KVA,箱变2#内设有一台变压器,容量为630KVA。

10KV工厂配电系统设计

工厂供电技术课程设计说明书 题目: 10KV高压变配电系统设计 学院:信息及控制工程学院 专业:自动化

班级:四班 学生姓名: 张泽妮学号: 指导教师:王公仆 2016年11 月30 日

目录 目录 (1) 1 绪论 (1) 1.1 工厂供电的意义和要求 (1) 1.2 设计依据 (1) 1.3 电力系统资料 (2) 2 全厂负荷计算和无功补偿计算 (3) 2.1 变电所1的负荷计算和无功补偿计算 (3) 2.2 变电所2的负荷计算和无功补偿计算 (7) 2.3 变电所3的负荷计算和无功补偿计算 (9) 3 系统主接线方案 (13) 3.1 主接线的基本要求 (13) 3.2 方案1:双回路高压单母线主接线 (13) 3.3 方案2:双回路高压单母线低压单母线分段主接线 (13) 3.4 方案的比较及选择 (14) 4. 变电所位置及变压器选择 (15) 4.1 变压器选择 (15) 4.2 变压器重新选择 (15) 4.3 变电所位置 (15) 5 短路电流计算 (17) 5.1 确定计算电路及计算电抗 (17) 5.2 短路电流计算 (18) 6 变电所一次设备的选择高压断路器的选择 (19) 6.1高压断路器的选择 (19) 6.2高压隔离开关的选择 (19) 7 结论 (21) 参考文献 (1)

1 绪论 1.1 工厂供电的意义和要求 工厂供电,就是指工厂所需电能的供应和分配,亦称工厂配电。 众所周知,电能是现代工业生产的主要能源和动力。电能既易于由其它形式的能量转换而来,又易于转换为其它形式的能量以供应用;电能的输送的分配既简单经济,又便于控制、调节和测量,有利于实现生产过程自动化。因此,电能在现代工业生产及整个国民经济生活中应用极为广泛。在工厂里,电能虽然是工业生产的主要能源和动力,但是它在产品成本中所占的比重一般很小(除电化工业外)。电能在工业生产中的重要性,并不在于它在产品成本中或投资总额中所占的比重多少,而在于工业生产实现电气化以后可以大大增加产量,提高产品质量,提高劳动生产率,降低生产成本,减轻工人的劳动强度,改善工人的劳动条件,有利于实现生产过程自动化。从另一方面来说,如果工厂的电能供应突然中断,则对工业生产可能造成严重的后果。因此,做好工厂供电工作对于发展工业生产,实现工业现代化,具有十分重要的意义。由于能源节约是工厂供电工作的一个重要方面,而能源节约对于国家经济建设具有十分重要的战略意义,因此做好工厂供电工作,对于节约能源、支援国家经济建设,也具有重大的作用。 工厂供电工作要很好地为工业生产服务,切实保证工厂生产和生活用电的需要,并做好节能工作,就必须达到以下基本要求: 安全在电能的供应、分配和使用中,不应发生人身事故和设备事故。 可靠应满足电能用户对供电可靠性的要求。 优质应满足电能用户对电压和频率等质量的要求 经济供电系统的投资要少,运行费用要低,并尽可能地节约电能和减少有色金属的消耗量。 此外,在供电工作中,应合理地处理局部和全局、当前和长远等关系,既要照顾局部的当前的利益,又要有全局观点,能顾全大局,适应发展。 1.2 设计依据 1.生产规模和产品规格:本厂规模5万锭毛纺织厂,年生产能力230万米。 2.车间组成和布置:工厂有一个主厂房,包括制条车间,纺纱车间,织造车间、染整车间等四个车间,还有辅助车间和及其它设施。 3、全厂各车间电气设备及车间变电所负荷计算表。