空调用冷冻站的设计说明书.

空调用冷冻站的设计说明书.
空调用冷冻站的设计说明书.

目录

前言 ......................................................................................................................... 3一设计题目.......................................................................................................... 3二设计目的.......................................................................................................... 3三原始资料.......................................................................................................... 3四设计内容.......................................................................................................... 41 制冷压缩机的型号与台数的选择..................................................................... 41.1 冷冻站的冷负荷的确定 ................................................................................ 41.2 制冷装置型式的选择 .................................................................................... 41.3 制冷工况的确定及理论计算......................................................................... 4

1.4 制冷压缩机的型号及台数的确定............................................................... 6

2 冷凝器的选择 .................................................................................................... 62.1 冷凝负荷的确定 .......................................................................................... 62.2 传热温差...................................................................................................... 7

2.3 确定冷凝器的型号 ...................................................................................... 7

3 蒸发器的选择 .................................................................................................... 8

4 油分离器的选择 ................................................................................................ 8

5 贮液器的选择 .................................................................................................... 8

6 集油器的选择 .................................................................................................... 9

7 急泄氨器的选择 ................................................................................................ 9

8 过滤器的选择 ................................................................................................ 10

9 冷冻站设备及管路的平面布置..................................................................... 109.1冷冻站房的设计 ......................................................................................... 109.2 制冷设备的布置 ...................................................................................... 11

9.3管道布置..................................................................................................... 11

10 管路和阀件的选择计算 .............................................................................. 1210.1管路计算................................................................................................... 1210.2 排气管道................................................................................................ 1310.3 冷凝器到贮液器液体管道..................................................................... 1510.4贮液器到蒸发器液体管道 ....................................................................... 1810.5阀件的选择............................................................................................... 20五参考文献...................................................................................................... 20

前言

本次设计的目的是为了对《空气调节用制冷技术》进行巩固,通过前期上课的理论学习,进行实践。具体内容是针对乌鲁木齐地区,设计其适合的空调用冷冻站的。首先通过查阅当

地的各项原始资料,然后,确定制冷机的工作工况,通过提供的冷负荷资料选定压缩机的型

号和台数。综合冷负荷、工作工况、当地的水质和环境情况,选择合适的冷凝器和蒸发器。

再根据已有的设备资料,结合设计具体要求选择合适的辅助设备:油分离器、高压贮液器、集油器、氨液分离器、紧急泄氨器、空气分离器、过滤器、阀门等。

最后由工厂发展规划资料初步确定工厂尺寸,将设备进行合理的布局。以求做到最经济

合理的布置。并根据设备布局确定管道的布局,计算管道的直径,给管道配置相应的阀门。

以上即是此次设计的流程,在设计过程中,应该注意统筹兼顾,有理有据。

一设计题目

北京宝元大厦空调用冷冻房设计

二设计目的

课程设计是“制冷技术”的主要教学环节之一,通过这一环节来达到了解冷

冻站设计的内容、程序和基本原则的目的,学习设计计算的步骤和方法,巩固所

学的理论知识和实际知识,以培养我们运用所学知识解决工程的能力。

三原始资料

1、基本资料:已知北京空调楼所需总耗冷量为1.6MW,以风机盘管为末端装置,要求冷冻水温为7℃,空调回水温度为12℃,制冷系统以氨为制冷剂;室外气象资料:夏季空调干球温度为33.5℃,湿球温度为26℃。

2、设计地点:北京市

3、压缩机:离心式压缩机

4 、冷凝器:水冷式冷凝器

5、蒸发器:氨卧式管壳蒸发器

6、膨胀阀:浮球式膨胀阀

四设计内容

1 制冷压缩机的型号与台数的选择

1.1 冷冻站的冷负荷的确定

Q T=(1+A)Q y;

式中: Q T——制冷系统的总制冷量(KW);

Q y——用户实际所需要的制冷量(KW);

A——冷损失附加系数;

对于间接式制冷系统,A=0.1~0.15。本课程设计属于此类,取A=0.1

Q=(1+0.1)×1.6=1.76MW

T

1.2 制冷装置型式的选择

本冷冻房设计采用离心式制冷机,氨制冷剂,单级压缩

1.3 制冷工况的确定及理论计算

1.3.1蒸发温度

t

o

一般,用于冷却水或盐水的蒸发器,被冷却液体的温度降(t1-t2)可取5~8℃。蒸发温度t0比被冷却液体的出口温度t2低2~3℃

t=7℃—(2~3℃)=4℃

所以

o

t

1.3.2 冷凝温度

K

水冷式冷凝器,冷凝温度与冷却水进口温度差取7~14℃,冷却水进出口温差取4~10℃

对于使用冷却塔的循环水系统,冷却水进水温度可按下式计算:

s s s t t t ?+=1=26℃+(4~2)℃=30℃

式中 s t ——当地夏季室外平均每年不保证50小时的湿球温度,℃

s t ?——安全值。选用机械通风冷却塔,4~3=?s t ℃。 所以 ℃4414~73014~7t s1=+=+=)()(K t

1.3.3 压缩机的吸汽温度1t

压缩机的吸汽温度一般与压缩机吸汽管的长短和保温情况有关,通常以氨为制冷剂时,吸汽温度1t 与蒸发温度0t 的差值不大于5~8℃。

即 1t = o t +5=4+2=6℃ 1.3.4再冷温度t r.c

对于风冷式冷凝器,均不考虑再冷。

以上工况确定以后,就可在lgP ——h 图上确定整个制冷的理论循环;并进行循环的理论

计算。

1.3.5 lgP-h 上理论循环的计算

1根据绘制的lgP-h 图查表求得各状态参数:

图中点1为压缩机吸入状态点(t 1=t 0=4℃);1-1’为过热过程(t 1’=6℃);2’为制冷剂出压缩机时状态点(由过1’的等熵线和压力为P k 的等压线来确定);4为制冷剂出冷凝器的状态点(t 4=t k =43℃)

2确定压力:P 1= P 0=498.146kpa ;P 4=P k =1737.216kpa ; 确定焓值:h 1=1460.672kJ/kg ;h 1’=1465.643kJ/kg ; h 2’=1644.068kJ/kg ;h 4=409.804kJ/kg;

比容:v 1=0.251916m 3/kg ;v 2’=0.10493 m 3/kg ;

3制冷系统热力计算

单位质量制冷量q 0的计算:q 0=h 1’-h 4=1465.643-409.80=1055.843kJ/kg ; 单位容积制冷量q v 的计算:q v =q 0÷v 1’=1055.843÷0.251916= 491.250kJ/kg ; 制冷剂质量流量q m 的计算:q m =Q T ÷q 0=1760÷1055.843=1.6669kg/s ;

单位理论压缩功w 0的计算:w 0=h 2’-h 1’=1644.068-1465.643=178.425kJ/kg ; 压缩机所需的理论功率P 0的计算:P 0=q m ×w 0=1.6669×159.946=297.416kW ;

压缩机吸入制冷剂蒸汽的体积流量q v 的计算:q v =q m ×v 1’=1.637×0.251916=0.4123m 3/s ; 制冷系数ε0的计算: ε0=q 0÷w 0=1760÷297.416=5.97;

单位冷凝负荷q k 的计算:q k =h 2’-h 4=1644.068-409.804=1234.264kJ/kg ; 冷凝器热负荷Q k 的计算:Q k =q m×q k =1.6669×1234.264=2057.394kW ; 逆卡诺循环制冷系数:εc=T c ÷(T k -T c )=(6+273)/(44-6)=7.346; 制冷效率η=ε0÷εc =5.97÷7.346=0.812;

1.4 制冷压缩机的型号及台数的确定

择制冷压缩机时,台数不宜过多一般2~4台,且系列应相同,方便维修。 标准工况下的制冷量,换算公式

(1RT)=79.63kcal/Kg*1000/24Hr=3318Kcal/hr=3859W 则RT=1760÷3.85=457.14

由麦克维尓提供的产品选择单压缩机水冷离心式, 型号:WSC087MAU49F/E3009C2609 制冷量:500RT=1.925MW 输入功率:315.4KW

2 冷凝器的选择 2.1 冷凝负荷的确定

冷凝器型式的选择应根据制冷剂和冷却介质(水或空气)的种类及冷却介质的品质优劣而定。

在冷却水质较差、水温较高和水量充足的地区,宜采用立式壳管式冷凝器,因为冷却水使用循环水,故采用卧式壳管式冷凝器。冷凝器的台数参考压缩机的台数,暂取一台。

i k P Q Q +≈0 式中 Q k ----冷凝器热负荷; Q 0----制冷机冷负荷; P i ----压缩机指示 一台压缩机的指示功率 i P =

211a h i

V h h v λη-?=

KW 6691.0643

.1465068.1644*2519.010493.0*81.0=- 所以: Q k=2057.394+66=2123.394KW

2.2 传热温差

2

k

1

k 12

t

t t t ln ---=

t t t Δ

式中: t 1、t 2----冷却剂进、出口温度,℃; t k ----冷凝温度,℃ 所以: 38443044ln

3038t t t t ln 2

k 1k 12---=---=

t t t Δ=4℃

冷却剂流量:M=()12t t Cp Q k

-=)

3038(186.4394.2123-?=63.4kg/s

2.3 确定冷凝器的型号

C p 为制冷剂定压比热容:4.187kJ/(kg ·K)

根据推荐值假设冷凝器的单位热负荷q t =3700kcal/(m 2·h)=5000w/m 2; F=

=t

K q Q 50002123394

=424.672m ;

查手册,选择卧式冷凝器LN-450(上海第一冷冻机厂)两台;冷凝面积F=2302m 则: t q =1061697÷451=4616.07w/m 2;

喷淋密度 : n

d G n w

π=

Γ 式中 G w -冷却水量,Kg/h;

d n -管子内径,m; N -管子根数。 则: =Γ63.4÷(3.14×0.051×200)=1.979kg/m.s=7126.2kg/m.h 管内强制对流放热系数 w α=5133

1Γ=9871.959w/2m .k

3 蒸发器的选择

以氨为载冷剂时,可采用卧式壳管式蒸发器,但冷冻水在蒸发器换热管内的流速不得小于1~

2m/s 蒸发器台数与冷凝器、压缩机台数相同。 38443044ln

3038t t t t ln 2

k 1k 12---=---=

t t t Δ=4 ℃

t

k Q F l

??= 其中卧式壳管式蒸发器K 取450~5002/w m 取K=4702/w m

F=2057.39÷1000÷470÷4=1094.32m

由《制冷与空调设备手册》519页 查得选用型号DWZ —360的卧式蒸发器3台 (大冷)

4 油分离器的选择

为了保证制冷装置运行时的安全、可靠和切换灵活,一台压缩机要有一台油分离器。选择油分离器可根据进排汽管径进行,一般要求管内汽体流速为10~25m/s 。或者也可根据油分离器的筒体直径来选择,筒内汽流速度一般要求为0.8~1.0m/s 。两种情况均可按下述公式进行计算:

D ≥

w

v v

V w v v V n h n h ...019.0...3600..41212λπλ= m

式中 D ——油分离器汽管或筒体直径,米; V h ——压缩机理论输汽量,米3/小时; λa ——压缩机输汽系数;

v 1——压缩机吸入汽体的比容,米3/公斤; v 2——压缩机排出汽体的比容,米3/公斤; w ——汽管内或筒体内汽体流速,米/秒

取ω=0.9m/s D>

9

.0*26.0*14.3*36000091

.0*81.0*840*4...3600..412=

w v v V n h πλ=0.096m 由《制冷与空调设备手册》607页查得

选择一台型号SYF-100 北冷式

5 贮液器的选择

贮液器的容积是按制冷剂循环量进行计算的。它应满足下述要求:(1)贮液器贮存制冷剂 的最大量按每小时制冷剂总循环量1/2~1/3的计算;(2)考虑到制冷剂受热膨胀可能带来的危险,贮液器贮存制冷剂的最大量不超过本身容积的80%。 贮液器的容积可按下式计算:

β

v

M V R .)31~21(= 3m

式中 M R ——液体制冷剂循环量,Kg/h ; v ——液体制冷剂比容,m 3/Kg ;

β——液体充满度,一般可取0.8。

根据计算值的大小,可选用单台或多台并联使用的贮液器,本设计中采用一台贮液器

V=0.4*8

.01007.060083

-??=0.23m

由《制冷与空调设备手册》538页查得 选择ZA-0.5 北冷式贮液器

6 集油器的选择

在氨制冷系统中需要装置集油器,以收集和放出从冷凝器、贮液器、蒸发器等设备底部积存的润滑油。通常几套压缩机可共用一个集油器

目前国内生产三种规格的集油器,当冷冻站标准工况下的制冷量小于250~350KW(20~30×104kcal/h)时,采用直径为150mm 的集油器一台;当标准工况下的制冷量为350~600KW(30~50×104kcal/h)时,采用直径为200mm 的集油器一台;当标准工况下的制冷量大于600KW(50×104kcal/h)时,采用直径为300mm 的集油器一台。

本设计中T Q =标36318kcal/h

采用直径为200mm 的集油器 由《制冷与空调设备手册》626页 选择JY-200北冷集油器

7 急泄氨器的选择

在大、中型制冷系统中,系统中的充氨量是较多的。当发生严重事故时,必须将系统中的氨迅速放掉,以保护设备和人身安全,故系统应设置紧急泄氨阀。目前国内生产的紧急泄氨阀为SA -50型,各系统均可选用。 由《制冷与空调设备手册》637页可查得

8 过滤器的选择

过滤器用来清除制冷剂中的机械杂质;结构都比较简单,一般制造厂都成套配给,设计中也可按管径的大小来选用。

9 冷冻站设备及管路的平面布置

9.1冷冻站房的设计

1、氨压缩式制冷装置应布置在隔断开的房间或单独的建筑物内,但不得布置在民用建筑和工业企业辅助建筑物内。规模较小的氨冷冻站,也可附设在一些不重要的厂房的一端,但需要用墙隔开,并且机器设备间与厂房不宜直接连通。另一端要尽量避免西晒

2、冷冻房设计时预留一定面积,以备日后增设设备.

3、冷冻站在工厂总图上的位置应考虑避免将其布置在乙炔站、锅炉房、氢氧站、煤气站、堆煤场、易于散发灰尘和有害汽体站房的近处及其下风向。

4、当冷冻站成为全厂的主要用电负荷或者用电负荷较大时,应考虑将站房靠近电源建筑。

5、布置氨冷冻站站房时,考虑到氨系有毒物质,为确保安全,在机器间和设备间的上、下面和直接相邻的四周,不宜建有宿舍、病房、学校、幼儿园、礼堂、餐厅、游艺场所、商店以及其它人多聚众的地方。如果冷冻站附近有要求防震的工艺设备,而冷冻站又不能离开较远时,压缩机及水泵等设备应采取必要的隔震及减震措施。

6、氨冷冻站宜设于单层建筑中,机器间的操作通道不宜超过12米。并设置两个相互尽量远离的出口,其中至少应有一个出口直接对外,冷冻站发门窗一律向外开,亦应考虑设备的安装要求。

7、冷冻站必须有良好的天然采光,其窗孔投光面积和站房地面的比例不应小于1﹕6。

8、冷冻站的机器间和设备间,应保持良好的自然通风条件。在设计时应尽量安排好穿堂风或采取其它形式的自然通风措施。氨冷冻站内的机器间和设备间内应保证有每小时不少于三次的通风措施,此外还必须设计有每小时不少于七次换气的事故通风装置

9、制冷机房的高度,应根据设备情况确定,并应符合下列要求

对于氨压缩式制冷,不应低于4.8米

10、大、中型制冷站站房可分为机器间和设备间,并应考虑到全厂的具体情况来确定在站房中建有变电间、配电间、水泵间、维修间、储藏间、控制间、值班室等单独的隔间。对于中小型站房,亦可将制冷设备共建在一个房间内

冷冻站设备布置房间长33000mm

冷冻站设备布置房间宽13504mm

冷冻站设备布置房间高5000mm

本设计中共开设18扇窗窗孔投光面积和站房地面的比例大于1﹕6

开设三个门,使得机器间的操作通道不超过12米

9.2 制冷设备的布置

1、压缩机必须设在室内,并应有减震基础。

2、制冷压缩机的所有压力表、温度计和其它仪表,均应设置在操作时便于观察的地方,通常情况下,应使其面向主要操作通道

3、制冷压缩机的进、排汽阀门的手轮应面向主要通道,其高度设置在1.5米以下,超过此高度时,应在制冷压缩机旁设立便于操作的工作台

4、制冷压缩机的主轴拔出端,应留有足够的空间,以便于检修时拆拔出主轴。本设计中压缩机和蒸发器错位排列,方便抽轴维修。

5、立式冷凝器一般情况下均安装在室外,使其距外墙不宜超过5米。对于夏季通风温度高于32℃的地区,在室外安装时应设置有遮阳设,。

6、立式冷凝器布置在室外时,应利用其底部的水池作为基础。冷凝器的水池壁与机器房等建筑物墙面,一般情况下应有不少于3米的间距,冷凝器的安装高度,必须使液体制冷剂借助于重力能通畅地流入高于贮液器内,一般冷凝器岀液口比贮液器高250~300mm以上

6、卧式蒸发器一般情况下均布置在室内

9.3管道布置

1、管路布置应便于装设支架。一般管路应尽可能沿墙、柱、梁布置,而且应考虑到便于维修、不影响室内采光、通风及门窗的启闭。非沿墙敷设的架空水平管道,其安装高度(由室内地坪至管底)经过人行通道时,不应小于2米。管道距墙、柱的距离应考虑安装和检修

的方便,对保温管道还应考虑保温层的厚度。一般管道外表面或保温层最外层距墙、柱距离不小于150mm

2、制冷压缩机的吸汽管道和排汽管道设置在同一支架或吊架上时,应将吸汽管道放在排汽管道的下面。数根平行管道之间应留有一定的间距,以便于管道的安装和检修。一般情况下管道间净间距不小于200mm。

3、设置管道时,除特殊要求外,一般情况下液体管道不应有局部向上凸起的管段,汽体管道不应有局部向下的凹陷的管段,以免产生“汽囊”和“液囊”,阻碍流体的流通。

4、从液体主管接出支管时,一般情况下应从主管底部接出。从汽体主管接出支管时,一般情况下应从主管的上部接出。

5、在钢制的支架或吊架上安装低温管道时,应根据保温层的厚度设置经过防腐处理的木垫块,以防止“冷桥”现象的产生。

6、压缩机吸汽管和排汽管的坡度及坡向,应符合下列要求:

(1)氨制冷压缩机吸汽管坡度,不得小于0.003,应坡向蒸发器;

(2)制冷压缩机排汽管坡度,不得小于0.01,应坡向油分离器或冷凝器。

7、壳管式冷凝器至贮液器之间的液体管内流速不应超过0.5m/s,在接管的水平管段上,应有不小于0.01坡度,坡向贮液器。

8、所有贮存制冷剂且在压力下工作的制冷设备和容器,均应设置安全阀。氨制冷系统的排氨口必须装设排放管,排放管的出口,应高于周围50米内最高建筑物的屋脊5米

9、大、中型氨制冷装置应装设紧急泄氨器,泄氨阀应该装在冷冻站外及便于操作的地点。

10、浮球阀的接管需要考虑正常运转时,液体能通过过滤器、浮球阀而进入蒸发器。在浮球检修或过滤器清洗时,液体由旁通管直接进入蒸发器。

10 管路和阀件的选择计算 10.1管路计算

11.1.1吸气管道

(1)初选管径d 1

4m q v

d u

π=

式中 m q ——流体质量流量,kg/s ; U ——流体速度, m/s ; d ——管子内径 , m ;

V —— 流体在工作压力和工作温度下的比容,3/m kg

其中吸气管流速u 为12~20m/s 取u=15m/s 3

0.24962/

v m k g = 00272.5

0.25/

(1460.873371.411)

m Q q k g s q =

==- 40.250.24961

72.823.1415

n d m m

??=

=? 由《实用制冷工程设计手册》P554查得83d mm =外 δ=3.5mm n d =76mm (2)确定管路的当量总长

最不利管路管长:480+2193+4995+2200+300=10173mm 管路上两个直通截止阀的当量长度: 由《实用制冷工程设计手册》P544查得

d

n

L d =340 ; 34027651680d L mm =??= 管路两个焊接弯头当量长度:

d

n

L d =60 ; 602769210d L mm =??=

蒸发器出口管道缩小,其当量长度: 由《实用制冷工程设计手册》P544查得

76

125d D = ; d n

L d =9.272 ; d L =705mm 压缩机进口管道扩大,其当量长度;

76

82d D = ; d n

L d =2.049; d L =156mm d L =10173+51680+9120+705+156=71934mm

(3)每米当量管长的允许压力降值

氨吸汽管、排汽管和液体管,不宜大于0.5℃ 蒸发温度4℃ 对应饱和压力P=498.47kpa

压缩机吸气温度3.5℃ 对应饱和压力P=489.178Kpa P ?=9.292kpa; 每米当量管长的允许压力降

69.292

1071834

d P L ?=?pa/m (4)由《实用制冷工程设计手册》P547查得 n d =69.5mm<76mm 选择合理 6缸计算同4缸相似 n d =98mm 吸气母管直径d

222

4

6

4

4

4

n n d d d πππ=

+

d=159mm

由《实用制冷工程设计手册》P554查得 取180d mm =外 δ=5mm

10.2 排气管道

6缸压缩机 (1)初选管径d

4m q v

d u

π=

其中吸气管流速u 为15~25m/s 取u=20m/s ; 3

0.123/v m k g

= 00272.5

0.25/

(1460.873371.411)

m Q q k g s q =

==- 40.250.123

44.263.1420

n d m m

??=

=? 由《实用制冷工程设计手册》P554查得68d mm =外 δ=3mm n d =62mm (2)确定管路的当量总长

最不利管路管长:6284+700+1588+500+4240+7650+1966=22928mm 管路上4个直通截止阀的当量长度: 由《实用制冷工程设计手册》P544查得

d

n

L d =340; 34046284320d L mm =??=

管路3个焊接弯头当量长度:

d

n

L d =60; 603629720d L mm =??= 管路中一个逆止阀当量长度:

d

n

L d =80; 801624960d L mm =??= 压缩机出口管道缩小,其当量长度: 由《实用制冷工程设计手册》P544查得

62

65d D = ; d n

L d =1.29; d L =81mm 集油器进口管道缩小,其当量长度;

5062d D =; d n

L d =5.42; d L =336mm

集油器出口管道扩大,其当量长度;

50

62d D =; d n

L d =13.2; d L =816mm 冷凝器进口管道扩大,其当量长度;

62100d D =; d n

L d =18.56 ; d L =1151mm d L =10173+84320+4960+81+336+816+1151=125752mm (3)每米当量管长的允许压力降值

氨吸汽管、排汽管和液体管,不宜大于0.5℃ 冷凝温度35.9℃ 对应饱和压力P=1388.383kpa 压缩机吸气温度36.4℃ 对应饱和压力P=1408.254Kpa P ?=19.871kpa

每米当量管长的允许压力降

3

19.78110158.18/125752

d P pa m L ?=?= (4)由《实用制冷工程设计手册》P547查得 n d =59mm<62mm 选择合理

6缸计算同4缸相似 n d =62mm 吸气母管直径d

222

4

6

4

4

4

n n d d d πππ=

+

d=108mm

由《实用制冷工程设计手册》P554查得 取121d mm =外 δ=4mm

10.3 冷凝器到贮液器液体管道

(1)初选管径d 1

4m q v

d u

π=

其中吸气管流速u 为<0.5m/s 取u=0.4m/s 331.7072310/v m kg =? 00272.5408.7520.3335/(1460.873371.411)

m Q q k g s q +?=

==- 340.3335 1.7072310

42.63.140.4

n d m m

-???==? 由《实用制冷工程设计手册》P554查得54d mm =外 δ=3mm n d =48mm (2)确定管路的当量总长

最不利管路管长:8635+3526+500+717+260=13638mm 管路上2个直通截止阀的当量长度: 由《实用制冷工程设计手册》P544查得

d

n

L d =340 ; 34024832640d L mm =??= 管路3个焊接弯头当量长度:

d

n

L d =60 ; 602488640d L mm =??=: 贮液器进口管道扩大,其当量长度:

由《实用制冷工程设计手册》P544查得

48

70d D = ; d n

L d =17.77 ; d L =854mm 冷凝器进口管道扩大,其当量长度;

4048d D = ; d n

L d =11.33 ; d L =544mm d L =8640+32640+13638+544+854=56316mm

(3)每米当量管长的允许压力降值

21()m i P P P Z Z ρ?=?+?+-

m P R L ?= 式中:R ——每米摩擦阻力 ; L ——管长

2

2

v R d ρλ=

式中: v ——流体速度m/s ; ρ——流体密度kg/3m ; D ——管子内径m ; λ——沿程阻力系数

e vd

R γ==3

6

0.448104136590.20510

--??=? 0.25

0.3164

e

R λ==0.01801

R=2

3

585.860.40.0180117.6748102-?=? 17.6713.638240.m P p a

?=?= 2

2

i v P ρζ

?=∑

式中:

ζ

∑——总的局部阻力系数

由《实用制冷与空调工程手册》P78查得

贮液器进口渐缩 ζ=0.01 (渐缩)

冷凝器出口扩大ζ=0.044(

2148484040

A A ?=?) 弯头ζ=1 (d>40) 截止阀ζ=7.2 (d=48)

ζ

∑=0.01+0.044+1?3+7.2?2=17.454

2

2

585.650.417.454818.0522

i v P pa ρζ??===∑ 21

()m i P P P Z Z ρ?=?+?+-=240.91+818.05+3

26010-??585.65=1211.28pa 每米当量管长的允许压力降值

1211.28

21.5/56.316

d P p a m L ?== (4)由《实用制冷工程设计手册》P547查得 n d =45mm<48mm 选择合理

冷凝器出液管汇合的母管直径

2

2

34

4

n d d ππ=

? d=83.14mm

由《实用制冷工程设计手册》P554查得 取95d mm =外 δ=3.5mm

10.4贮液器到蒸发器液体管道

(1)初选管径d 1

4m q v

d u

π=

其中液体管流速u 为0.5~1.25m/s 取u=0.8m/s 331.7072310/v m kg =?

00272.5408.7520.3335/(1460.873371.411)

m Q q k g s q +?=

==- 340.3335 1.7072310

30.13.140.8n d m m

-???==? (2)确定管路的当量总长

最不利管路管长:708+1380+2930+800+2580+6628+2187+1412=17945mm 管路上4个直通截止阀的当量长度: 由《实用制冷工程设计手册》P544查得

d

n

L d =340 ; 34023750320d L m m =??= 管路8个焊接弯头当量长度:

d

n

L d =60 ; 6083717760d L m m =??= 贮液器出口管道缩小,其当量长度: 由《实用制冷工程设计手册》P544查得

37

70d D = ; d n

L d =10.54 ; d L =391mm 蒸发器进口管道缩小,其当量长度;

3237d D = ; d n

L d =3.78 ; d L =140mm d L =17945+50320+17760+81+391+140=86556mm (3)每米当量管长的允许压力降值

氨吸汽管、排汽管和液体管,不宜大于0.5℃

冷凝温度温度28.5℃ 对应饱和压力P=1388.383kpa 蒸发器金液温度35.4℃ 对应饱和压力P=1368.723Kpa

P ?=19.68kpa 每米当量管长的允许压力降

619.68

10227.38/86556

d P pa m L ?=?=

(4)由《实用制冷工程设计手册》P547查得 n d =59mm<62mm 选择合理 贮液器到调节装置管路直径d

2

2

34

4

n d d ππ=

? ; d=64.69mm

由《实用制冷工程设计手册》P554查得 取73d mm =外δ=3mm

10.5阀件的选择

针对满液式蒸发器应当选怎浮球式膨胀阀 浮球阀的制冷量可根据下式计算:

γ.4.5000p ufq Q ?=

式中:0Q ——浮球阀的容量,亦即蒸发器的制冷量,kcal/h ; u ——流量系数,氨,u =0.3;R -12,u =0.6~0.8; f ——浮球阀通道计算截面积,mm 2;

0q ——蒸发器内制冷剂的单位质量制冷量,kcal/h ;

p ?——浮球阀前后的压力差,一般情况下可近似取o k p p p -=?,kg/cm 2; γ——浮球阀前液体制冷剂的比重,kg/l 。

虑到制冷系统的超负荷运行,计算出的通道截面积f 应加大30~50%后,再选择合适的浮球式膨胀阀

本设计中根据蒸发器进液口的管径来选择膨胀阀即可。

五 参考文献

● 《制冷工程设计手册》编写组.制冷工程设计手册.北京:中国建筑工业出版社,1978年。

● 《制冷与空调设备手册》,国防工业出版社,1987年。

● 《实用制冷工程设计手册》 郭庆堂北京:中国建筑工业出版社,1994年。 ● 《传热学》 杨世铭 高等教育出版社,2006年

《制冷原理与设备》 吴业正 西安交通大学出版社 1997

暖通空调设计毕业设计说明书

摘要 本设计为哈尔滨望江集团办公楼空调系统工程设计。哈尔滨望江集团办公楼属中小型办公建筑,本建筑总建筑面积4138m2,空调面积2833m2。地下一层,地上八层,建筑高度33.9m。全楼冷负荷为191千瓦,全楼采用水冷机组进行集中供给空调方式。 此设计中的建筑主要房间为办公室,大多面积较小,且各房间互不连通,应使所选空调系统能够实现对各个房间的独立控制,综合考虑各方面因素,确定选用风机盘管加新风系统。在房间内布置吊顶的风机盘管,采用暗装的形式。将该集中系统设为风机盘管加独立新风系统,新风机组从室外引入新风处理到室内空气焓值,不承担室内负荷。风机盘管承担室内全部冷负荷及部分的新风湿负荷。风机盘管加独立新风系统由百叶风口下送和侧送。水系统采用闭式双管同程式,冷水泵三台,两用一备;冷却水泵选三台,两用一备。 在冷负荷计算的基础上完成主机和风机盘管的选型,并通过风量、水量的计算确定风管路和水管路的规格,并校核最不利环路的阻力和压头用以确定新风机和水泵。 依据相关的空调设计手册所提供的参数,进一步完成新风机组、水泵、热水机组等的选型,从而将其反应在图纸上,最终完成整个空调系统设计。 关键词:风机盘管加独立新风系统;负荷;管路设计;制冷机组:冷水机组

Abstract The design for the Harbin Wangjiang Design Group office building air conditioning system. Harbin Wangjiang Group is a small and medium-sized office building office buildings, the total floor area of building is 4138m2, air-conditioned area is 2833m2. There are eight floor of the building, building height is 33.9m. Cooling load for the entire floor, 191 kilowatts, the whole floor using Central Cooling Chillers to focus on the way . This design of the main room of the building for office, most of them is very small, and the rooms are not connected, the selected air-conditioning system should be able to achieve independent control of each room, considering the various factors to determine the selection of fan-coil plus fresh air system. Arrangement in the room ceiling fan coil units, using the dark form of equipment. Set the focus on fan-coil system, plus an independent air system, fresh air from the outdoor unit to deal with the introduction of a new wind to the indoor air enthalpy value, do not bear the load of indoor. All bear the indoor fan-coil cooling load and part of its new rheumatoid load. Fan-coil plus an independent air system sent by the Venetian and the under side air delivery. Closed water system with a dual-track program, three cold-water pump, dual-use a prepared; cooling pumps three elections, one prepared by dual-use. In the cooling load calculation based on the completion of the selection of host and fan coil units, and air volume, the calculation of water, the wind pipe and water pipes to determine the specifications of the road and check the resistance to the most disadvantaged and the loop to determine the pressure head new fans and pumps. Based on the relevant manuals provided by air-conditioning design parameters, and further completion of the new air units, water pumps, hot water units, such as the selection, which will be reflected in their drawings, the final design of the entire air-conditioning system Key words: PAU+FCU systems; load; pipeline design; refrigeration machine; Chillers

冰箱制冷系统设计说明书word版本

冰箱制冷系统设计说 明书

冰箱制冷系统设计说明书1.冰箱设计步骤

图1 BCD-348W/H电冰箱制冷系统图 2.冰箱的总体布置 2.1箱体设计要求及形式 电冰箱箱体设计的优劣,直接影响使用性能、外观、耐久性制造成本和市场销售。在进行设计时,要求造型别致、美观大方。除色调要与家庭家具协调外,还必须考虑占地面积小内容积大,宽度、深度与高度的比例合理,有稳定感等。冰箱箱体尺寸见表1。 表1箱体尺寸

2.2箱体外表面温度校核和绝热层厚度 设计箱体的绝热层时,可预先参照国内外冰箱的有关资料设定其厚度,并计算出箱体表面温度t w 。如果箱体外表面温度t w 低于露点温度t d ,则会在箱体表面发生凝露现象,因此箱体表面温度必须高于露点温度,一般t w > t d +0.2 )(i o o o W t t a K t t -- = (1) 国家标准GB8059.1规定,电冰箱在进行凝露实验时 亚温带SN 、温带N 气候条件下,露点温度为19±0.5℃ 亚热带ST 、热带T 气候条件下,露点温度为27±0.5℃ t o t i

在t w > t d 的前提下,计算箱体的漏热量Q 1,并用下面的公式校验绝热层的厚度 1 21) (Q t t A w w -= λδ (2) 1w t ----冰箱外壁温度,℃ 2w t ----冰箱内壁温度,℃ λ-----绝热层导热系数,w/(m.k) A -----传热面积,m 2 校验计算的厚度在设定厚度基础上进行修正,反复计算,直到合理为止。 3.冰箱热负荷计算 总热负荷Q=Q 1+Q 2+Q 3 Q 1---- 箱体的漏热量 Q 2---- 门封漏热量 Q 3---- 除露管漏热量 (1)箱体的漏热量Q 1 由于箱体外壳钢板很薄,而其导热系数很大,所以钢板热阻很小,可忽略不计。内胆多用塑料ABS 成型,热阻较大,可将其厚度一起计入隔热层,箱体的传热可以看做单层平壁的传热。 )(1i o t t KA Q -= (3) (4) 其中:K —— 传热系数,W/m 2·℃; A —— 传热面积,m 2 ; i o a a K 111 ++= λδ

家用空调设计计算说明书

制冷系统课程设计说明书 热能与动力工程专业 目录 一、 设计工况 ............................................ 3 二、 压缩机选型 .......................................... 3 三、 热力计算 ............................................ 5 1、循环工况: ......................................... 5 2、 热力计算: ........................................ 6 四、蒸发器设计计算 (7)

1、设计工况: (7) 2、计算过程: (8) 3、风机的选择 (18) 4、汇总 (18) 五、冷凝器换热计算 (19) 第一部分:设计计算 (19) 一、设计计算流程图 (19) 二、设计计算 (19) 3、计算输出 (25) 第二部分:校核计算 (25) 一、校核计算流程图 (25) 二、计算过程 (26) 六、节流装置的估算和选配 (27) 七、空调电器系统 (28)

一、设计工况 3KW机组,半封闭压缩机,风冷冷凝器,风冷蒸发器,毛细管,制冷剂R22,蒸发温度5℃,过热度20℃,冷凝温度50℃,过冷度5℃ 二、压缩机选型 1、选型条件:制冷量3kW,制冷剂R22,蒸发温度5℃,过热度20℃,冷凝温度50℃,过冷度5℃。 2、选型结果:使用压缩机选型软件select 6,选择型号为DKM-75的半封闭往复式压缩机。 a.其基本参数如下:制冷量3.15kW,输入功率1.06kW,cop为 2.97,电流(400V)2A,质量流量18.9g/s,放热 3.65kWb. b.其技术参数:

空调系设计说明.

民强商业大厦空调系统设计说明 概述 珠海民大以位于珠海香洲区翠前南路,是集商业、办公、酒店等诸多功能于一体城市综合体,共17层,总建筑面积21000平方米 一、商场水冷螺杆式机组系统说明 一层、二层为银行营业和商场,三层至四层为酒楼餐厅或洗浴按摩中心或卡拉OK歌厅,五层为西餐厅或健身中心,空调空调面积约4800平方米。整个空调系统采用二台日立公司高效螺杆(RCUF200WZP)+麦克维尔公司吊顶新风柜和风机盘管提供冷源,吊顶新风柜负责提供新鲜空气,风机盘管负责提供各区域所需冷量,每台风机盘管单独控制,冷量灵活调配,以后业态改变或空间大需变化时容改造,增加热量表就可进行单独计费,无需更改风管,冷却塔为方形横流冷却塔,系统分层计费方式采用超声波热量表,每层一个,如有需要可在各层单独可增加,集中监控管理系统对机房螺杆机、水泵、冷却塔、新风柜、风机盘管进行监控,根椐区域温度设定要求智能化管理控制,在监控室监控制冷系统和各层区间温度,从而降低能能耗,并统计出各区实际使用冷量,进行精准计费,在管理专用电脑实现远程管理,大大降低管理人员人数 空调水系统 1、设备布置 制冷主机设在地下室冷冻机房内,冷却塔设置在综合楼的屋顶。 2、冷冻水系统 冷冻水系统为两管制闭式循环系统,冷冻水循环泵设在地下室的制冷机房,冷冻水膨胀水箱设在综合楼的顶层天面,由给排水的供水管道向膨胀水箱补水。 3、冷却水系统 冷却水循环泵设在地下室的制冷机房,冷却塔设在综合楼的屋顶。由给排水的供水管道向冷却塔补水。 4、冷凝水系统: 根据各建筑,各层的功能不同,冷凝水就近集中排入污水系统,或由立管集中收集至首层排入污水系统。 5、空调方式 各建筑各层均采用水冷式空调机,气流组织按功能及装修要求采用上(侧)送下(侧)回。 6、空调新风及排风 1)新风从外墙防水百页新风口进来,经风柜降温处理后送到各空调区,通过对开多叶调节阀调节新风量。 2)排风量由门窗缝隙及楼梯口正压排出室外或卫生间等处排风机排出室外。 7、空调自动控制 本工程的空调控制采用就地控制+集中智能控制。 1)、抄表维护方便:超声波热量表数据自动采集,分月、分年自动统计和

制冷站设计说明书参考

. I 目录 (一)设计题目与原始条件 (1) (二)方案设计 (1) (三)冷负荷的计算 (1) (四)制冷机组的选择 (1) (五)水力计算 (2) (六)设备选择 (3) (七)设计总结 (6) (八)参考文献 (7)

设计说明书 一、设计题目与原始条件 ××市某办公楼空气调节用制冷机房设计 本工程为××市某办公楼空调用冷源——制冷机房设计,办公楼共五层,建筑面积40000m2,所供应的冷冻水温度为7/12℃。 二、方案设计 该机房制冷系统为四管制系统,即冷却水供/回水管、冷冻水供/回水管系统。 经冷水机组制冷后的7℃的冷冻水通过冷冻水供水管到达分水器,再通过分水器分别送往办公楼的各个区域,经过空调机组的12℃的冷冻水回水经集水器再由冷冻水回水管返回冷水机组,通过冷水机组中的蒸发器实现降温过程。 从冷水机组出来的37℃的冷却水经冷却水供水管到达冷却塔,经冷却塔冷却后返回冷水机组,如此循环往复。 考虑到系统的稳定安全运行,系统中配备补水系统,软化水系统,水处理系统等附属系统。 三、冷负荷的计算 1.面积热指标 q为90~140W/m2[1],取q=110 W/m2 2.根据面积热指标计算冷负荷 Q z=110×40000=4.4×106W 对于间接供冷系统一般附加7%~15%,这里选取12%。 Q= Q z(1+12%)=4.4×106×(1+12%)=4.963×106W=4963kW 四、制冷机组的选择 根据标准,属于较大规模建筑,宜取制冷机组3台,而且三台机组的容量相同。所以每台制冷机组制冷量Q’=4963/3=1654.3 kW 根据制冷量选取制冷机组具体型号如下:[3] 名称:RC系列模块化冷水机组 型号:RC130-13.0

综合办公楼空调系统设计说明书

综合办公楼空调系统设 计说明书 空调系统 过去 50 年以来,空调得到了快速的发展,从曾经的奢侈品发展到可应用于大多 数住宅和商业建筑的比较标准的系统。在 1970 年的美国, 36% 的住宅不是全空气调节就是利用一个房间空调器冷却;到1997年,这一数字达到了 77%,在那年作的第一 次市场调查表明,在美国有超过一半的住宅安装了中央空调 (人口普查局, 1999)。在1998年,83%的新建住宅安装了中央空调 ( 人口普查局, 1999)。中央空调在商业建筑物中也得到了快速的发展,从 1970年到1995年,有空调的商业建筑物的百分比从54% 增加到 73%(杰克森和詹森,1978)。 建筑物中的空气调节通常是利用机械设备或热交换设备完成.在大多数应用中,建筑物中的空调器为维持舒适要求必须既能制冷又能除湿,空调系统也用于其他的场所,例如汽车、卡车、飞机、船和工业设备,然而,在本章中,仅说明空调在商业和住宅 建筑中的应用。 商业的建筑物从比较大的多层的办公大楼到街角的便利商店,占地面积和类型差 别很大,因此应用于这类建筑的设备类型比较多样,对于比较大型的建筑物,空调设 备设计是总系统设计的一部分,这部分包括如下项目:例如一个管道系统设计,空气 分配系统设计,和冷却塔设计等。这些系统的正确设计需要一个有资质的工程师才能 完成。居住的建筑物(即研究对象)被划分成单独的家庭或共有式公寓,应用于这些 建筑物的冷却设备通常都是标准化组装的,由空调厂家进行设计尺寸和安装。 本章节首先对蒸汽压缩制冷循环作一个概述,接着介绍制冷剂及制冷剂的选择,最后介绍冷水机组。 1.1 蒸汽压缩循环

空调系统设计说明书_范文

设计总说明 本设计为上海市某办公楼空调通风系统设计。该办公楼属大型办公建筑,总建筑面积约为55000㎡。地下两层,地上二十八层,建筑总高度为99.6m。地下两层为车库及设备用房,地上二十八层均为办公用房。该建筑的主要功能间有办公室、会议室、接待室等。全楼冷负荷为3080千瓦,全楼采用风冷热泵机组进行集中供给空调方式。 本建筑位于上海市。上海市地处我国东部沿海地区,东经121°43′,北纬31°16′。属于亚热带季风气候区,四季分明,夏热冬冷,春秋短暂,但由于地处沿海,雨季较为分散,以夏季雨量最大。夏季空调室外日平均温度30.4℃,办公室室内温度26℃,湿度65%,室内风速v ≤0.3 m/s;冬季办公室室内温度20℃,湿度40%,室内风速v≤0.2 m/s。 设计的依据主要有同济大学浙江学院毕业设计(论文)任务书《上海市某办公楼空调通风系统设计》、采暖通风与空调设计规范GBJ19—87、HV AC暖通空调节设计指南、高层民用建筑设计防火规范GB50045—95(2005版)、GB 50189-2005 公共建筑节能设计标准、简明通风设计手册等。 考虑该大厦为办公楼,空调的运行时间主要在上班时间,所以计算负荷时本设计取的时间为6—18时。此设计中的建筑主要房间为办公室,大多面积较小,且各房间互不连通,应使所选空调系统能够实现对各个房间的独立控制,综合考虑各方面因素,确定选用风机盘管加新风系统。在房间内布置吸顶式风机盘管,嵌入暗装的形式。将该集中系统设为风机盘管加独立新风系统,新风机组从室外引入新风处理到室内空气焓值,不承担室内负荷。风机盘管承担室内全部冷负荷及部分的新风湿负荷。风机盘管加独立新风系统由百叶风口下送和侧送。水系统采用闭式双管异程式,冷水泵四台,三用一备。 在冷负荷计算的基础上完成主机和风机盘管的选型,并通过风量、水量的计算确定风管路和水管路的规格,并校核最不利环路的阻力和压头用以确定风机和水泵。 通风设计方面,地下室为车库及设备用房,设计成机械送排风为主,自然进排风为辅的方式,其换气每小时不小于6次;卫生间排风设计为排风扇机械排风到外阳台,排风量按每小时不小于10次的换气量计算;考虑到办公室吸烟问题,也采用排风扇机械排风到外阳台,排风量为送风量的80%。电梯前室及楼梯间设计加压送风。 该设计按照建筑结构及其要求制定空调方案,力求能够满足使用的要求,即能够满足办公舒适性。此外还要从空调设计的科学合理性和经济性,以及建筑整体的美观度考虑。中央空调在现代建筑中越来越多的应用,技术也越来越成熟先进。能够有效的管理,一次性投资,后期使用方便,并且不占用建筑的有效空间。本文就是对中央空调的设计到选型,到校核计算的一个说明。从使用性到科学性再到经济性上做到好的结合。方案选择是整体考虑以及设计的总体思想,计算部分是整个设计的基础,绘图部分是与设计施工相联系的实际的走管和安装。三个部分相依相承,都与整个工程密不可分。各个部分都要保证科学合理,正确无误,经济适用。 本设计是真实性课题的典例。其中,有理论的分析计算,有中央空调方案的选择论证,有实际的绘图安装。是一个完整的工程设计实例。设计计算主要有冷负荷的计算,送风量的计算,管路的计算等。冷负荷的计算确定了各个房间的空气状况和调节条件,以及整个工程的负荷量。是确定室内空调调节方案的主要数据。也是选择冷水机组最主要的参考数据。送风量和管路的计算是面向实际设备和管路的数据资料。都是整个设计的基础。 在上面主要阶段完成以后还要对一些具体细节的问题加以论证思考并列出解决方案。比如管

制冷设计说明

安徽建筑大学环能工程学院课程设计说明书 课程:《制冷课程设计》 班级: dddddd 姓名: ccc 学号: qqqq 指导教师:ddd 2012年6月

目录 (一)设计题目与原始条件 (1) (二)方案设计 (2) (三)制冷机组的选择………………………………… 2 (四)水力计算 (4) (五)设备选择……………………………………… 6 (六)制冷机房的注意事项 (11) (七)设计总结 (11) (八)参考文献 (12)

一、设计题目与原始条件 1、课程设计题目 某空调系统制冷站工艺设计 2、原始条件 制冷量为1800Kw,能源为电; 3、课程设计目的 课程设计是《空调用制冷技术》课程的重要教学环节之一,通过课程设计了解空调用制冷站工艺设计的内容、程序和基本原则,学习设计计算方法和步骤,提高运算和制图能力,增强对制冷站中所应用的冷水机组、水泵、冷却塔等设备的认知,巩固所学理论知识。并学习运用这些知识解决工程问题。 二、方案设计 该机房制冷系统为四管制系统,即冷却水供/回水管、冷冻水供/回水管系统。 经冷水机组制冷后的7℃的冷冻水通过冷冻水供水管到达分水器,再通过分水器分别送往各个区域,经过空调机组的12℃的冷冻水回水经集水器再由冷冻水回水管返回冷水机组,通过冷水机组中的蒸发器实现降温过程。 从冷水机组出来的37℃的冷却水经冷却水供水管到达冷却塔,经冷却塔冷却后返回冷水机组,如此循环往复。 考虑到系统的稳定安全运行,系统中配备补水系统,软化水系统,水处理系统等附属系统。 三、制冷机组的选择 1、已知制冷量为1800kw 2、确定冷水机组的型号及台数 (1)制冷机组选型要熟悉机组的性能、特点,才能进行冷水机组主要性能比较机组的性能及特点主要包括:制冷量范围性能系数、调节特点等。 (2)选用制冷机组时台数不宜过多,一般为2—4台,不考虑备用。多机头机组可以选用单台。当采用多台型号相同的机组时,单机容量调节下限常冷量大于最小负荷时,应选用一台小型机组来适应低负荷需要。 ◆确定制冷机组型号后,应记录冷水机组的主要性能参数参数,如下:名义冷量;名义耗功率;名义工况性能系数;冷冻水、冷却水压力损失及水流量,以及机组的外形尺寸运行重量等,为后续设计收集资料。 (一)冷水机组选型 1、冷水机组的简介 ①活塞式冷水机组 ②螺杆式冷水机组 ③离心式冷水机组 ④吸收式冷水机组 前三种都是依靠电能实现制冷循环第四种是依靠热能实现制冷循环的.对于

制冷课程设计说明书

前言 本次设计的目的是为了对《空气调节用制冷技术》进行巩固,通过前期上课的理论学习,进行实践。具体内容是针对乌鲁木齐地区,设计其适合的空调用冷冻站的。首先通过查阅当地的各项原始资料,然后,确定制冷机的工作工况,通过提供的冷负荷资料选定压缩机的型号和台数。综合冷负荷、工作工况、当地的水质和环境情况,选择合适的冷凝器和蒸发器。 再根据已有的设备资料,结合设计具体要求选择合适的辅助设备:油分离器、高压贮液器、集油器、氨液分离器、紧急泄氨器、空气分离器、过滤器、阀门等。 最后由工厂发展规划资料初步确定工厂尺寸,将设备进行合理的布局。以求做到最经济合理的布置。并根据设备布局确定管道的布局,计算管道的直径,给管道配置相应的阀门。 以上即是此次设计的流程,在设计过程中,应该注意统筹兼顾,有理有据。

目录 一设计题目-----------------------------------------------------------------------------------4 二设计目的-----------------------------------------------------------------------------------4 三原始资料---------------------------------------------------------------------------=------4 四设计内容-----------------------------------------------------------------------------------4 1制冷压缩机的型号与台数的选择------------------------------------------------------4 1.1冷冻站的冷负荷的确定--------------------------------------------------------------4 1.2制冷装置型式的选择-----------------------------------------------------------------4 1.3 制冷工况的确定及理论计算-------------------------------------------------------5 1.4 制冷压缩机的型号及台数的确定------------------------------------------------6 2冷凝器的选择------------------------------------------------------------------------------7 2.1冷凝负荷的确定-----------------------------------------------------------------------7 2.2传热温差--------------------------------------------------------------------------------8 2.3确定冷凝器的型号--------------------------------------------------------------------7 3蒸发器的选择------------------------------------------------------------------------------9 4 油分离器的选择-------------------------------------------------------------------------10 5 贮液器的选择--------------------------------------------------------------------------10 6油器的选择-------------------------------------------------------------------------------11 7空气分离器的选择--------------------------------------------------------------------11 8 急泄氨器的选择----------------------------------------------------------------------11

空调毕业设计说明书

……………………. ………………. ………………… 山东农业大学 毕 业 设 计 题目:南京实验楼集中空调系统设计 院 部 水利土木工程学院 专业班级 建筑环境与设备工程2010级3班 届 次 2010 学生姓名 孙晴 学 号 20103496 指导教师 王萌 二O 一四年六月十四日 装 订 线 ……………….……. …………. …………. ………

目录 一. 设计资料及说明 (1) 二. 空调设计方案分析 (2) 三. 负荷计算 (4) 四.空气处理过程设计 (12) 五. 房间气流组织方案设计 (14) 六. 水系统的水力计算 (15) 七.风系统的水力计算 (17) 八. 冷热源的设计和布置 (19) 九.空调设备明细表 (20) 十.空调系统消声减振的设计方案 (22) 十一.空调系统控制和调节 (24) . . . 参考文献 (24) 致谢词 (25) 附录(附件) (26)

南京实验楼集中空调系统设计 作者:孙晴 10建环3班 指导老师:王萌 设计内容简介: 对南京实验楼集中空调系统进行了设计。该实验楼共三层,建筑总面积6738.24m2,其功能包括:实验室、教室、办公室。该中心总冷负荷880.83kw,总热负荷744.02kw。基于冷负荷、湿负荷、热湿比及其功能区特点,并考虑到经济性和可行性,确定出了该实验楼的具体所适用的空调系统方案,并针对此方案进行了水管风管的布置、水力计算、设备选型及设备布置及对设备的消声减振的设计。

1 设计说明及资料 1.1原始资料 1.1.1 设计地区:江苏南京 1.1.2 建筑资料:该实验楼为五层建筑,第一、二、三层有实验室,内厅,卫生间等,第四层有实验室,教室,办公室,卫生间等。第五层有教室,卫生间。现以提供各层结构平面图等。每层层高除二层为5.4m外均为4.5m,吊顶3m(局部可低)1.1.3 室内设计参数 表1-1-1 1.2 室外气象资料和围护结构资料 1.2.1室外气象资料 表1-2-1 1.2.2围护结构资料 外窗-------普通玻璃,传热系数为3.6 w/m2.℃

中央空调设计手册

暖通空调系统设计手册 目录 第一章设计参考规范及标准 (5) 一、通用设计规范: (5) 二、专用设计规范: (5) 三、专用设计标准图集: (5) 第二章设计参数 (6) 一、商业和公共建筑物的空调设计参数ASHRAE (6) 二、舒适空调之室内设计参数日本 (7) 三、新风量 (8) 1、每人的新风标准ASHRAE (8) 2、最小新风量和推荐新风量UK (9) 3、各类建筑物的换气次数 UK (9) 4、各场所每小时换气次数 (9) 5、每人的新风标准UK (10) 6、考虑节能的基本新风量(1/s人)(日本) (10) 7、办公室环境卫生标准日本 (11) 8、民用建筑最小新风量 (11) 第三章空调负荷计算 (15) 一、不同窗面积下,冷负荷之分布% (15) 二、负荷指标(估算)(仅供参考) (15) 三、空调冷负荷法估算冷指标。空调冷负荷法估算冷指标(W/M2空调面积)见下表 (16) 四、按建筑面积冷指标进行估算建筑面积冷指标 (17) 五、建筑物冷负荷概算指标香港 (18) 六、各类建筑物锅炉负荷估算W/M3℃ (19) 七、热损失概算W/M3℃ (19) 八、冷库冷负荷概算指标 (20) 第四章风管系统设计 (21) 一、通风管道流量阻力表 (21) 1、缩伸软管摩擦阻力表 (21) 2、镀锌板风管摩擦阻力表 (21) 二、室内送回风口尺寸表 (24) 1、风口风量冷量对应表 (24) 2、不同送风方式的风量指标和室内平均流速ASHRAE (24) 三、室内风管风速选择表 (25) 1、低速风管系统的推荐和最大流速m/s (25) 2、低速风管系统的最大允许速m/s (25) 3、通风系统之流速m/s (25) 四、室内风口风速选择表 (26) 1、送风口风速 (26) 2、以噪音标准控制的允许送风流速m/s (26)

制冷站设计说明书

目录 (一)设计题目与原始条件 (1) (二)方案设计 (1) (三)冷负荷的计算 (1) (四)制冷机组的选择 (1) (五)水力计算 (2) (六)设备选择 (3) (七)设计总结 (6) (八)参考文献 (7)

设计说明书 一、设计题目与原始条件: 广州市某办公楼空气调节用制冷机房设计 本工程为广州市某办公楼空调用冷源——制冷机房设计,办公楼共五层,建筑面积40000m2,所供应的冷冻水温度为7/12℃。 二、方案设计 该机房制冷系统为四管制系统,即冷却水供/回水管、冷冻水供/回水管系统。 经冷水机组制冷后的7℃的冷冻水通过冷冻水供水管到达分水器,再通过分水器分别送往办公楼的各个区域,经过空调机组的12℃的冷冻水回水经集水器再由冷冻水回水管返回冷水机组,通过冷水机组中的蒸发器实现降温过程。 从冷水机组出来的37℃的冷却水经冷却水供水管到达冷却塔,经冷却塔冷却后返回冷水机组,如此循环往复。 考虑到系统的稳定安全运行,系统中配备补水系统,软化水系统,水处理系统等附属系统。 三、冷负荷的计算 1.面积热指标 q为90~140W/m2[1],取q=110 W/m2 2.根据面积热指标计算冷负荷 Q z=110×40000=4.4×106W 对于间接供冷系统一般附加7%—15%,这里选取12%。 Q= Q z(1+12%)=4.4×106×(1+12%)=4.963×106W=4963kW 四、制冷机组的选择 根据标准,属于较大规模建筑,宜取制冷机组3台,而且三台机组的容量相同。 所以每台制冷机组制冷量Q’=4963÷3=1654.3 kW 根据制冷量选取制冷机组具体型号如下:[3] 名称:RC系列模块化冷水机组 型号:RC130-13.0

上海市某综合楼中央空调系统设计毕业设计说明书

毕业设计(论文)原创性声明和使用授权说明 原创性声明 本人郑重承诺:所呈交的毕业设计(论文),是我个人在指导教师的指导下进行的研究工作及取得的成果。尽我所知,除文中特别加以标注和致谢的地方外,不包含其他人或组织已经发表或公布过的研究成果,也不包含我为获得及其它教育机构的学位或学历而使用过的材料。对本研究提供过帮助和做出过贡献的个人或集体,均已在文中作了明确的说明并表示了谢意。 作者签名:日期: 指导教师签名:日期: 使用授权说明 本人完全了解大学关于收集、保存、使用毕业设计(论文)的规定,即:按照学校要求提交毕业设计(论文)的印刷本和电子版本;学校有权保存毕业设计(论文)的印刷本和电子版,并提供目录检索与阅览服务;学校可以采用影印、缩印、数字化或其它复制手段保存论文;在不以赢利为目的前提下,学校可以公布论文的部分或全部内容。 作者签名:日期:

学位论文原创性声明 本人郑重声明:所呈交的论文是本人在导师的指导下独立进行研究所取得的研究成果。除了文中特别加以标注引用的内容外,本论文不包含任何其他个人或集体已经发表或撰写的成果作品。对本文的研究做出重要贡献的个人和集体,均已在文中以明确方式标明。本人完全意识到本声明的法律后果由本人承担。 作者签名:日期:年月日 学位论文版权使用授权书 本学位论文作者完全了解学校有关保留、使用学位论文的规定,同意学校保留并向国家有关部门或机构送交论文的复印件和电子版,允许论文被查阅和借阅。本人授权大学可以将本学位论文的全部或部分内容编入有关数据库进行检索,可以采用影印、缩印或扫描等复制手段保存和汇编本学位论文。 涉密论文按学校规定处理。 作者签名:日期:年月日 导师签名:日期:年月日

暖通初步设计说明书

暖通空调初步设计说明书 摘要:地下三层,地上十层,框剪结构,空调形式为冰蓄冷,冷辐射吊顶。 1 设计依据 1.1上级批文详见总论部分; 1.2甲方提供的设计任务书; 1.3建筑专业提出的平面图和剖面图; 1.4室外计算参数(北京地区) 夏季空调计算干球温度33.2℃ 夏季空调计算日平均温度28.6℃ 夏季空调计算湿球温度26.4℃ 夏季通风计算干球温度30.0℃ 夏季空调计算相对湿度78 % 夏季大气压力99.86Kpa 夏季平均风速 1.9 m/s 冬季空调计算干球温度-12℃ 冬季通风计算干球温度-5℃ 冬季空调计算相对湿度45 % 冬季大气压力102.04 Kpa 冬季平均风速 2.8 m/s 1.6国家主要规范和行业标准 (1)《采暖通风与空气调节设计规范》GB50019-2003; (2)《高层民用建筑设计防火规范》GB50045-95(2001版); (3)《民用建筑热工设计规范》GB50176-93; (4) 全国民用建筑工程设计技术措施《暖通空调·动力》; (5) 《民用建筑隔声设计规范》GBJ118 1.7 2004年5月19日由中船重工集团组织的《科技研发大厦空调方案研讨会》专家组意见。 2 设计范围

本工程为船舶科技研发大厦,总建筑面积为33928平方米,预留建筑面积为5494平方米,建筑高度为33.99米。地下二﹑三层为停车库及设备用房,层高3.6米;地下一层主要为餐厅﹑厨房﹑多功能厅及档案室,层高5米;首层至八层主要为办公及会议室,首层层高为5.0米,其余为3.9米。 设计范围为采暖、通风、空调、防排烟及冷热源设计。冷冻机房冷却水系统由给排水专业设计。 3 设计原则 满足国家及行业有关规范﹑规定的要求,利用国内外先进的空调技术及设备,创建健康舒适的室内空气品质及环境。 4 空调设计

设计方案说明(格力空调)

第一部分:设计方案说明 格力小型中央空调系统设计方案 一、工程概况 本方案中住宅的建筑室内面积约为多m2空调使用面积约为m2。设有客厅、餐厅、主卧室、次卧、书房。 本工程设计:主机采用格力数码多联家用中央空调机组。 1.电控系统:由主机电控部分、末端内机电控部分、主机与室内机联网控制部分组成。 2.控制方式:各房间室内机就地独立自动控制,主机在电脑控制下自动运行,全部室内机末端可与主机联动。 二、设计参数 (一) 室外气象参数: 夏季空调室外计算干球温度 T=36.5℃ 夏季空调室外计算湿球温度 Ts=27.3℃ 冬季干球温度 T=2.0℃ 冬季空调室外计算相对湿度Ф=82% 大气压力夏季 991.2hPa 冬季 973.2hPa (二)室内设计参数: 三、设计依据 (一)设计采用规范 1.《采暖通风与空气调节设计规范》。GBJ19-87(2001年版) 2.《户用和类似用途冷水热泵机组》国家标准(GB/T18430.2-200119-87) 3.《家用中央空调实用技术手册》(交通出版社) (二)业主要求 1.业主单位提供的建筑平面图; 2.主机与室内机均采用格力产品 3.空调主机按全负荷的计算。 4.空调内外机连接采用紫铜管,冷凝水管采用蓝色UPVC管。 四、设计思想 (一)优化系统设计,确保运行稳定可靠。 (二)室内温度可在一定范围内随意调控,控制器为格力标配的液晶显示智能温控器,其特点为:1.超小型外观设计,大液晶数字显示室内温度。

2.室内自动恒温控制,24小时定时开/关功能。 (三)系统噪音最小化。 (四)尽量提高安装高度,融入装饰之中 (五)降低初投资和运行费用 五、主机、末端选型 经计算总冷负荷为17.5KW,根据使用功能分配要求,考虑到空调区域的使用功能不同,不具有同时使用负荷高峰的可能性(如客厅与卧室一般使用会交替)。总负荷峰值按总末端负荷70%计算.故主机负荷为12kw. 制冷机的选型采用珠海格力空调设备有限公司生产的数码多联家用中央空调一台,型号为GMV-R120W/H,总制冷/制热量为12KW/13KW,制冷/制热用电功率为3.5KW/3.6KW。主机电源为220V、50Hz。脑板的控制下根据负荷变化,自动无级工作保证空调区域温度稳定。 六、空调氟系统及气流组织设计 1.铜管系统 (1)铜管系统: 空调内外机连接采用铜管,闭式循环系统;其管路走向由设计人员、施工人员根据现场具体情况与业主、装修及各施工单位共同协商确定、详见空调平面布置图。 (2)冷凝水系统 空调冷凝水依就近排入卫生间旁通地漏的原则,其管路布置根据现场具体情况与业主、装修单位共同确定。凝结水管路必须保证顺水流方向的斜度1/100,以保证凝结水能自然流畅。 (3)保温材料 冷(热)水路系统管道保温密闭,采用材料为橡塑福乐斯,外缠扎带。 2.气流组织 气流组织决定房间空调效果,本设计采用侧送下回风方式(详见空调方案设计图)。由施工人员根据现场具体情况与业主、装修单位共同确定,其开口及表面美饰由装修单位处理。 七、施工说明与其它注意事项 (一)在工程施工过程中,施工人员应多协调业主、装修及各工种,及时解决工程问题,做到气流组织合理,装修美观,空调安装方便,达到业主与设计要求;并保质、保量,按期完成工程内容。 (二)空调铜管系统管道保温连接处不能有缝隙,保温材料无破损。 (三)冷凝水管路必须保证凝结水自流畅通。

制冷技术课程设计报告书

科技学院 环境科学与工程学院课程设计说明书 课程名称:空调用制冷技术课程设计 题目:商业办公综合楼冷冻站设计 学生:胡海旭学号: 系别:环境学院 专业班级:建筑设备z1211

指导老师:志高翠敏 2015年10月 目录 1 设计目的 2 2 设计任务 2 3 负荷计算 2 4 机组选择 2 5 方案设计 3 6 水力计算 4 4 6.1 冷冻水的水力计算 6.1.1确定水流量 6.1.2确定管径

6.1.3水力计算结果 6.2 冷却水水力计算 7 6.2.1水力计算结果 7 设备选择7 7.1 冷却塔的选择7 8 7.2 水泵选择 7.2.1冷冻水泵的选择 7.2.2冷却水泵的选择 8 参考文献11 附录 一、设计目的 课程设计是《空气调节用制冷技术》教学中一个重要的实践环节,综合运用所学的有关知识,在设计中掌握解决实际工程问题的能力,进一步巩固和提高理论知识。通过课程设计,了解工程设计的容、方法及步骤,培养确定空调冷冻站的设计方案、进行设计计算、绘制工程图、使用技术资料、编写设计说明书的能力。 二、设计任务

商业办公综合楼冷冻站设计 (一)设计原始资料 1、建筑物概况:建筑面积:10200㎡ 层数3层,层高4.8米 2、参数条件:空调冷冻水参数:供水7℃,回水12℃ 冷却水参数:进水32℃,出水37℃ 三、负荷计算 空调负荷指标:q=250~350 W/㎡。本设计取250/㎡,则建筑总负荷为Q=250×10200=2550KW 建筑物的最小冷负荷为设计冷负荷的15%,则q min=2550×15%=382.5KW 四、机组选择 在选择制冷机的计算中,应考虑到管道系统及设备的冷损失,故间接供冷系统一般附加7%~15%富裕量。则制冷机组承担的制冷量为 W=Q×(1+10%)=2550×(1+10%)=2805KW 为了满足最小冷负荷下的工作情况,最小冷负荷考虑富裕量之后得出的值为q min =382.5×(1+10%)=420.75KW,分别按承担负荷

家用空调设计计算说明书模板

家用空调设计计算 说明书

制冷系统课程设计说明书 热能与动力工程专业 目录 一、 设计工况 .................................................................................... 4 二、 压缩机选型 ................................................................................ 4 三、 热力计算 (6) 1、循环工况:............................................................................. 6 2、 热力计算: ............................................................................ 7 四、蒸发器设计计算 . (8)

文档仅供参考 1、设计工况: (8) 2、计算过程: (9) 3、风机的选择 (19) 4、汇总 (19) 五、冷凝器换热计算 (20) 第一部分:设计计算 (20) 一、设计计算流程图 (20) 二、设计计算 (21) 3、计算输出 (27) 第二部分:校核计算 (28) 一、校核计算流程图 (28) 二、计算过程 (29) 六、节流装置的估算和选配 (30) 七、空调电器系统 (31)

一、设计工况 3KW机组,半封闭压缩机,风冷冷凝器,风冷蒸发器,毛细管,制冷剂R22,蒸发温度5℃,过热度20℃,冷凝温度50℃,过冷度5℃ 二、压缩机选型 1、选型条件:制冷量3kW,制冷剂R22,蒸发温度5℃,过热度20℃,冷凝温度50℃,过冷度5℃。 2、选型结果:使用压缩机选型软件select 6,选择型号为DKM-75的半封闭往复式压缩机。 a.其基本参数如下:制冷量3.15kW,输入功率1.06kW,cop 为2.97,电流(400V)2A,质量流量18.9g/s,放热3.65kW b. b.其技术参数: